K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
E

Fire Alarm Pull Station Obstructed by Storage Items

Wyndmoor Hills Rehabilitation And Nursing CenterWyndmoor, Pennsylvania Survey Completed on 01-27-2025

Summary

The facility failed to maintain the initiation of the required fire alarm system, specifically affecting one of the four levels in the facility. During an observation on January 27, 2025, at 2:00 p.m., it was noted that the fire alarm pull station inside the Activities Department was not readily accessible. This inaccessibility was due to the pull station being blocked by miscellaneous storage items. During an exit interview with the Administrator and Maintenance Director on the same day at 2:30 p.m., it was acknowledged that the fire alarm pull station was obstructed by these items.

Plan Of Correction

1. Items blocking the pull station inside the Activities Department were immediately removed. 2. Pull stations throughout the facility audited to ensure they remain readily accessible. 3. Education provided to ensure proper compliance with this regulation. 4. An audit of the pull station in the Activities Department will be conducted to ensure it remains readily accessible. Audit will be done 2x a month for 2 months and 1x a month for 1 month. 5. The findings of these quality monitoring's to be reported to the Quality Assurance/Performance Improvement Committee monthly x6 months.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0342 citations
Smoke Detector Failed to Initiate Fire Alarm During Testing
D
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A smoke detector outside a resident room failed to activate the fire alarm system during two separate tests with artificial smoke. Staff could not determine the cause at the time, but noted the proximity of an AC vent, which may have affected the detector's function. This issue impacted 14 residents in one smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Blocked Fire Alarm Pull Station in Dining Room
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A fire alarm pull station was observed to be blocked in the Delaware dining room near the courtyard doors, making it inaccessible and in violation of NFPA 101 requirements for manual fire alarm system initiation. This was confirmed by the Facilities Director during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Obstructed Access to Fire Alarm Pull Stations
E
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

Surveyors found that access to two fire alarm pull stations was blocked by portable nurse worktables and a dirty linen cart, with the Maintenance Supervisor confirming staff awareness of proper storage procedures. The facility's policy requires maintenance of safe and accessible equipment, but these obstructions were not removed as required.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Manual Fire Alarm Pull Stations Missing Protective Snap Bars
D
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

Two manual fire alarm pull stations were found without their required protective snap bars, one near a resident room and another near a nurse station. The Maintenance Supervisor indicated that patients may have removed the snap bars. This deficiency impacted two smoke compartments and left the pull stations not properly maintained as designed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Box Obstruction in Kitchen
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A fire alarm pull box in the facility's kitchen was obstructed by a steel table used as an extension of the dishwashing machine table, blocking access to the alarm. This deficiency was confirmed during an interview with the AIT and reported at the Life Safety Code exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Manual Pull Stations Obstructed
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

The facility failed to ensure fire alarm manual pull stations were accessible, as required by NFPA 72:2010. Observations revealed that a pull station in the dining room was blocked by a table, and another in the physical therapy room was obstructed by wheelchairs and a bed. This deficiency could potentially affect all 83 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙