Failure to Maintain and Document Required Emergency Battery Backup Lighting Tests
Summary
The deficiency involves the facility’s failure to maintain and document required testing of emergency battery backup lighting in accordance with NFPA 101 standards. During a record review conducted with the Maintenance Director, surveyors requested documentation for the required monthly 30-second functional tests and the annual 90-minute tests of the facility’s battery backup emergency lights. For all 3 of 3 sampled battery backup emergency lights, no documentation was provided to show that the monthly 30-second tests had been performed. Similarly, no documentation was available to demonstrate that the required annual 90-minute battery backup lighting tests had been conducted for the same 3 of 3 emergency lights. The Maintenance Director, interviewed concurrently with the record review, acknowledged the lack of documentation. The deficiency was determined to affect all residents and staff in the facility and was discussed with the Administrator and the Maintenance Director during the exit conference.
Plan Of Correction
The statement made on this Plan of Correction are not and do not constitute an agreement with the alleged deficiencies herein. To remain in compliance with all federal and state regulations the center has taken or will take the actions set forth in the following plan of correction. The following plan of correction constitutes the centers allegation of compliance such that all alleged deficiencies cited have been or will be corrected by the date indicated. K291 Emergency Lighting It is the practice of this facility to maintain emergency battery backup lighting. Immediate Corrective Action: The Maintenance Director was in-serviced on the required monthly and annual testing for emergency battery backup lighting. The 3 of 3 emergency battery backup lights were tested. Identification of other residents potentially affected: All residents have the potential to be affected by this practice. Measures: Maintenance Director and/or designee will in-service the Maintenance Assistants on the required monthly and annual testing for emergency battery backup lighting. Monitoring: Maintenance Director will complete monthly audits for three months, to ensure that the monthly test is being completed. Results of these audits will be reviewed by the QA committee during monthly meetings to ensure continued compliance. K0291 The statement made on this Plan of Correction are not and do not constitute an agreement with the alleged deficiencies herein. To remain in compliance with all federal and state regulations the center has taken or will take the actions set forth in the following plan of correction. The following plan of correction constitutes the centers allegation of compliance such that all alleged deficiencies cited have been or will be corrected by the date indicated. K291 Emergency Lighting It is the practice of this facility to maintain emergency battery backup lighting. Immediate Corrective Action: The Maintenance Director was in-serviced on the required monthly and annual testing for emergency battery backup lighting. The 3 of 3 emergency battery backup lights were tested. Identification of other residents potentially affected: All residents have the potential to be affected by this practice. Measures: Maintenance Director and/or designee will in-service the Maintenance Assistants on the required monthly and annual testing for emergency battery backup lighting. Monitoring: Maintenance Director will complete monthly audits for three months, to ensure that the monthly test is being completed. Results of these audits will be reviewed by the QA committee during monthly meetings to ensure continued compliance.
Penalty
Trusted data from CMS and state health departments
Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.
Trusted by long-term care providers and associations.