K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
D

Smoke Detector Failed to Initiate Fire Alarm During Testing

Crestwood Wellness And Recovery CenterRedding, California Survey Completed on 06-09-2025

Summary

During a facility tour and staff interview, surveyors observed that a smoke detector located outside resident room 209 failed to initiate the fire alarm system when tested with artificial smoke. The test was conducted twice, and on both occasions, the alarm did not activate. Staff present during the testing were unable to provide an explanation for the malfunction at the time of the observation. It was noted that the air conditioning vent was approximately 36 inches from the smoke detector, and staff speculated that airflow from the vent might be interfering with the detector's ability to sense smoke. This deficiency affected 14 out of 90 residents in one of ten smoke compartments, as the non-functioning smoke detector could delay notification to emergency forces in the event of a fire.

Plan Of Correction

The facility recognizes the importance of maintaining the fire alarm system. The facility shall continue to maintain the smoke detectors and fire alarm system. The facility contacted Sa-Fire to inspect the current locations of the smoke detectors. Facility plans to move / re-locate the 4 ceiling mount smoke detectors away from the proximity of the air registers that may have affected the smoke detectors, causing the testing issues. Sa-Fire will be placing the system on test to complete the work, and the annual fire alarm inspection is scheduled to be completed July 25, 2025. The detectors will be re-tested at that point. Further issues regarding the fire alarm system and/or the smoke detectors will be received during the QA process and brought to the QAPI Committee for review and discussion. The Administrator, Environmental Services Supervisor, maintenance staff, and nursing staff shall be responsible for monitoring and ongoing compliance. This page is purposefully blank.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0342 citations
Blocked Fire Alarm Pull Station in Dining Room
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A fire alarm pull station was observed to be blocked in the Delaware dining room near the courtyard doors, making it inaccessible and in violation of NFPA 101 requirements for manual fire alarm system initiation. This was confirmed by the Facilities Director during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Obstructed Access to Fire Alarm Pull Stations
E
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

Surveyors found that access to two fire alarm pull stations was blocked by portable nurse worktables and a dirty linen cart, with the Maintenance Supervisor confirming staff awareness of proper storage procedures. The facility's policy requires maintenance of safe and accessible equipment, but these obstructions were not removed as required.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Manual Fire Alarm Pull Stations Missing Protective Snap Bars
D
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

Two manual fire alarm pull stations were found without their required protective snap bars, one near a resident room and another near a nurse station. The Maintenance Supervisor indicated that patients may have removed the snap bars. This deficiency impacted two smoke compartments and left the pull stations not properly maintained as designed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Pull Station Obstructed by Storage Items
E
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

The facility failed to maintain the initiation of the required fire alarm system on one level. A fire alarm pull station in the Activities Department was blocked by storage items, making it inaccessible. This was confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Box Obstruction in Kitchen
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A fire alarm pull box in the facility's kitchen was obstructed by a steel table used as an extension of the dishwashing machine table, blocking access to the alarm. This deficiency was confirmed during an interview with the AIT and reported at the Life Safety Code exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Manual Pull Stations Obstructed
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

The facility failed to ensure fire alarm manual pull stations were accessible, as required by NFPA 72:2010. Observations revealed that a pull station in the dining room was blocked by a table, and another in the physical therapy room was obstructed by wheelchairs and a bed. This deficiency could potentially affect all 83 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙