K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
F

Failure to Maintain and Document Fire Alarm System per NFPA Requirements

Adams County ManorWest Union, Ohio Survey Completed on 03-25-2026

Summary

Surveyors identified that the facility failed to maintain and document its fire alarm system in accordance with NFPA 101 and NFPA 72 requirements, potentially affecting all 69 residents in the building. During record review, the only annual fire alarm documentation provided consisted of a single page without a device list. No documentation was available to verify that the required semi-annual visual inspections of the fire alarm system had been completed, and there was also no documentation confirming that fire alarm devices in the facility had undergone the required sensitivity testing. Documentation was requested multiple times throughout the survey period, including at the entrance conference and later in the morning, but none was produced by the time of exit. During the physical tour of the facility, surveyors observed multiple issues with fire alarm breakers in electrical panels. In electrical panel PP-5, the fire alarm breaker was found in the off position and was neither marked in red nor secured from unauthorized access. Another fire alarm breaker located in the generator main A panel was also not marked in red or secured, and the panel itself had no label indicating that a fire alarm breaker was inside. Additionally, in the electrical panel labeled generator sub-A at the front of the building, the fire alarm breaker was not marked in red or secured from unauthorized access. These observations were confirmed in an interview with the Maintenance Director.

Plan Of Correction

1. Based on observation, record review, and staff interview, no residents experienced negative outcomes related to fire alarm system testing and maintenance deficiencies. The facility failed to provide complete annual fire alarm documentation listing (only one page with no device list provided during survey), failed to provide documentation of required semi-annual visual inspections, and failed to provide documentation of required device sensitivity testing. Additionally, observations identified fire alarm breakers that were in the off position, not marked in red, not secured from unauthorized access, and not properly labeled within electrical panels. 2. The Medical Director was notified by LNHA on 03/26/2026 of the deficiency, including incomplete fire alarm system documentation, lack of required inspections and testing, and electrical breaker deficiencies identified during survey. 3. Fire alarm system inspection, testing, and documentation will be completed by a contracted fire protection vendor on or before 04/30/2026. This will include: (a) completion of a full annual inspection with a complete device list, (b) completion and documentation of semi-annual visual inspections, and (c) completion and documentation of sensitivity testing of all required devices. All missing documentation will be obtained and maintained onsite. Electrical deficiencies will be corrected by Maintenance Director/designee or licensed electrician on or before 04/30/2026, including: (a) ensuring all fire alarm breakers are in the correct position, (b) marking all fire alarm breakers in red, (c) securing breakers from unauthorized access, and (d) labeling all panels to clearly identify fire alarm circuits including those located within generator panels. All required inspections, testing, and maintenance will be placed on an an automatically recurring schedule per NFPA 72 requirements by Administrator/designee on or before 04/30/2026. 4. Documentation of all fire alarm system inspections, testing, and maintenance will be maintained onsite and readily available. The Maintenance Director/designee will audit compliance monthly. Compliance will be reviewed in QAPI every quarter and as needed to ensure ongoing systemic compliance. 5. LNHA educated Maintenance Director on 03/26/2026 regarding maintenance of the facility's fire alarm equipment/system, including listing out all devices.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0345 citations
Failure to Perform and Document Annual Duct Detector Differential Testing
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to perform and/or document the required annual Duct Detector Differential testing for the fire alarm system in accordance with NFPA 101, NFPA 70, and NFPA 72. During record review and interviews with the Director of Facilities, no documentation could be produced to show that this annual testing had been completed, and the Director acknowledged the lack of records. This deficiency was cited as potentially affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Fire Alarm System Inspection and Testing Documentation
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

The facility did not maintain required inspection and testing documentation for its fire alarm system. During surveyor review, no records could be produced to show that semi-annual visual inspections or the two-year smoke detector sensitivity testing had been completed, and the maintenance supervisor confirmed that this documentation was unavailable at the time of the survey. This deficiency affected the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Properly Test Fire Alarm System Components
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and properly test multiple fire alarm system components, including smoke detectors near the medical supply area and house laundry that could not be located, elevator fire hat and primary recall functions that could not be reset due to lack of a key, and an untested elevator control shunt trip. On revisit, the missing smoke detectors had been replaced with battery-operated units that were not connected to the building’s fire alarm notification system, and the previously identified fire alarm issues remained uncorrected.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Fire Alarm Documentation and Testing Records
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain required fire alarm system documentation and testing records. During record review with the Maintenance Director, there was no vendor-signed log book at the fire panel documenting work performed at each visit, no documentation of biennial smoke detector sensitivity testing, and no fire alarm system design plans located at the fire panel, as required by NFPA 101 and NFPA 72.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Alarm System in Proper Working Order
D
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors identified that the facility did not maintain its fire alarm system in accordance with NFPA 72 when the fire alarm control panel was observed displaying a trouble signal. During the observation, the Maintenance Director confirmed that the trouble condition was related to a faulty heat detector. This unresolved trouble indication showed that the fire alarm system was not being properly maintained to ensure it functioned as designed for the entire building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Semi-Annual Fire Alarm System Inspections
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors determined that the facility did not comply with NFPA 101 and NFPA 72 requirements for fire alarm system maintenance when record review showed incomplete fire alarm inspection reports and no documentation of required semi-annual visual inspections of fire detection components. The Director of Maintenance confirmed that these six-month inspections had not been documented and reported being unaware of the requirement, creating a deficiency that had the potential to affect all four residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙