K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
F

Failure to Provide Emergency Lighting at Main Electrical Room Transfer Switch

The Laurels Of Carson CityCarson City, Michigan Survey Completed on 04-24-2025

Summary

During an observation on April 24, 2025, at approximately 10:29 am, it was found that the facility did not provide a battery pack emergency light at the transfer switch located in the main electrical room. This was identified as a failure to ensure automatic emergency lighting in accordance with section 7.9. The deficiency was confirmed through an interview with the facility's environmental supervisor at the time of the observation. This deficiency could affect all occupants, staff, and visitors in the event that the emergency power systems fail to operate as designed during an electrical utility power outage.

Plan Of Correction

K291 Emergency Lighting SS=F 1. A battery pack emergency light was installed at the transfer switch located in the main electrical room on 5/15/25. 2. Residents residing within the facility have the potential to be affected. 3. Facility administrator has re-educated the maintenance director on the regulatory requirement for an emergency backup light at the transfer switch. The facility preventative maintenance system (TELS) has been updated to ensure that back up lighting is testing per regulatory standards. 4. Facility Administrator and/or designee will verify regulatory compliance with emergency backup lighting monthly x4. Findings will be reported to the QAPI committee for further review and/or recommendations. The Administrator is responsible for sustained compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0291 citations
Failure to Document Required Annual 90‑Minute Emergency Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not have documentation showing completion of the required annual 90‑minute test of emergency lighting. During record review and interview, the Director of Facilities confirmed that records of this annual test, required under NFPA 101 sections 19.2.9.1 and 7.9, were not available. This deficiency was cited as affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Annual 90‑Minute Emergency Battery Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or could not document the required annual 90‑minute test of battery-powered emergency lighting as required by NFPA 101 (2012 and 2021). During a record review with the Maintenance Director, no records were available to show that the annual 90‑minute emergency lighting test had been completed, and the Maintenance Director acknowledged the absence of this documentation, resulting in a cited deficiency affecting all occupants of the building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Required Emergency Battery Backup Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility failed to maintain and document required testing of emergency battery backup lighting in accordance with NFPA 101. During record review with the Maintenance Director, no documentation was available for the monthly 30-second tests or the annual 90-minute tests for all sampled battery backup emergency lights. The Maintenance Director acknowledged the absence of these records, and the deficiency was determined to affect all residents and staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Required Emergency and Exit Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or document required monthly and annual inspections of battery back-up emergency and exit lighting in accordance with NFPA 101 standards. During record review, no evidence was available to show that emergency lights throughout the building had been tested for the required 90-minute annual duration, despite multiple requests for documentation. The Maintenance Director confirmed that the documentation could not be produced, and this deficiency potentially affected all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Emergency Lighting Testing
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

The facility did not provide documentation to verify that required monthly and annual tests of battery-powered emergency lighting were performed, as confirmed by both document review and interviews with the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Emergency Lighting Test
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors determined that the facility did not conduct or document the required annual 90-minute test of battery backup emergency lighting. This was confirmed by facility leadership during the survey process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙