K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
C

Lack of Documentation for Emergency Lighting Testing

Kadima Rehabilitation & Nursing At LititzLititz, Pennsylvania Survey Completed on 07-01-2025

Summary

The facility failed to provide documentation verifying that monthly and annual testing of battery-powered emergency lighting had been performed, as required by NFPA 101 standards. During a document review, it was found that there was no record of these required tests for the emergency lighting sources. This was confirmed in an interview with the DON and Director of Maintenance, who acknowledged that documentation for the testing of installed back-up emergency lighting could not be provided. No information regarding specific residents, their medical history, or their condition at the time of the deficiency was included in the report.

Plan Of Correction

1. The facility is unable to retroactively perform this testing. 2. Monthly and annual battery-powered emergency lighting tests were completed in July. 3. The Environmental Services Director was re-educated on the requirements of K0291. Monthly battery-powered emergency lighting tests are scheduled. Annual testing will occur in July of each year. 4. The NHA or designee will complete an audit of the battery-powered emergency lighting testing monthly x 6 months. Annual testing will be confirmed in July. The results will be submitted to the QAPI Committee for review and analysis of need for ongoing monitoring.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0291 citations
Failure to Document Required Annual 90‑Minute Emergency Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not have documentation showing completion of the required annual 90‑minute test of emergency lighting. During record review and interview, the Director of Facilities confirmed that records of this annual test, required under NFPA 101 sections 19.2.9.1 and 7.9, were not available. This deficiency was cited as affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Annual 90‑Minute Emergency Battery Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or could not document the required annual 90‑minute test of battery-powered emergency lighting as required by NFPA 101 (2012 and 2021). During a record review with the Maintenance Director, no records were available to show that the annual 90‑minute emergency lighting test had been completed, and the Maintenance Director acknowledged the absence of this documentation, resulting in a cited deficiency affecting all occupants of the building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Required Emergency Battery Backup Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility failed to maintain and document required testing of emergency battery backup lighting in accordance with NFPA 101. During record review with the Maintenance Director, no documentation was available for the monthly 30-second tests or the annual 90-minute tests for all sampled battery backup emergency lights. The Maintenance Director acknowledged the absence of these records, and the deficiency was determined to affect all residents and staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Required Emergency and Exit Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or document required monthly and annual inspections of battery back-up emergency and exit lighting in accordance with NFPA 101 standards. During record review, no evidence was available to show that emergency lights throughout the building had been tested for the required 90-minute annual duration, despite multiple requests for documentation. The Maintenance Director confirmed that the documentation could not be produced, and this deficiency potentially affected all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Emergency Lighting Test
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors determined that the facility did not conduct or document the required annual 90-minute test of battery backup emergency lighting. This was confirmed by facility leadership during the survey process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Conduct Monthly Emergency Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

The facility did not perform or document required monthly emergency lighting tests for several months, as confirmed by record review and the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙