K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
F

Failure to Perform and Document Annual 90‑Minute Emergency Battery Lighting Test

Glades Health Care CenterPahokee, Florida Survey Completed on 04-29-2026

Summary

The deficiency involves the facility’s failure to perform and document required annual 90‑minute testing of battery-powered emergency lighting in accordance with NFPA 101 (2012 and 2021 editions), Sections 18.2.9.1 and 19.2.9.1. During a record review conducted between 9:15 AM and 1:30 PM with the Maintenance Director, surveyors were unable to locate documentation showing that the annual 90‑minute emergency battery lighting test had been completed. The Maintenance Director acknowledged that the facility could not provide documentation that this required annual 90‑minute testing of the battery lighting was performed. The deficiency was cited as affecting all occupants of the building under NFPA 101 2012 and 2021, 19.2.9.1, Class III. No specific residents, medical histories, or clinical conditions were mentioned in the report, and the findings were limited to the facility’s emergency lighting testing and documentation practices as observed during the surveyor’s record review and staff interview.

Plan Of Correction

Preparation and/or execution of the Plan of Correction does not constitute admission or agreement of the provider of the truth of the facts alleged or conclusions set forth in the statement of deficiencies. The Plan of Correction is prepared and/or executed solely because it is required by the provision of Federal and State law. The 90 minute battery lighting test was completed and documentation is placed in the maintenance director book. The facility has determined that all residents have the potential to be affected. An in-service education program will be conducted by the administrator. The administrator will conduct for three months random checks of completed documentation. Preparation and/or execution of the Plan of Correction does not constitute admission or agreement of the provider of the truth of the facts alleged or conclusions set forth in the statement of deficiencies. The Plan of Correction is prepared and/or executed solely because it is required by the provision of Federal and State law. The 90 minute battery lighting test was completed and documentation is placed in the maintenance director book The facility has determined that all residents have the potential to be affected. An in-service education program will be conducted by the administrator. The administrator will conduct monthly random checks to verify completed documentation.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0291 citations
Failure to Document Required Annual 90‑Minute Emergency Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not have documentation showing completion of the required annual 90‑minute test of emergency lighting. During record review and interview, the Director of Facilities confirmed that records of this annual test, required under NFPA 101 sections 19.2.9.1 and 7.9, were not available. This deficiency was cited as affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Required Emergency Battery Backup Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility failed to maintain and document required testing of emergency battery backup lighting in accordance with NFPA 101. During record review with the Maintenance Director, no documentation was available for the monthly 30-second tests or the annual 90-minute tests for all sampled battery backup emergency lights. The Maintenance Director acknowledged the absence of these records, and the deficiency was determined to affect all residents and staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Required Emergency and Exit Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or document required monthly and annual inspections of battery back-up emergency and exit lighting in accordance with NFPA 101 standards. During record review, no evidence was available to show that emergency lights throughout the building had been tested for the required 90-minute annual duration, despite multiple requests for documentation. The Maintenance Director confirmed that the documentation could not be produced, and this deficiency potentially affected all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Emergency Lighting Testing
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

The facility did not provide documentation to verify that required monthly and annual tests of battery-powered emergency lighting were performed, as confirmed by both document review and interviews with the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Emergency Lighting Test
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors determined that the facility did not conduct or document the required annual 90-minute test of battery backup emergency lighting. This was confirmed by facility leadership during the survey process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Conduct Monthly Emergency Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

The facility did not perform or document required monthly emergency lighting tests for several months, as confirmed by record review and the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙