K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
F

Failure to Perform and Document Annual Duct Detector Differential Testing

Stratford Court Of Boca RatonBoca Raton, Florida Survey Completed on 04-30-2026

Summary

Surveyors identified a deficiency related to the facility’s fire alarm system testing and maintenance, specifically the required annual Duct Detector Differential testing. During record review conducted between 11:30 AM and 3:00 PM, surveyors requested documentation demonstrating that this annual testing had been completed in accordance with NFPA 101 (2012 and 2021 editions), NFPA 70, and NFPA 72. The facility was unable to produce records showing that the Duct Detector Differential testing had been performed as required. In an interview conducted during the same time frame, the Director of Facilities acknowledged that the facility failed to provide documentation of the annual Duct Detector Differential testing. The deficiency was cited under NFPA 101 2012 (19.2.9.1, 7.9) and NFPA 101 2021 (19.2.9.1, 7.9), indicating noncompliance with the standards that require fire alarm detection systems, including duct detectors, to be tested and maintained annually. The report notes that this deficiency could affect all occupants of the facility in the event of a fire or other emergency.

Plan Of Correction

Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Fire Alarm System - Testing and Maintenance K0345 1. On The facility a certified fire alarm vendor to perform annual duct detector differential testing. All required testing has now been completed and documented. 2. All residents and staff were considered at risk due to lack of documented testing. A facility-wide review of all fire alarm components was conducted on 3. The facility established a service agreement to ensure all fire alarm testing (including duct detectors) is completed annually per NFPA 72 and NFPA 101 requirements. A compliance calendar has been implemented with alerts for required inspections and testing. The Director of Facilities/designee has been re-educated on required testing intervals and documentation. 4. The Director of Facilities or designee will audit for 3 months all documentation for the annual testing and inspection of the duct detector pressure differential test. The Director of Facilities will present the findings of site inspections for 3 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Fire Alarm System - Testing and Maintenance K0345 1. On The facility a certified fire alarm vendor to perform annual duct detector differential testing. All required testing has now been completed and documented. 2. All residents and staff were considered at risk due to lack of documented testing. A facility-wide review of all fire alarm components was conducted on. 3. The facility established a service agreement to ensure all fire alarm testing (including duct detectors) is completed annually per NFPA 72 and NFPA 101 requirements. A compliance calendar has been implemented with alerts for required inspections and testing. The Director of Facilities/designee has been re-educated on required testing intervals and documentation. 4. The Director of Facilities or designee will audit for 3 months all documentation for the annual testing and inspection of the duct detector pressure differential test. The Director of Facilities will present the findings of site inspections for 3 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0345 citations
Missing Required Fire Alarm System Inspection and Testing Documentation
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

The facility did not maintain required inspection and testing documentation for its fire alarm system. During surveyor review, no records could be produced to show that semi-annual visual inspections or the two-year smoke detector sensitivity testing had been completed, and the maintenance supervisor confirmed that this documentation was unavailable at the time of the survey. This deficiency affected the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Properly Test Fire Alarm System Components
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and properly test multiple fire alarm system components, including smoke detectors near the medical supply area and house laundry that could not be located, elevator fire hat and primary recall functions that could not be reset due to lack of a key, and an untested elevator control shunt trip. On revisit, the missing smoke detectors had been replaced with battery-operated units that were not connected to the building’s fire alarm notification system, and the previously identified fire alarm issues remained uncorrected.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Fire Alarm Documentation and Testing Records
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain required fire alarm system documentation and testing records. During record review with the Maintenance Director, there was no vendor-signed log book at the fire panel documenting work performed at each visit, no documentation of biennial smoke detector sensitivity testing, and no fire alarm system design plans located at the fire panel, as required by NFPA 101 and NFPA 72.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Alarm System in Proper Working Order
D
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors identified that the facility did not maintain its fire alarm system in accordance with NFPA 72 when the fire alarm control panel was observed displaying a trouble signal. During the observation, the Maintenance Director confirmed that the trouble condition was related to a faulty heat detector. This unresolved trouble indication showed that the fire alarm system was not being properly maintained to ensure it functioned as designed for the entire building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Semi-Annual Fire Alarm System Inspections
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors determined that the facility did not comply with NFPA 101 and NFPA 72 requirements for fire alarm system maintenance when record review showed incomplete fire alarm inspection reports and no documentation of required semi-annual visual inspections of fire detection components. The Director of Maintenance confirmed that these six-month inspections had not been documented and reported being unaware of the requirement, creating a deficiency that had the potential to affect all four residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Fire Alarm System per NFPA Requirements
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and document its fire alarm system in accordance with NFPA 101 and NFPA 72, potentially affecting all residents. The only annual fire alarm record provided was a single page without a device list, and there was no documentation of required semi-annual visual inspections or sensitivity testing of devices. During the tour, surveyors observed multiple fire alarm breakers in various electrical panels that were not marked in red, not secured from unauthorized access, and in one case left in the off position, with panel labeling insufficient to identify the presence of a fire alarm breaker. These findings were confirmed with the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙