K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
F

Fire Alarm Box Obstruction in Kitchen

Concord Healthcare & Rehabilitation CenterLakewood, New Jersey Survey Completed on 12-20-2024

Summary

The facility failed to ensure that each manual fire alarm box was accessible, unobstructed, and visible, as required by NFPA 101: 2012 Edition and NFPA 72: 2010 Edition. During an observation, it was noted that one of the two fire alarm pull boxes in the facility's kitchen was blocked by a freestanding steel table. This table was being used as an extension of the dishwashing machine table and had dishes and cups on it, obstructing access to the fire alarm box. This deficiency was confirmed through an interview with the Administrator in Training (AIT) at the time of the observation. The issue was brought to the attention of the facility's administration during the Life Safety Code exit conference.

Plan Of Correction

K342 1. The facility conducted a comprehensive inspection of all fire alarm pull stations to identify and ensure that all the fire alarm pull stations are accessible, unobstructed, and visible per NFPA standards. The identified area in the kitchen was repaired on 12/23/24 by Allied Fire and Safety. The maintenance director and administrator inspected the area to ensure it meets NFPA standards. 2. All maintenance personnel were educated on the importance of maintaining an accessible, unobstructed, and visible clear path in front of any fire alarm pull stations and the impact on resident safety. All residents have the potential of being affected by this. The facility will keep detailed records of fire alarm pull stations, including dates and any issues discovered. 3. The facility conducts monthly drills to ensure staff and residents are familiar with emergency procedures, which includes fire alarm pull stations. All staff at the facility are educated annually in life safety regulations, which includes maintaining an accessible, unobstructed, and visible clear path for the fire alarm pull station. 4. The facility will conduct monthly life safety audits on all fire alarm pull stations for the next 3 months to ensure the facility is in accordance with NFPA standards. The results of these audits will be communicated with the QAPI team for the next 2 quarters. Based on the results, the QAPI team will decide to conclude or continue with these audits. The QAPI team meets on a quarterly basis.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0342 citations
Smoke Detector Failed to Initiate Fire Alarm During Testing
D
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A smoke detector outside a resident room failed to activate the fire alarm system during two separate tests with artificial smoke. Staff could not determine the cause at the time, but noted the proximity of an AC vent, which may have affected the detector's function. This issue impacted 14 residents in one smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Blocked Fire Alarm Pull Station in Dining Room
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A fire alarm pull station was observed to be blocked in the Delaware dining room near the courtyard doors, making it inaccessible and in violation of NFPA 101 requirements for manual fire alarm system initiation. This was confirmed by the Facilities Director during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Obstructed Access to Fire Alarm Pull Stations
E
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

Surveyors found that access to two fire alarm pull stations was blocked by portable nurse worktables and a dirty linen cart, with the Maintenance Supervisor confirming staff awareness of proper storage procedures. The facility's policy requires maintenance of safe and accessible equipment, but these obstructions were not removed as required.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Manual Fire Alarm Pull Stations Missing Protective Snap Bars
D
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

Two manual fire alarm pull stations were found without their required protective snap bars, one near a resident room and another near a nurse station. The Maintenance Supervisor indicated that patients may have removed the snap bars. This deficiency impacted two smoke compartments and left the pull stations not properly maintained as designed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Pull Station Obstructed by Storage Items
E
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

The facility failed to maintain the initiation of the required fire alarm system on one level. A fire alarm pull station in the Activities Department was blocked by storage items, making it inaccessible. This was confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Manual Pull Stations Obstructed
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

The facility failed to ensure fire alarm manual pull stations were accessible, as required by NFPA 72:2010. Observations revealed that a pull station in the dining room was blocked by a table, and another in the physical therapy room was obstructed by wheelchairs and a bed. This deficiency could potentially affect all 83 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙