Surveyors found that the facility did not have documentation showing completion of the required annual 90‑minute test of emergency lighting. During record review and interview, the Director of Facilities confirmed that records of this annual test, required under NFPA 101 sections 19.2.9.1 and 7.9, were not available. This deficiency was cited as affecting all occupants in the event of a fire or other emergency.
Surveyors found that the facility failed to perform and/or document the required annual Duct Detector Differential testing for the fire alarm system in accordance with NFPA 101, NFPA 70, and NFPA 72. During record review and interviews with the Director of Facilities, no documentation could be produced to show that this annual testing had been completed, and the Director acknowledged the lack of records. This deficiency was cited as potentially affecting all occupants in the event of a fire or other emergency.
Surveyors found that the facility failed to perform and/or document required annual testing and exercising of main and feeder circuit breakers in accordance with NFPA 99 and manufacturer recommendations. During record review, no documentation could be produced to show that the annual breaker exercises had been completed, and the Director of Facilities acknowledged this lack of records. This deficiency relates to the essential electrical system that supports life safety and critical branches during emergencies.
Surveyors observed that an adapter was used to power a refrigerator in the kitchen and a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities confirmed both uses, which did not comply with NFPA 99 and NFPA 70 requirements prohibiting adapters and power strips from being used as substitutes for permanent wiring.
Surveyors found that food service operations failed to meet professional food safety standards in both the main and satellite kitchens. In the main kitchen, a cook’s facial hair was not fully covered, the handwashing sink did not initially provide warm water, wet-nested pans and dirty plate domes were stored for use, ice buckets were stained with mold-like discoloration, and the high-temp dishwasher failed to reach the required sanitizing temperature. In the satellite pantry, the dishwasher did not reach required wash temperatures, vents and cabinets above serving dishes had mold-like buildup and residue, floors were damaged and soiled, the dishwasher chemical cabinet was rusted, the AC filter was heavily soiled, the juice dispenser had debris near clean cups, and tray carts contained dirty sheet trays. During tray line observation, salad items were held above 41°F, and a pureed vegetable listed on the menu extension was not available on the line.
Two residents on physician-ordered modified diets (pureed and mechanical soft with nectar-thick liquids) were given Regular Menus listing items such as fresh fruit, salad greens, and grilled cheese that were not compatible with their diet orders. Both residents selected items from these Regular Menus, but the facility either could not provide the chosen foods due to diet restrictions or substituted different items (e.g., canned peach halves instead of fresh fruit), despite the residents’ expressed preferences. The RD and dietetic technician confirmed that Regular Menus were routinely provided to all residents, including those on mechanically altered diets, leading to menu choices that did not align with ordered diet consistencies.
Surveyors found that the facility did not follow physician-ordered therapeutic diets or provide prescribed Magic Cup nutritional supplements for several cognitively impaired residents. A resident on a pureed diet with honey-thick liquids was served a lunch without the ordered pureed vegetable, and tray line review on another day showed no pureed vegetables available despite the menu specifying them. Multiple residents with orders for Magic Cup supplements had these listed on their meal tickets but were instead served other desserts or received no supplement at all, while documentation on the MAR indicated full consumption. Dietary staff acknowledged responsibility for providing Magic Cups but could not explain why residents in the dining room did not receive them.
Surveyors determined that the facility did not comply with FAC 59A-4.126 when it failed to conduct and/or maintain documentation of the required semi-annual testing of its comprehensive emergency management plan for internal or external disasters. During record review and interviews with the Director of Facilities and the Administrator, the facility was unable to produce records showing that these emergency plan drills or tests had been performed, and leadership acknowledged the lack of documentation. This Class III deficiency was identified as potentially affecting all occupants during a fire or other emergency.
Two residents on physician-ordered modified diets (pureed and mechanical soft with nectar-thick liquids) were routinely given Regular Menus listing items such as fresh fruit, salad greens, stir-fried vegetables, and grilled cheese sandwiches that were not compatible with their diet orders. One resident with severe cognitive impairment had a pureed, honey-thick diet but received a Regular Menu with no appropriate options, while another resident with moderate cognitive impairment selected fresh fruit from a Regular Menu but was served canned peach halves instead and voiced dissatisfaction. The RD and dietary manager confirmed that Regular Menus were provided to all residents, including those on mechanically altered diets, resulting in residents being offered choices that could not be honored according to their prescribed diet consistencies.
Surveyors identified that the facility did not follow physician-ordered therapeutic diets or provide ordered nutritional supplements. A resident on a pureed, honey-thick diet with severe cognitive impairment was repeatedly served lunches without the ordered pureed vegetable, and tray line review showed no pureed vegetables available despite the menu specifying them. In addition, several residents with orders for 4 oz Magic Cup supplements at meals did not receive them as listed on their meal tickets; one was given regular desserts instead, even though the MAR documented full consumption of the supplement. The RD and dietary manager confirmed that dietary staff were responsible for Magic Cups but could not explain the failures in provision.
The facility failed to maintain professional standards for food service safety, with issues such as open garbage bins, undated and improperly stored food, and incorrect food temperatures observed in the main and satellite kitchens. These deficiencies were acknowledged by the facility's Administrator, potentially affecting 48 residents.
The facility failed to ensure a clean environment in four resident rooms, where AC filters and vents were found with a black mold-like substance. Residents in these rooms, who were on oxygen therapy, reported issues such as shortness of breath. Despite routine cleaning by maintenance staff, the mold-like substance persisted, indicating a lapse in maintaining a safe and sanitary environment.
A resident with severe cognitive impairment experienced significant weight loss due to inadequate nutritional monitoring and intervention. The facility failed to provide timely and consistent administration of prescribed nutritional supplements, and the Certified Dietary Manager discontinued a high-calorie supplement without an alternative plan. Staff interviews revealed a lack of coordination and awareness regarding the resident's nutritional needs.
A resident with end-stage renal disease missed dialysis treatments due to transportation issues and lack of coordination between the LTC facility and the dialysis center. The resident required a stretcher for transport due to a recent hip fracture, but transportation arrived with inappropriate equipment. Additionally, a positive Covid-19 test further complicated the situation, leading to hospitalization.
The facility failed to properly manage controlled substances for two residents, leading to discrepancies in medication reconciliation. A Buprenorphine patch was not discarded as required, and a tablet of Oxycodone-Acetaminophen was removed without a physician order or documentation. These actions highlight failures in medication management processes.
The facility failed to maintain a medication error rate below 5%, resulting in a 10.34% error rate affecting two residents. Errors included omitted medications and incorrect administration, with discrepancies in documentation and availability of prescribed medications.
The facility failed to provide the correct diet consistency for two residents on a Pureed diet. Both residents, with severe cognitive impairments, were served Cream of Mushroom soup that was lumpy and thick, contrary to the required smooth texture. The Executive Chef admitted to estimating the amount of thickener, leading to improper food consistency. The Speech Pathologist confirmed the deficiency upon reviewing photographic evidence.
A facility failed to implement proper infection control measures for a resident with a bacterial UTI, as staff did not use PPE or place the resident on contact precautions upon admission. Additionally, during wound care for another resident, a nurse neglected to perform hand hygiene between glove changes, violating the facility's infection control policy.
Failure to Document Required Annual 90‑Minute Emergency Lighting Test
Penalty
Summary
Surveyors identified a deficiency related to emergency lighting when, during record review and staff interview between 11:30 AM and 3:00 PM with the Director of Facilities, the facility was unable to provide documentation that the required annual 90‑minute testing of emergency lighting had been performed. The Director of Facilities acknowledged that there was no documentation available to show completion of this annual 90‑minute emergency lighting test, as required by NFPA 101 (2012 and 2021 editions), sections 19.2.9.1 and 7.9. This failure to document the annual emergency lighting test was cited as a noncompliance that could affect all occupants of the facility in the event of a fire or other emergency. No specific residents, medical histories, or clinical conditions were mentioned in the report; the deficiency pertains to facility-wide life safety systems and their required testing and documentation.
Plan Of Correction
Emergency Lighting CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Emergency Lighting K0291 The facility immediately conducted a comprehensive inspection of all emergency lighting systems. On The Director of Facilities performed the required 90-minute annual testing of all emergency lighting units. Documentation of testing has been completed and is maintained on-site. 2. All areas of the facility were considered at risk due to lack of documented annual testing. A full facility-wide audit of all emergency lighting units was completed on by the Director of Facilities to ensure compliance. 3. The facility implemented a preventative maintenance schedule to ensure annual 90-minute emergency lighting testing is completed in accordance with NFPA 101 (2012), Section 7.9. A log tracking system has been developed to document all required testing. The Director of Facilities/designee will receive re-education on Life Safety Code requirements and documentation standards. 4. The Director of Facilities will review fire alarm testing records quarterly for 12 months, will present the findings for 12 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the twelve months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required. Emergency Lighting CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Emergency Lighting K0291 The facility immediately conducted a comprehensive inspection of all emergency lighting systems. On The Director of Facilities performed the required 90-minute annual testing of all emergency lighting units. Documentation of testing has been completed and is maintained on-site. 2. All areas of the facility were considered at risk due to lack of documented annual testing. A full facility-wide audit of all emergency lighting units was completed on by the Director of Facilities to ensure compliance. 3. The facility implemented a preventative maintenance schedule to ensure annual 90-minute emergency lighting testing is completed in accordance with NFPA 101 (2012), Section 7.9. A log tracking system has been developed to document all required testing. The Director of Facilities/designee will receive re-education on Life Safety Code requirements and documentation standards. 4. The Director of Facilities will review fire alarm testing records quarterly for 12 months, will present the findings for 12 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the twelve months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Failure to Perform and Document Annual Duct Detector Differential Testing
Penalty
Summary
Surveyors identified a deficiency related to the facility’s fire alarm system testing and maintenance, specifically the required annual Duct Detector Differential testing. During record review conducted between 11:30 AM and 3:00 PM, surveyors requested documentation demonstrating that this annual testing had been completed in accordance with NFPA 101 (2012 and 2021 editions), NFPA 70, and NFPA 72. The facility was unable to produce records showing that the Duct Detector Differential testing had been performed as required. In an interview conducted during the same time frame, the Director of Facilities acknowledged that the facility failed to provide documentation of the annual Duct Detector Differential testing. The deficiency was cited under NFPA 101 2012 (19.2.9.1, 7.9) and NFPA 101 2021 (19.2.9.1, 7.9), indicating noncompliance with the standards that require fire alarm detection systems, including duct detectors, to be tested and maintained annually. The report notes that this deficiency could affect all occupants of the facility in the event of a fire or other emergency.
Plan Of Correction
Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Fire Alarm System - Testing and Maintenance K0345 1. On The facility a certified fire alarm vendor to perform annual duct detector differential testing. All required testing has now been completed and documented. 2. All residents and staff were considered at risk due to lack of documented testing. A facility-wide review of all fire alarm components was conducted on 3. The facility established a service agreement to ensure all fire alarm testing (including duct detectors) is completed annually per NFPA 72 and NFPA 101 requirements. A compliance calendar has been implemented with alerts for required inspections and testing. The Director of Facilities/designee has been re-educated on required testing intervals and documentation. 4. The Director of Facilities or designee will audit for 3 months all documentation for the annual testing and inspection of the duct detector pressure differential test. The Director of Facilities will present the findings of site inspections for 3 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Fire Alarm System - Testing and Maintenance K0345 1. On The facility a certified fire alarm vendor to perform annual duct detector differential testing. All required testing has now been completed and documented. 2. All residents and staff were considered at risk due to lack of documented testing. A facility-wide review of all fire alarm components was conducted on. 3. The facility established a service agreement to ensure all fire alarm testing (including duct detectors) is completed annually per NFPA 72 and NFPA 101 requirements. A compliance calendar has been implemented with alerts for required inspections and testing. The Director of Facilities/designee has been re-educated on required testing intervals and documentation. 4. The Director of Facilities or designee will audit for 3 months all documentation for the annual testing and inspection of the duct detector pressure differential test. The Director of Facilities will present the findings of site inspections for 3 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required
Failure to Perform and Document Annual Main and Feeder Breaker Testing
Penalty
Summary
The deficiency involves the facility’s failure to perform and document required annual maintenance and testing of the main and feeder circuit breakers in accordance with NFPA 99 and manufacturer recommendations. During a record review conducted between 11:30 AM and 3:00 PM, surveyors requested documentation of the annual main and feeder breaker exercise. The facility was unable to provide records demonstrating that this testing and exercising had been completed as required. In interviews conducted during the same time frame, the Director of Facilities acknowledged that the facility did not have documentation showing that the annual main and feeder breaker exercise was performed according to manufacturer recommendations. The report notes that this failure to comply with NFPA 99 (2012 and 2021 editions, Sections 6.4.4 and 6.5.4) could affect all occupants of the facility in the event of a fire or other emergency, and that written records of maintenance and testing are required to be maintained and readily available.
Plan Of Correction
Electrical Systems - Essential Electric System CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Systems - Essential Electric System Maintenance and Testing K0918 1. On A licensed electrical contractor performed the annual main and feeder breaker testing/exercising in accordance with manufacturer recommendations. Documentation has been completed and is maintained on-site. 2. All residents were considered at risk due to lack of documented testing. A full review of the essential electrical system was conducted on 3. A preventative maintenance program has been implemented to ensure that annual breaker testing is completed per NFPA 99 (2012). The facility has incorporated electrical system testing into its environmental compliance tracking system. The Director of Facilities/designee received re-education on NFPA requirements. 4. The Director of Facilities will audit electrical system maintenance logs quarterly for 12 months. Inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required. Electrical Systems - Essential Electric System CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Systems - Essential Electric System Maintenance and Testing K0918 1. On A licensed electrical contractor performed the annual main and feeder breaker testing/exercising in accordance with manufacturer recommendations. Documentation has been completed and is maintained on-site. 2. All residents were considered at risk due to lack of documented testing. A full review of the essential electrical system was conducted on . 3. A preventative maintenance program has been implemented to ensure that annual breaker testing is completed per NFPA 99 (2012). The facility has incorporated electrical system testing into its environmental compliance tracking system. The Director of Facilities/designee received re-education on NFPA requirements. 4. The Director of Facilities will audit electrical system maintenance logs quarterly for 12 months. Inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, , and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Improper Use of Adapters and Power Strips for Refrigerators
Penalty
Summary
The deficiency involves improper use of electrical adapters and power strips as substitutes for permanent wiring, in violation of NFPA 99 and NFPA 70 requirements. During an observation with the Director of Facilities, surveyors found that an adapter was being used to power a refrigerator in the kitchen. The Director of Facilities acknowledged that an adapter was in use for this refrigerator, contrary to the standards that prohibit adapters from being used in place of fixed wiring. In a separate observation with the Director of Facilities, surveyors identified that a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities acknowledged that a power strip was being used for this refrigerator. These findings showed that the facility was not complying with NFPA 99 provisions that require power strips and adapters not be used as substitutes for permanent wiring for such equipment.
Plan Of Correction
Formatted text (without <text> tags or quotes): Electrical Equipment - Power and Extension Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Equipment - Power and Extension K0920 1. On The adapter in the kitchen refrigerator and the power strip in the dining room manager's office were immediately removed. All equipment was plugged directly into approved wall outlets. 2. On A facility-wide inspection was conducted by The Director of Facilities to identify improper use of power strips and adapters. Any non-compliant items were removed immediately. 3. On Staff were educated on proper electrical safety practices, including prohibited use of extension and adapters. Routine environmental rounds now include electrical safety checks. 4. The Director of Facilities/designee will conduct monthly environmental rounds for 3 months, then quarterly thereafter. Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that Continued from page occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required. Electrical Equipment - Power and Extension CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Equipment - Power and Extension K0920 1. On The adapter in the kitchen refrigerator and the power strip in the dining room manager's office were immediately removed. All equipment was plugged directly into approved wall outlets. 2. On A facility-wide inspection was conducted by The Director of Facilities to identify improper use of power strips and adapters. Any non-compliant items were removed immediately. 3. On Staff were educated on proper electrical safety practices, including prohibited use of extension and adapters. Routine environmental rounds now include electrical safety checks. 4. The Director of Facilities/designee will conduct monthly environmental rounds for 3 months, then quarterly thereafter. Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Food Safety and Sanitation Deficiencies in Main and Satellite Kitchens
Penalty
Summary
Surveyors identified multiple failures to store, prepare, distribute, and serve food in accordance with professional standards for food service safety in both the main kitchen and a satellite pantry kitchen. In the main kitchen, a cook’s beard cover did not fully cover all facial hair, and the handwashing sink initially did not provide warm water until the Executive Director manually adjusted a valve under the sink. In the pot washing area, full-sized steam table pans were stacked while still wet, and more than five plate domes with stuck-on food particles were found piled in the tray line area ready for use, indicating they had not been properly washed. Two large ice buckets were stained with black and grey mold-like discoloration and white wear marks. The high-temperature dishwashing machine in the main kitchen was run three times but failed to reach the required 180°F rinse temperature, only reaching 172°F, meaning dishes were not properly sanitized. In the second-floor satellite pantry kitchen, the high-temperature dishwashing machine was also run three times and failed to meet required wash temperatures, reaching only 139°F instead of the required 150–165°F, so dishes were not properly cleaned and sanitized. Additional sanitation and maintenance issues were observed, including a vent above serving dishes with a mold-like accumulation, broken and soiled cabinets above serving dishes with residue on the handles, and pantry floors with cracked, broken, and missing tiles with debris or residue buildup. The dishwasher chemical cabinet lock was rust-laden, the AC filter was covered with dark grey soot and dust, the juice dispenser with clean cups nearby had debris on top, and tray delivery carts contained large sheet trays with residue and stuck-on food debris. During a tray line observation, chopped tomatoes and sliced avocados on the salad line were held at 44°F and 45°F respectively, above the required 41°F or less, and the menu extension listed pureed peas for a pureed diet, but no pureed vegetable was present on the line.
Plan Of Correction
Food Procurement, Store/Prepare/Serve-Sanitary CFR(s): 483.60(i)(1)(2) §483.60(i) Food safety requirements. Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required F0812 1. All identified sanitation issues were corrected on Hot water valve was fixed immediately by maintenance team Steam table pan wet nesting was corrected The 5 plate domes that were dirty were taken to the dishwasher to be washed Stained ice buckets were replaced with new ones Dishwashing machine not reaching temperature for rinse cycle was fixed by Eco lab the same day Team member was provided education and in-service on proper use of beard guard. Corrected on [R] 2.Identified issues from satellite Kitchen were corrected on [R] Dishwashing machine not reaching temperature for rinse cycle was fixed by Eco lab the same day The vent located above the serving dishes was cleaned by maintenance team The cabinets were cleaned immediately The floors of the pantry area were observed with broken, cracked, missing tiles, with buildup residue and debris. Maintenance director made aware in the process of getting replaced. The locking mechanism of the dishwasher chemical cabinet is rust laden. Laden removed and in the process of being replaced. The AC filter was cleaned by maintenance team Th juice dispenser was cleaned by dietary aide The large delivery trays with residue and food debris were discarded 3. Issues identified during Tray line observation were corrected: The chopped tomatoes and sliced avocados were discarded Pureed vegetable was added to the line. Inservice on serving all food groups, starches, protein and vegetables to residents on texture modified diet order. Inservice provided to all dietary aides Inservice on maintaining and holding temperatures for ready to eat foods. Inservice provided to all cooks and dietary aides Daily sanitation rounds will be conducted by the Certified Dietary manager /designee for one week. Weekly for 2 months. 4. The Certified Dietary Manager/Executive Chef/designee will report the findings of the above observations and audits to the monthly QAPI Committee. The Administrator is responsible for confirming implementation and compliance of this POC and and resolving any variances that may occur.
Failure to Honor Diet-Appropriate Menu Choices for Residents on Modified Diets
Penalty
Summary
The facility failed to provide residents with menu choices that matched their physician-ordered diet textures and liquid consistencies. One resident with severe cognitive impairment had a physician order for a controlled diet with pureed texture and honey-thick liquids. During a noon meal observation, this resident’s meal ticket was stapled to a Regular Menu listing items such as lettuce and tomato salad, stir-fried vegetables, and a grilled cheese sandwich, none of which were appropriate for the resident’s ordered diet. The Registered Dietitian and the Dietetic Technician confirmed that Daily Menu printouts with Regular Menu options were provided to all residents, including those on mechanically altered diets, resulting in residents being offered choices that could not be honored due to diet restrictions. Another resident with moderate cognitive impairment had a physician order for a mechanical soft diet with nectar-thick liquids. This resident’s lunch tray ticket was also stapled to a Regular Menu that included salad greens, which are not allowed on a mechanical soft diet. On a separate breakfast observation, the same resident’s Regular Menu included fresh fruit as a choice, which the resident circled, but the tray contained canned peach halves instead. The resident stated she wanted her chosen fresh fruit rather than the peaches and reiterated her food preferences during the interview. Photographic evidence was obtained to document these discrepancies between ordered diets, menu offerings, and the food actually provided.
Plan Of Correction
Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is requiredF05501. Resident #54 and Resident #56 were immediately assessed by the Registered Dietitian (RD) & CDM (Certified Dietary Manager) for food preferences on Residents #54 and #56 were offered meal choices consistent with the prescribed diet. No adverse outcomes were identified. 2. 100% audit of all residents with therapeutic diets was completed on [R] by CDM to ensure menus and meal selections consistent with physician-ordered diets.On [R] , CDM provided in-service provided to dietary aides, certified nursing assistants, nurses, managers on new selective menu processes. 3. The facility implemented a diet-specific menu system and pre-meal diet verification process by reviewing the diet in tray ticket program IMPAC and PCC. Copies of the menus to be provided as part of the audits.Diet Menu was revised to include a mechanically altered diet to be consistent with physician orders. Therapeutic diets menus are available and offered to each resident according to physician orders. The Dietary Manager or designee will conduct weekly audits of 4 residents on therapeutic diets x 4 weeks then monthly x 2months, to verify the correct menu is offered and served. 4. The Dietary Manager or designee will report findings at the monthly QAPI meeting. The Administrator is responsible for confirming implementation and compliance with this POC and [R] , and resolving any variances that occur.
Failure to Follow Therapeutic Diet Orders and Provide Prescribed Nutritional Supplements
Penalty
Summary
The deficiency involves the facility’s failure to follow physician-ordered therapeutic diets and prescribed nutritional supplements for multiple residents. One resident with severe cognitive impairment and a physician’s order for a controlled diet with pureed texture and honey-thick liquids was observed at lunch without the ordered pureed vegetable; her plate contained only pureed chicken, a pureed starch, and possibly a pureed bread, all covered in gravy. The pureed menu for that meal listed broccoli as the vegetable, and a subsequent tray line observation on another day showed no pureed vegetables available, despite the pureed menu specifying pureed peas. The dietary manager and registered dietitian were informed of the missing pureed vegetables, and photographic evidence was obtained. The facility also failed to provide ordered Magic Cup nutritional supplements as prescribed. One resident with severe cognitive impairment and a care plan addressing risk for compromised nutritional status had a physician’s order for a 4 oz Magic Cup on day and evening shifts with lunch and dinner; during a breakfast observation, the meal ticket listed Magic Cup, but none was provided. Another resident with moderate cognitive impairment had a physician’s order for a 4 oz Magic Cup with lunch; during lunch observation, the meal ticket indicated Magic Cup, but the resident was served chocolate ice cream and ate coconut cream pie for dessert instead. The MAR documented 100% consumption of a Magic Cup on two consecutive days, despite the observed failure to provide it. During interviews, the RD and dietary manager explained that Magic Cups were to be provided by dietary staff either on trays or via the dessert/ice cream cart, but they could not explain why residents in the dining room did not receive the ordered supplements. Photographic evidence was obtained of these occurrences.
Plan Of Correction
Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required F0803 1. Upon identification, resident #54 was given pureed vegetables. Residents #23, #39, and #54 were given Magic Cup supplements as ordered. On [R] CDM re-educated team members on supplement delivery including proper documentation and confirming that pureed diet being served matches what is listed on spread sheet. Dietary aides' morning and evening shifts are accountable for serving all food groups including vegetables when serving puree meals to residents. 2. A 100% audit of all residents with therapeutic diets and/or supplements was completed on [R] by Certified Dietary Manager. 3. A tray line checklist and diet/supplement reconciliation process between dietary and nursing were implemented by [R]. RD oversight of menu compliance was initiated. The Certified Dietary Manager or designee will audit food tray weekly x 4 weeks then weekly x 2 months. 4. The Certified Dietary Manager/Designee will report on the findings at the monthly QAPI meeting. The Administrator is responsible for confirming implementation and compliance with this POC and [R], and resolving any variances that may occur.
Failure to Conduct and Document Semi-Annual Emergency Management Plan Testing
Penalty
Summary
The facility failed to comply with Florida Administrative Code 59A-4.126 by not conducting and/or documenting the required semi-annual testing of its written, comprehensive emergency management plan for internal or external disasters or emergencies. During record review and staff interviews conducted between 11:30 AM and 3:00 PM with the Director of Facilities and the Administrator, surveyors requested documentation showing that semi-annual testing of the emergency management plan had been performed. The facility was unable to provide any such documentation, and both the Director of Facilities and the Administrator acknowledged that they failed to provide documentation showing that the semi-annual testing of the emergency management plan was performed. The deficiency was cited as a Class III violation and was noted as having the potential to affect all occupants of the facility in case of a fire or other emergency. No specific residents, medical histories, or clinical conditions were mentioned in the report, and the deficiency pertained to facility-wide emergency preparedness processes rather than individual patient care events.
Plan Of Correction
Emergency Management Plan CFR(s): FAC 59A-4.126 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required. Emergency Management Plan K10531. On The Director of Facilities conducted a comprehensive emergency management drill to meet semi-annual testing requirements. Documentation of the drill and evaluation has been completed. 2. On Emergency preparedness documentation was reviewed by The Director of Facilities to ensure all required drills and evaluations are up to date. 3. A structured emergency preparedness calendar has been implemented to ensure semi-annual drills are conducted and documented in compliance with FAC 59A-4.126. 4. The Director of Facilities will present emergency preparedness documentation quarterly for compliance at Quality Assurance Performance Improvement (QAPI) meetings. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, [R] and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Failure to Honor Diet-Appropriate Menu Choices for Residents on Modified Diets
Penalty
Summary
The deficiency involves the facility’s failure to provide residents with appropriate menu choices that matched their physician-ordered diets, thereby not assuring residents’ rights to knowledge of available choices and independent personal decisions. One resident with severe cognitive impairment was admitted with multiple medical diagnoses and had a physician’s order for a controlled diet with pureed texture and honey-thick liquids. During a lunch observation, this resident’s meal ticket was found stapled to a Regular Menu listing items such as lettuce and tomato salad, stir-fried vegetables, and a grilled cheese sandwich, none of which were compatible with the resident’s ordered pureed diet. The Registered Dietitian and the Dietary Manager confirmed that Daily Menu printouts for the Regular Menu were provided to all residents, including those on mechanically altered diets, and acknowledged that residents on such diets would be offered items like fresh fruit that could not actually be provided according to their prescribed diet consistency. Another resident with moderate cognitive impairment and multiple medical diagnoses, including failure-related conditions, had a physician’s order for a mechanical soft diet with nectar-thick liquids. This resident’s lunch tray was observed with a meal ticket stapled to a Regular Menu that included salad greens, which are not allowed on a mechanical soft diet. On a separate breakfast observation, the same resident’s meal ticket was again stapled to a Regular Menu that listed fresh fruit as a choice. The resident had circled fresh fruit as her preference but instead received canned peach halves on her tray and verbally expressed that she wanted her chosen item rather than the peaches, reiterating her food preferences before the surveyor left the room. These observations, along with staff interviews, showed that residents on modified diets were routinely given Regular Menus with options that could not be honored due to their diet orders.
Plan Of Correction
Resident Rights/Exercise of Rights Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required N0181 1. Resident #54 and Resident #56 were immediately assessed by the Registered Dietitian (RD) & CDM (Certified Dietary Manager) for food preferences on [R] . Residents #54 and #56 were offered meal choices consistent with the prescribed diet. No adverse outcomes were identified. 2. 100% audit of all residents with therapeutic diets was completed on [R] by CDM to ensure menus and meal selections consistent with physician-ordered diets. On [R] , CDM provided in-service provided to dietary aides, certified nursing assistants, nurses, managers on new selective menu processes. 3. The facility implemented a diet-specific menu system and pre-meal diet verification process by reviewing the diet in tray ticket program IMPAC and PCC. Copies of the menus to be provided as part of the audits. Diet Menu was revised to include a mechanically altered diet to be consistent with physician orders. Therapeutic diets menus are available and offered to each resident according to physician orders. The Dietary Manager or designee will conduct weekly audits of 4 residents on therapeutic diets x 4 weeks then monthly x 2months, to verify the correct menu is offered and served. 4. The Dietary Manager or designee will report findings at the monthly QAPI meeting. The Administrator is responsible for confirming implementation and compliance with this POC and [R] and resolving any variances that may occur.
Failure to Follow Therapeutic Diet Orders and Provide Ordered Nutritional Supplements
Penalty
Summary
Surveyors found that the facility failed to follow physician-ordered therapeutic diets and provide ordered supplements. One resident on a controlled pureed diet with honey-thick liquids, who had severe cognitive impairment and was care planned for risk of compromised nutritional status, was not served a vegetable at lunch; her tray contained only pureed chicken, a pureed starch, and possibly a pureed bread covered in gravy, despite the menu listing a pureed vegetable (broccoli on one day and peas on another). During tray line observation, no pureed vegetables were present on the line even though the pureed menu specified a pureed vegetable. The Dietary Manager and Registered Dietitian were informed of the missing pureed vegetable and acknowledged the absence. The facility also failed to provide physician-ordered Magic Cup nutritional supplements as specified. One resident with varying dietary intake and a care plan for compromised nutritional status had an order for a 4 oz Magic Cup on day and evening shifts with lunch and dinner, but during a breakfast observation the Magic Cup was listed on the meal ticket and not provided. Another resident observed at the same breakfast also had a Magic Cup ordered but did not receive it. A third resident with moderate cognitive impairment had an order for a 4 oz Magic Cup with lunch; during lunch observations, this resident’s ticket read Magic Cup, but she was given a chocolate ice cream cup and ate coconut cream pie for dessert instead of the ordered supplement, while the MAR documented 100% consumption of a Magic Cup on consecutive days. The RD and Dietary Manager stated that dietary staff were responsible for providing Magic Cups but could not explain why residents in the dining room did not receive them.
Plan Of Correction
Dietary Services CFR(s): 400.141(1)(i), FS Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required N0407 1. Upon identification, resident #54 was given pureed vegetables. Residents #23, #39, and #54 were given Magic Cup supplements as ordered. On CDM re-educated team members on supplement delivery including proper documentation and confirming that pureed diet being served matches what is listed on spread sheet. Dietary aides' morning and evening shifts are accountable for serving all food groups including vegetables when serving puree meals to residents. 2. A 100% audit of all residents with therapeutic diets and/or supplements was completed on by Certified Dietary Manager. 3. A tray line checklist and diet/supplement reconciliation process between dietary and nursing were implemented by [R] . RD oversight of menu compliance was initiated. The Certified Dietary Manager or designee will audit food tray weekly x 4 weeks then weekly x 2 months. 4. The Certified Dietary Manager/Designee will report on the findings at the monthly QAPI meeting. The Administrator is responsible for confirming implementation and compliance with this POC and [R] and resolving any variances that may occur.
Food Safety Deficiencies in Kitchen and Satellite Kitchen
Penalty
Summary
The facility failed to adhere to professional standards for food service safety, as observed during a tour of the main kitchen and satellite kitchen. In the main kitchen, several issues were noted, including open garbage bins without lids, a Styrofoam cup with an employee's name in the food production area, and dirty Traulsen reach-in refrigerators. The commercial charcoal grills were found with an old sticky black substance, and a rectangular silver tray had debris and dirt. The walk-in refrigerator contained undated boxes of chicken breast filets sitting in a pool of red fluid, and the chicken was not sealed properly. Additionally, a container of clam base was found to be ten days old, exceeding the recommended usage period of three days. The walk-in refrigerator also had undated boxes of oven-roasted chicken halves and raw fish, and the floor in the dry storage area was dirty with a live insect observed on the wall. In the 2nd floor satellite kitchen, an open garbage container without a lid was observed. Further observations revealed that the internal temperatures of blue cheese and ham and cheese sandwiches were above the recommended 40 degrees Fahrenheit, measuring 44.2 and 45.8 degrees Fahrenheit, respectively. These findings were acknowledged by the facility's Administrator during an interview, indicating a failure to maintain proper food storage, preparation, and distribution standards, potentially affecting 48 residents in the facility.
Failure to Maintain Clean AC Units in Resident Rooms
Penalty
Summary
The facility failed to maintain a sanitary and clean environment in four residents' rooms, specifically regarding the air conditioning (AC) filters and vents, which were observed to have a black mold-like substance. During an initial tour on September 23, 2024, the surveyors noted the presence of this substance in rooms 238-B, 235-D, 226-W, and 232-B. Photographic evidence was obtained to document these findings. Interviews with residents in these rooms revealed that they were on oxygen therapy, with one resident expressing feelings of shortness of breath. Staff E, a Maintenance Assistant, acknowledged the presence of the mold-like substance during an environmental tour on September 26, 2024, and stated that he usually cleans the AC filters once a week. Despite this routine maintenance, the black mold-like substance was still present, indicating a failure in maintaining a clean and safe environment for the residents. The census at the time of the survey was 48, highlighting the potential impact of this deficiency on multiple residents within the facility.
Failure to Monitor and Address Nutritional Needs
Penalty
Summary
The facility failed to adequately monitor and address the nutritional needs of a resident, leading to a significant weight loss over several months. The resident, who was readmitted with severe cognitive impairment and required substantial assistance with eating, experienced a weight decline from 128 pounds to 118 pounds over a period of approximately five months. Despite this weight loss trend, the facility did not implement timely or effective nutritional interventions. The Certified Dietary Manager discontinued a high-calorie nutritional supplement without providing an alternative plan, even though the resident's oral intake was inconsistent and ranged from 50% to 75% of meals. Additionally, there were inconsistencies in the administration of prescribed nutritional supplements, with several instances of delayed administration recorded. The resident was supposed to receive Ensure three times a day, but it was often given late or not at all, as noted in the Medication Administration Audit Report. Interviews with staff revealed a lack of awareness and coordination regarding the resident's nutritional needs and supplement schedule. The Clinical Dietitian and Certified Dietary Manager did not adequately monitor or respond to the resident's weight loss, failing to make necessary adjustments to the care plan.
Failure to Provide Appropriate Dialysis Care Due to Transportation Issues
Penalty
Summary
The facility failed to provide appropriate dialysis care for a resident, resulting in missed dialysis treatments. The resident, who was cognitively intact and had a history of end-stage renal disease, heart failure, and a recent hip fracture, required dialysis three times a week. However, due to transportation issues, the resident missed scheduled dialysis sessions. The facility's Dialysis Policy Statement required ongoing communication and coordination with the dialysis center, but this was not effectively implemented. The resident missed dialysis on two occasions due to transportation arriving with inappropriate equipment, such as a chair instead of a stretcher, which was necessary due to the resident's hip surgery. The facility's Staff Director of Sales attempted to rectify the situation by arranging alternative transportation, but the resident still missed a dialysis session. The lack of proper communication and coordination between the facility, the transportation company, and the dialysis center contributed to these missed treatments. Additionally, the resident tested positive for Covid-19, which further complicated the situation and led to the resident being sent to the hospital. The facility's failure to ensure timely and appropriate transportation and communication with the dialysis center resulted in the resident missing critical dialysis treatments, highlighting a deficiency in the facility's adherence to professional standards of practice for dialysis care.
Controlled Substance Management Deficiencies
Penalty
Summary
The facility failed to properly manage and destroy controlled substances for two residents, leading to discrepancies in medication reconciliation. For one resident, a Buprenorphine Transdermal Patch was not discarded as required. The patch, dated 09/10/24, was found in the medication cart instead of being destroyed and documented by two nurses. The responsible nurse admitted to forgetting to complete the destruction process and did not date the controlled substance inventory sheet. Additionally, the resident's patch was administered without proper documentation of the previous patch's destruction. For another resident, a tablet of Oxycodone-Acetaminophen was removed from the controlled substance box without a corresponding physician order or documentation on the Medication Administration Record (MAR). The medication had been discontinued earlier, yet a tablet was still removed and not accounted for in the records. The Director of Nursing confirmed the discrepancy, highlighting a failure in the facility's medication management and reconciliation processes.
Medication Administration Errors Exceed Acceptable Rate
Penalty
Summary
The facility failed to maintain a medication error rate below 5 percent, resulting in a rate of 10.34 percent. This deficiency affected two residents, who were part of a sample reviewed for medication administration. The facility's policy requires medications to be administered as prescribed and documented immediately after administration. However, discrepancies were observed in the medication administration process for two residents, leading to errors. For one resident, the medication administration observation revealed that two medications, Ferrous Sulfate and Trelegy Ellipta, were omitted during the observed administration. The nurse involved claimed to have administered the Trelegy Ellipta prior to the observation, but documentation showed otherwise. Additionally, the Ferrous Sulfate was not administered as it was not available in the medication cart, despite being signed off as given. The resident's physician was later contacted, and a one-time dose of a similar medication was administered. Another resident was supposed to receive a Multivitamin with minerals, as per the physician's order. However, during the medication administration, only a Multivitamin without minerals was available and administered. The nurse confirmed that she had not seen or administered the correct Multivitamin with minerals. A review of the facility's supply confirmed that the Multivitamin without minerals was the only type available, indicating a failure to provide the correct medication as prescribed.
Improper Diet Consistency for Pureed Diets
Penalty
Summary
The facility failed to provide the correct diet consistency for residents on a Pureed diet during dining observations. Specifically, Resident #20 and Resident #6, both with severe cognitive impairments and specific dietary orders, were served Cream of Mushroom soup that did not meet the required pureed consistency. The soup was observed to be lumpy and thick, resembling an oatmeal-like consistency, which is not compliant with the pureed diet requirements that stipulate a smooth texture with no lumps. During the observation, Resident #6 was noted to cough while attempting to consume the soup, indicating potential difficulty in swallowing due to the improper consistency. The Executive Chef admitted to not measuring the thickener accurately, instead relying on estimation, which contributed to the inconsistency in the food texture. The facility's Speech Pathologist confirmed that the soup did not meet the pureed consistency standards when shown photographic evidence, further highlighting the deficiency in food preparation for residents requiring modified diets.
Infection Control Lapses in Resident Care
Penalty
Summary
The facility failed to implement an effective infection control program, as evidenced by the mishandling of a resident with a bacterial urinary tract infection (UTI). Resident #249, who was admitted with a diagnosis of sepsis and an extended spectrum beta-lactamase (ESBL) resistant E. coli UTI, was not placed on contact precautions upon admission. Despite having an active physician order for intravenous antibiotics, the resident's room lacked signage and personal protective equipment (PPE) supplies, and staff were observed not wearing PPE when interacting with the resident. The Assistant Director of Nursing (ADON) admitted to the oversight, confirming that contact precautions were only initiated several days after the resident's admission. Additionally, the facility's infection control practices were further compromised during a wound care observation for Resident #34, who had severe cognitive impairment and was dependent on staff for daily living activities. During the procedure, a registered nurse (RN) failed to perform hand hygiene between glove changes multiple times while treating the resident's pressure ulcer. The RN was observed retrieving supplies and handling the treatment cart without washing hands, despite the facility's policy requiring hand hygiene after glove removal. Both the RN and an assisting staff member acknowledged the lapse in protocol. These deficiencies highlight significant lapses in the facility's infection prevention and control measures, particularly in the areas of transmission-based precautions and hand hygiene during wound care. The failure to adhere to established protocols for infection control put residents at risk of infection transmission and compromised the quality of care provided.
Latest citations in Florida
Surveyors found that the facility failed to comply with 42 CFR 483.73(a) by not conducting the required annual review and update of its Emergency Preparedness (EP) plan. During record review, no documentation showed that the EP plan had been reviewed or updated within the past year, and the Administrator confirmed that the Emergency Management Plan had not been reviewed or revised as required.
Surveyors found that smoke/fire-rated enclosures were not properly maintained, with penetrations in smoke barriers in several general storage rooms across multiple smoke compartments. The Maintenance Director stated that insulation and fiberglass were used to pack and cover these holes but could not confirm that the materials were approved for fire-rated construction. Inspectors observed penetrations covered with fiberglass and noted a hole in one fiberglass panel in a storage room, resulting in a deficiency under NFPA 101 requirements for smoke barrier construction.
Surveyors found that fixed patient-care electrical equipment was not properly maintained or inspected in accordance with NFPA 99. In one room, a bedside remote had mismatched insulation and exposed wiring, and in another room, a call button receptacle had exposed low-voltage conductors. The Maintenance Director acknowledged both issues and reported that new bed remotes had been received but not yet installed.
Surveyors found that the facility failed to maintain a safe, clean, and homelike environment, with strong, persistent urine and feces odors noted throughout multiple halls and confirmed by staff. On two nursing units, hallways and resident rooms contained torn flooring, food debris, broken blinds, dirty and leaking toilets and sinks, rusted and corroded fixtures, missing outlet covers with oxygen concentrators plugged in, exposed light sockets, unmade and visibly soiled beds, and black, mold-like substances on walls and around toilet bases. Bathrooms had missing ceiling tiles, cracked door facings with brown stains, used briefs and torn toilet paper on floors, and toilets with brown or rust-like buildup. Outside, the patio and fencing area had broken and rotted railings, exposed rusted nails, fallen palm fronds, and overgrown vegetation, and the Administrator acknowledged the area was not safe for residents. Housekeeping and maintenance staff described daily cleaning and a work-order process, but the Maintenance Director reported being unaware of many of the observed issues, and the DON confirmed there was no specific environmental cleaning policy despite job descriptions and a general policy requiring a safe, sanitary, and comfortable environment.
A resident exited the building through a bedroom window, walked off the property, and was observed and redirected by staff with assistance from law enforcement, who encountered the resident down the road and helped escort the resident back. The facility’s internal documentation lacked staff or witness statements and characterized the event as the resident remaining on facility grounds without injury. Despite the resident’s account, a police report, and a maintenance staff report confirming that the resident left the premises and that law enforcement responded, the DON did not report the incident to required state and federal agencies, even though the DON acknowledged that any incident involving law enforcement response must be reported.
A resident with moderate cognitive impairment and a history of stroke was repeatedly observed over several days in visibly soiled clothing and bedding, with a strong urine odor, despite stating multiple times that he had requested assistance with changing and hygiene. Documentation indicated he was independent with toileting and personal hygiene and only occasionally incontinent, but his care plan lacked detail on the level of assistance needed, while an LPN reported he actually required staff help with bathing, grooming, toileting, and care. Laundry practices involved leaving clean, labeled clothing bagged in the linen room for nursing staff to distribute rather than returning it directly to rooms, and the DON reported that staff were expected to round every two hours and as needed to keep residents clean and dry, although there were no written ADL or resident care policies in place.
Surveyors observed four full O2 cylinders on one nursing unit stored unsecured directly on the floor under a sign labeled "FULL CYLINDERS" instead of in a secured storage rack. The ADON confirmed the cylinders were full and should not be on the ground. Reference to NFPA 99 showed that freestanding cylinders must be protected from damage and properly chained or supported in a stand or cart. The DON and Maintenance Director both acknowledged that O2 cylinders are required to be stored in a secure rack, should never be on the floor, and that unsecured cylinders on the floor present a safety risk.
A resident with multiple cardiopulmonary conditions and a documented full code status was found unresponsive without pulse or respirations during the night shift. A CNA notified the RN, who either instructed CNAs to clean and cover the resident or, per her and an LPN’s account, called a code blue and performed CPR with the LPN for about 20 minutes before stopping, without calling 911. The RN believed the resident was on hospice and did not verify code status, then notified the DON, provider, and family instead of EMS. Several hours later, after the DON called the facility and asked whether 911 had been contacted, the RN called 911 and briefly reinitiated CPR shortly before EMS arrived and pronounced the resident deceased, documenting postmortem changes. The facility’s investigation and root cause analysis found that staff failed to follow policy requiring immediate EMS activation and continuous CPR for full code residents until EMS arrival, leading to an Immediate Jeopardy finding.
A resident with full code status was found unresponsive without respirations or pulse during the night shift. An RN and an LPN initiated CPR but did not activate EMS, and they discontinued CPR after about 20 minutes. The RN, who lacked documented orientation and competency assessment and had obtained BLS certification through a fully online, non–instructor-led course, pronounced the resident deceased without authority and later stated she believed the resident was on hospice and did not verify code status. The LPN’s BLS certification was expired, and a CNA with an expired BLS certification performed several chest compressions despite facility policy that CNAs were not to perform CPR. The RN had not participated in documented code blue drills, and leadership confirmed that required clinical orientation and skills competencies had not been completed for her, leading surveyors to determine that staff were not adequately trained or competent to respond to a cardiopulmonary arrest for a full code resident, resulting in an Immediate Jeopardy finding.
Surveyors found multiple instances of improper use of relocatable power taps (RPTs) and extension cords during a facility tour with the Maintenance Director. In the social services office, an RPT was plugged into another RPT connected to a wall outlet, with the cord running across a walkway and taped to the floor. In the multipurpose room, a television was plugged into an extension cord, and in the MDS office, an RPT was plugged into another RPT with an outlet adapter in use. These conditions did not comply with NFPA 101, NFPA 99, and NFPA 70 standards governing electrical equipment, power strips, and extension cords.
Failure to Annually Review and Update Emergency Preparedness Plan
Penalty
Summary
Surveyors identified a deficiency related to the facility’s Emergency Preparedness (EP) Program under 42 CFR 483.73(a). During record review at 4:00 PM, surveyors examined the facility’s EP documentation and found no evidence that the emergency preparedness plan had been reviewed or updated on an annual basis as required. The regulation mandates that LTC facilities develop and maintain an emergency preparedness plan that is reviewed and updated at least annually to comply with applicable Federal, State, and local emergency preparedness requirements. In an interview, the Administrator acknowledged that the facility’s Emergency Management Plan had not been reviewed or updated. No documentation was provided to show that the required annual review and update of the EP plan had occurred. The deficiency is based solely on the lack of documented annual review and update of the emergency preparedness plan by facility administration; no specific resident cases or clinical events were described in the report.
Plan Of Correction
Preparation and/or execution of the Plan of Correction does not constitute admission or agreement of the provider of the truth of the facts alleged or conclusions set forth in the statement of deficiencies. The Plan of Correction is prepared and/or executed solely because it is required by the provision of Federal and State law. Facility EP was reviewed and signed off on by the DON, Maintenance Director and Administrator. The facility has determined that all residents have the potential to be affected. An in-service education program will be conducted by the administrator. The administrator will conduct monthly random checks to verify completed documentation.
Improper Repair of Smoke Barrier Penetrations in Multiple Smoke Compartments
Penalty
Summary
Surveyors identified a deficiency in the facility’s maintenance of smoke/fire-rated enclosures, specifically related to penetrations in smoke barriers in multiple smoke compartments. During an interview, the Maintenance Director reported that insulation was used to pack holes and then covered with fiberglass in general storage rooms in smoke compartments 1, 2, and 3, but was unable to confirm whether these materials were approved for use in fire-rated walls. Subsequent observation showed that the penetrations were indeed covered with fiberglass, and one general storage room in smoke compartment 2 had a hole in one of the fiberglass panels. The report states that this failure to properly maintain penetrations through smoke/fire-rated construction could allow smoke and flammable gases to spread to other areas and cause the smoke/fire-rated construction to fail to perform as designed.
Failure to Maintain and Inspect Patient-Care Electrical Equipment
Penalty
Summary
Surveyors identified a deficiency in the facility’s compliance with NFPA 99 requirements for testing and maintaining fixed patient-care electrical equipment. During an observation in one resident room, the bedside remote was found to have two different types of insulation and exposed wiring. In another resident room, the call button receptacle was observed with exposed low-voltage conductors. These conditions were noted during a survey of two of six smoke compartments. During an interview conducted at the time of the observations, the Maintenance Director stated that the facility had just received a new shipment of bed remotes and had not yet replaced the existing ones. The Maintenance Director also acknowledged the issue with the exposed conductors at the call button receptacle. The surveyors cited this as a failure to properly inspect and maintain fixed patient care electrical equipment in accordance with NFPA 99 (2012 Edition), sections 10.3 and 10.5.2.1.
Widespread Odors and Environmental Disrepair in Resident Care Areas
Penalty
Summary
Surveyors identified that the facility failed to provide a safe, clean, comfortable, and homelike environment as required by 42 CFR 483.10(i). Upon entrance to the building on multiple days, surveyors noted a strong, pungent odor of urine and feces throughout the facility, with the odor particularly strong on the 200, 300, and 400 halls. Staff interviews confirmed that the building "usually smells like" urine, and staff attributed the odor to residents defecating and urinating on the floor, an old building structure, and cleaning products that sanitize but do not deodorize. Housekeeping staff reported that they clean resident rooms daily but that nursing staff must first clean fecal and urine waste before housekeeping can sanitize, and delays by nursing staff in doing so postponed housekeeping’s ability to address the odors. On the 300 unit, surveyors observed multiple environmental and sanitation issues in resident rooms and bathrooms. The hallway had torn flooring, food particles, and a butter knife on the floor. Individual rooms had food debris, a straw on the floor, and broken blinds. Bathrooms contained dark brown stains on walls, rusted ceiling tile trim, toilets with brownish substances inside, and wet floors around toilets. Trim was missing around toilet bases, exposing a black, mold-like substance. Corroded and rusted sink faucet handles, leaking faucets, rusted pipes under sinks with buildup of corrosion, and rusted sprinklers were observed. Some toilets and three-in-one commodes had duct tape on them, and bathroom walls had black, mold-like substances. Doors and door facings showed rust, scrape marks, chipped and peeling paint, and exposed wood. In some rooms, electrical outlets had no covers while oxygen concentrators were plugged into them, boards covered windows, light fixtures over beds lacked covers with sockets exposed, and one fixture had only one bulb. A resident bed appeared dirty with a black substance on it, and dresser drawers were broken with drawer fronts on the floor. On the 400 unit, surveyors again noted a strong odor of urine upon entry and found additional environmental deficiencies. Bathrooms had missing ceiling tiles, broken emergency light covers with no pull strings, and toilet tank covers that did not fit properly, exposing the inside of the tank. In one bathroom, torn toilet paper and used briefs were lying in the corner of the floor, and toilets had brown, rust-like substances inside the bowls. Door facings appeared cracked with brown substances along the sides, and toilets had brownish-black buildup around the bases with broken, peeling trim. Light bases on walls had rust-like appearances, multiple rooms had broken or missing blinds, and some outlets lacked covers while oxygen concentrators were plugged into them. Some rooms had unmade beds, exposed wires at outlets, toilets with dark brown-black rings around the base and flooring, uncovered light fixtures, leaking sinks with rusted pipes, loose flooring, loose toilet seats, and dry red substances on door frames. Surveyors also observed deficiencies in the outdoor patio area adjacent to the locked unit. The gate code was broken, and a resident lock was placed on the gate. The patio and surrounding fencing had fallen palm fronds on the grass, broken and rotted wooden fence railings, unsteady railings, and multiple exposed rusted nails protruding from the railings where boards were broken or detached. Overgrown trees and bushes from the perimeter extended through the fence railings. When asked, the Administrator acknowledged that the area was not safe for residents and stated that they planned to have it redone in the future. The Maintenance Director reported that he and one other maintenance person relied on work orders and verbal reports to identify needed repairs and stated he was not aware of the specific room and equipment issues on the 300 and 400 units. Housekeeping staff stated they would report broken items via a work order book or text to maintenance, but one housekeeper, who cleaned the 400 unit daily, denied noticing stains or biohazard-like materials on walls and door frames despite the surveyors’ observations. Review of facility documents showed that the housekeeper job description required staff to maintain assigned work areas in a clean, safe, comfortable, and attractive manner and to report maintenance problems noted during cleaning. A facility policy titled "Policies and Practices - Control" stated that the facility must maintain a safe, sanitary, and comfortable environment for personnel, residents, visitors, and the public. The DON stated that blinds had been changed out and new cabinets and door handles purchased, and that staff were directed to use standard precautions when cleaning rooms, but also stated there was no policy specific to cleaning the environment. These observations and interviews demonstrated that the facility did not maintain sanitary, orderly, and comfortable interior conditions, did not adequately control offensive odors, and did not ensure that the physical environment, including resident rooms, bathrooms, and outdoor areas, was maintained in a safe, clean, and homelike condition as required by regulation.
Failure to Report Elopement Incident Involving Law Enforcement
Penalty
Summary
The deficiency involves the facility’s failure to report an elopement incident to required state and federal agencies as mandated by 42 CFR 483.12(c). On the referenced date, Resident #5 exited the building through his bedroom window around 12:15 PM and walked across the facility property toward the perimeter fence. A CNA observed the resident outside and called for assistance, after which staff redirected and escorted the resident back into the building and placed him on one-to-one supervision. The facility’s internal incident documentation noted the window exit and subsequent maintenance inspection of the window seals but did not include any staff or witness statements. The DON later stated that the resident never left facility grounds and was returned without injury, and therefore the incident was not considered reportable. However, interviews and external records showed that the resident did leave the facility premises and that law enforcement was involved. Resident #5 recalled being outside the facility, being brought back by staff and a “police man,” and being told by the officer not to leave again. A police report from the local police department confirmed an encounter with the resident outside the facility and that an officer assisted staff in escorting him back. Maintenance staff (Staff G) also reported that the resident climbed out the window, left the facility property, and was stopped “down the road,” then redirected back with law enforcement assistance. In interviews, the DON initially denied that law enforcement had been notified or involved, then later acknowledged that law enforcement had responded but asserted they did not come into the facility. The DON also confirmed awareness that any incident in which law enforcement investigates or responds is required to be reported, yet the elopement and law enforcement involvement were not reported to the State Survey Agency or other required officials within the required time frames.
Failure to Provide Timely ADL and Hygiene Care to a Dependent Resident
Penalty
Summary
Surveyors found that the facility failed to provide necessary ADL care, including grooming and hygiene, to a dependent resident over multiple days. The resident was repeatedly observed in visibly soiled clothing with a strong odor of urine, first standing in his doorway holding onto a wheelchair with wet navy pants saturated down to his calves, stating he had been waiting for staff to change his clothes. More than an hour later the same day, he remained in the same soiled pants and shirt while seated in a wheelchair near the nurses’ station. The following day, he was again observed wearing the same soiled clothes, smelling of urine, with his shirt stained with food and a dark liquid. His room had a strong urine odor, his bed was soiled with urine, and only two pairs of pants were seen on a chair with no other clothing available in the room. On a subsequent observation, he was seated on the edge of his bed wearing different pants and no shirt, with yellow-stained sheets beneath him and his previously soiled clothes on the floor; he reported that he had requested assistance but no staff had come, so he changed himself. Record review showed the resident had a history of stroke and repeated unspecified conditions, with a recent Quarterly MDS indicating moderate cognitive impairment (BIMS score of 10). The MDS documented him as independent for toileting, showering, personal hygiene, and related ADLs, and only occasionally incontinent, but his care plan did not specify the level of assistance he required for incontinence care and other ADLs. In contrast, an LPN familiar with the resident stated he required staff assistance with bathing, grooming, toileting, and care, and that he did not refuse such assistance and appropriately requested help. The LPN also explained that personal clothing was laundered at the facility and left bagged in the linen room for nursing staff to distribute, rather than being returned directly to resident rooms. The DON stated that staff were expected to follow best practices, including rounding every two hours and as needed to keep residents clean and dry, and acknowledged that all residents required some level of assistance with ADLs. The DON further stated the facility had no written ADL, resident care, or quality of care policies, despite these expectations.
Unsecured Storage of Full Oxygen Cylinders on Nursing Unit
Penalty
Summary
Surveyors found that the facility failed to ensure safe storage of oxygen cylinders on the West 1 unit. At 9:03 a.m., four full oxygen cylinders were observed stored unsecured directly on the ground rather than in the designated secured cylinder storage rack, under a sign labeled "FULL CYLINDERS." Photographic evidence was obtained of this condition. At 9:18 a.m., the ADON confirmed that the four cylinders were full and acknowledged they should not be stored on the ground. Review of NFPA 99 (2021) 11.6.2.3(11) indicated that cylinders must be protected from damage and that freestanding cylinders must be properly chained or supported in a proper stand or cart. Later that day, the DON stated that oxygen cylinders should be stored in a secure rack and never directly on the ground, and acknowledged that unsecured cylinders on the floor were a safety risk. The Maintenance Director also confirmed that oxygen cylinders should be in a secure rack and never stored directly on the ground, stating that cylinders stored on the floor can tip over and cause damage. These observations and interviews demonstrated noncompliance with regulatory and NFPA standards for safe storage of oxygen cylinders.
Plan Of Correction
This plan of correction constitutes a written allegation of compliance for the deficiency cited. Submission of this plan of correction is not an admission that the deficiency exists or that one was cited correctly. This plan of correction is submitted to meet the requirements established by the State and Federal law. The four unsecured [R] cylinders on the West 1 unit were secured. The Nursing Department completed a baseline audit of [R] cylinder storage within the facility to ensure all [R] cylinders were secured and stored properly. Ongoing education will be completed with current facility staff regarding the facility's [R] storage policy and procedure; and will be completed during new hire and agency orientation to the facility by ADON/designee. Audits will be completed by the Director of Nursing/designee regarding adherence to the facility's [R] storage policy and procedure twice weekly x 4 weeks, then weekly x 4 weeks, then monthly x 4 months, or until continued substantial compliance has been met. Results of audits will be reported to the QAPI Committee on a monthly basis by the Director of Nursing/designee.
Failure to Provide Required CPR and Activate EMS for Full Code Resident
Penalty
Summary
The deficiency involves the facility’s failure to provide immediate and appropriate basic life support, including CPR, to a resident with a documented full code status when the resident was found unresponsive. The resident had diagnoses including a slow-progressing circulatory condition involving narrowing or blockage of vessels, a condition that restricts airflow and makes breathing difficult, and other listed conditions. The physician’s order specified “Full Code,” and the care plan documented that the resident was under court-ordered guardianship with wishes honored as full code. The facility’s policy required that in the event of cardiac or respiratory arrest, staff immediately call for assistance, overhead page a code, begin CPR in the absence of a valid DNR, and continue CPR until EMS assumes responsibility or the resident responds. On the night of the incident at approximately 2:00–2:07 a.m., a CNA found the resident unresponsive in bed and notified the RN on duty. One CNA’s written statement indicated that the RN said she already knew the resident was going to die and instructed the CNA to clean and cover the resident. Another CNA’s account stated that the RN came to the room, took vital signs, and then instructed her to clean the resident. The RN’s own written statement and interview indicated that she called a code blue, that an LPN brought the crash cart, and that they performed CPR for approximately 20 minutes. The LPN’s statement corroborated that a code blue was called, that he brought the crash cart, and that CPR was performed for about 20 minutes before the RN stopped and stated that the resident was gone or words to that effect. The RN acknowledged that the resident had no vital signs but was warm and not responding, and she stated that she believed the resident was on hospice and therefore did not call 911. After CPR was discontinued, the RN did not activate EMS and instead notified the DON, the provider, and the resident’s family. The DON documented receiving a message from the RN that the resident had no pulse and no blood pressure and that the assigned nurse had initiated CPR but was unable to revive the resident. The DON later received a text from the RN that the resident had expired. The DON stated that at approximately 6:00 a.m. she called the facility and asked if 911 had been called, and upon learning it had not, she instructed the RN to call 911. The RN then reinitiated CPR at around 6:00 a.m., approximately four hours after the resident was first found without pulse or respirations, and stated that they tried to do something until EMS arrived because EMS had to see them doing CPR. EMS records showed activation at 6:18 a.m., arrival at 6:27 a.m., and pronouncement of death at 6:31 a.m., with documentation that CPR was not attempted by EMS because it was considered futile and that the resident exhibited postmortem changes. The Medical Director confirmed that the resident was full code and stated that staff should have started CPR and called 911 and that CPR should not be done four hours after a resident is pronounced dead. The facility’s investigation and a root cause analysis concluded that the RN and LPN did not follow the facility’s established policy and procedure to call 911 and administer CPR to a full code resident until EMS arrival. The root cause was identified as the nurse’s belief that the resident was on hospice and her failure to check the resident’s code status as outlined in facility policy. The surveyors determined that the failure to immediately activate EMS and to continue CPR until EMS arrival for this full code resident constituted noncompliance with the requirement to provide basic life support and resulted in an Immediate Jeopardy determination.
Plan Of Correction
This plan of correction is submitted as required under Federal and State regulations and statutes applicable to long term care providers. This plan of correction does not constitute an admission of liability on the part of the facility, and such liability is hereby specifically denied. The submission of this plan does not constitute agreement by the facility that the surveyors' findings or conclusions are accurate, that the findings constitute a deficiency, or that the scope or severity regarding any of these deficiencies cited are correctly applied. Resident #1 no longer resides in the facility as of 4.7.26. This has the potential to affect all residents in the facility. All codes to 1.1.26 were reviewed to ensure protocol was followed. No outliers were noted. All licensed nurses received education from the Director of Nursing and/or nursing management on [R] policy and procedure and Florida [R] policy. This includes where to find the code status. Education addressed what to do for full code hospice residents. Education completed with CNA's that protocol is that they do not assist with [R] or breaths during a [R] event. All education will be added to new hire orientation. Code drills will occur 3 x weekly x 4 weeks, followed by 2 x weekly x 4 weeks, followed by 1 x weekly x 4 weeks. Results will be brought to QAPI to determine need for ongoing auditing.
Removal Plan
- Educated licensed nurses on CPR policy and procedure and Florida Do Not Resuscitate (DNRO) policy, including where to find code status and what to do for full code hospice residents; emphasized initiating emergency services immediately when resident is full code, continuing CPR until EMS arrives, and that nurses cannot pronounce death or stop CPR on a full code resident unless instructed by EMS.
- Implemented emergency response “Code Blue” drills on all three shifts, including full code and full code hospice scenarios, with emphasis on calling 911 immediately.
- Educated licensed nurses and CNAs on the facility abuse and neglect policy, including resident rights.
- Required licensed nurses to complete a CPR post-test; restricted staff who have not completed education/testing from working until completion.
- Educated licensed nurses regarding change in condition.
- Placed laminated instructions on how to overhead page during a code at all nursing station phones and other designated phones.
- Held a Quality Improvement Performance Committee meeting to review root cause analysis findings and approve recommendations.
- Held a Quality Improvement Performance Committee meeting to review progress of the plan and approve recommendations.
- Completed a “like resident” audit of all expired residents and rehospitalizations for a defined period to determine whether involved staff were the same as the code event and whether proper procedure was followed.
Failure to Provide Competent CPR Response and Verify Code Status for Full Code Resident
Penalty
Summary
The deficiency involves the facility’s failure to ensure that nursing staff possessed and demonstrated the competencies required to respond appropriately to a cardiopulmonary emergency for a resident with full code status. Resident #1, who was designated as full code, was found unresponsive and without respirations or pulse at approximately 2:07 a.m. Clinical staff, consisting of an RN (Staff A) and an LPN (Staff B), initiated CPR but did not activate Emergency Medical Services (EMS) as required by facility policy for a full code resident. After approximately 20 minutes of CPR, the RN and LPN stopped resuscitation efforts without EMS involvement. The RN, without authority to do so, pronounced the resident deceased based on the absence of vital signs and did not verify the resident’s code status before discontinuing CPR. The RN later stated she believed the resident was on hospice and therefore did not call 911, and that she was confused about which residents were hospice and which were full code. The LPN reported that he assumed the RN had called 911 and continued CPR for about 20 minutes until the RN “called the code” and left, and he acknowledged that he knew CPR should continue until EMS arrival but did not speak up. Four hours after CPR was stopped, at approximately 6:00 a.m., the RN restarted CPR and activated EMS after receiving instructions from the DON. The investigation further identified that the RN had no documented orientation, onboarding education, or skills competency assessments since hire, despite being promoted to weekend supervisor. Her BLS certification had been obtained through a fully online course without an instructor or live feedback. The LPN’s BLS certification was expired, and a CNA who performed several chest compressions also had an expired BLS certification, even though facility policy did not permit CNAs to perform CPR. Facility records showed that monthly code blue drills had been conducted, but there was no documentation that the RN had ever participated in these drills. Leadership interviews confirmed that required clinical orientation and competency evaluations had not been completed for the RN, and that she had failed tests for a clinical manager position but was nonetheless functioning in a supervisory role. These actions and omissions led surveyors to determine that staff were not adequately trained or competent to respond to cardiopulmonary arrest for residents with full code status, resulting in an Immediate Jeopardy determination. The facility’s own root cause analysis, as reflected in meeting minutes, identified that the nurse did not check the resident’s code status and lacked knowledge about when CPR could be discontinued and when 911 should be called. The analysis documented that the nurse believed the resident was hospice and therefore did not start or continue CPR appropriately or call EMS when the resident was found without respirations and pulse. The facility assessment tool and policies referenced the need for staff training and competencies in identifying changes in condition, end-of-life care, advance care planning, and adherence to the CPR policy, but the documented events showed that these expectations were not met in practice for the staff involved in this incident. Surveyors concluded that the failure to ensure nursing staff were trained and competent to respond appropriately to cardiopulmonary arrest for a full code resident, including immediate initiation and continuation of CPR and activation of EMS, constituted noncompliance with requirements for sufficient and competent nursing staff. The failure affected Resident #1 and placed other full code residents at risk, leading to an Immediate Jeopardy finding that was later reduced in scope and severity after verification of an acceptable Immediate Jeopardy removal plan.
Plan Of Correction
This plan of correction is submitted as required under Federal and State regulations and statutes applicable to long term care providers. This plan of correction does not constitute an admission of liability on the part of the facility, and such liability is hereby specifically denied. The submission of this plan does not constitute agreement by the facility that the surveyors' findings or conclusions are accurate, that the findings constitute a deficiency, or that the scope or severity regarding any of these deficiencies cited are correctly applied Resident # 1 no longer resides in the facility as of 4.7.26. This has the potential to affect all residents in the facility. All licensed nurses were audited to ensure current [R] certification. Facility will ensure [R] certification through a [R] provider whose training includes a [R] on session either in a physical or virtual instructor-led setting in accordance with accepted national standards. Human resources, or designee, will audit monthly to ensure all licensed nurses have a current [R] certification.Education was completed with licensed nurses on initiating [R] services immediately when a resident is full code. Education included that [R] is to continue on a full code resident until [R] arrives and that the nurse cannot pronounce [R] on the full code resident and/or stop [R] until instructed by [R].Education will be added to new hire orientation.7 random licensed nurses will complete a knowledge quiz related to code events. Per week x 4 weeks, followed by 5 nurses x 4 weeks, then 3 nurses x 4 weeks. Results will be brought to QAPI to determine need for ongoing auditing.
Removal Plan
- Regional Director of Clinical Services educated the Administrator and Director of Nursing regarding the CPR policy and the need to immediately contact emergency medical services (911) in the event of a full code; Administrator and DON signed the education
- Regional Director of Clinical Services provided documented education to the Administrator and Director of Nursing regarding the CPR policy and the need to immediately contact emergency medical services (911) in the event of a full code
- Director of Nursing and/or nursing management educated all licensed nurses on the CPR policy and procedure, including where to find code status and what to do for full code hospice residents
- Reinforced through education that CPR must be initiated immediately for full code residents, continued until EMS arrives, and that nurses cannot pronounce death or stop CPR on a full code resident unless instructed by EMS
- Conducted an Ad Hoc Quality Improvement Performance Committee meeting to review root cause analysis recommendations related to the incident; recommendations approved
- Conducted a follow-up Ad Hoc Quality Improvement Performance Committee meeting to review progress on the plan; recommendations approved
Improper Use of Power Strips and Extension Cords in Multiple Facility Areas
Penalty
Summary
Surveyors identified deficiencies related to the use and maintenance of relocatable power taps (RPTs) and extension cords that did not comply with NFPA 101, NFPA 99, and NFPA 70 requirements. During a facility tour conducted between 11:00 a.m. and 3:30 p.m. with the Maintenance Director, surveyors observed in the social services office an RPT plugged into another RPT, which was then plugged into a wall outlet, with the cord running across a walkway and taped to the floor. In the multipurpose room, a television was found plugged into an extension cord, contrary to standards that prohibit using extension cords as a substitute for fixed wiring and require temporary extensions to be removed immediately after use. Further observations included the MDS office, where an RPT was plugged into another RPT and an outlet adapter was in use. These configurations did not meet the NFPA 99 provisions governing the proper use of power strips and extension cords, including requirements that power strips be appropriately rated and used only as intended, and that extension cords not be used as permanent wiring. During concurrent interviews, the Maintenance Director acknowledged these findings as they were observed by the surveyors.
Plan Of Correction
The RPT observed plugged into an RPT plugged into an outlet in the Social Services Office was removed. The extension cord used to plug in the television in the multipurpose room was removed. The RPT plugged into an RPT and outlet adapter in the MDS office was removed. Additional offices and resident care areas will be reviewed for the improper use of plug adapters, power strips and extension. The Executive Director/designee will educate the Maintenance Director on the importance of NFPA 101 Electrical Equipment- Power and Extension specific to the improper use of plug adapters, power strips, and extension and will continue to monitor in accordance with NFPA standards. Any findings will be reported to the monthly QAPI Committee for further review. The RPT observed plugged into an RPT plugged into an outlet in the Social Services Office was removed. The extension cord used to plug in the television in the multipurpose room was removed. The RPT plugged into an RPT and outlet adapter in the MDS office was removed. Additional offices and resident care areas will be reviewed for the improper use of plug adapters, power strips and extension. The Executive Director/designee will educate the Maintenance Director on the importance of NFPA 101 Electrical Equipment - Power and Extension specific to the improper use of plug adapters, power strips, and extension and will continue to monitor in accordance with NFPA standards. Any findings will be reported to the monthly QAPI Committee for further review.