K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
E

Smoke Barrier Door Deficiency on First Floor

Dunmore Health Care CenterDunmore, Pennsylvania Survey Completed on 12-23-2024

Summary

The facility failed to maintain the smoke barrier separation doors on the first floor, specifically those located closest to the Nurse's Station. During an observation conducted on December 23, 2024, at 10:50 a.m., it was noted that these doors required adjustment to fully latch. This deficiency was confirmed during an exit interview with the Facility Administrator and the Facilities Manager later that day, between 1:25 p.m. and 1:30 p.m.

Plan Of Correction

First floor, smoke barrier separation doors, were adjusted and fully latch. Smoke barrier separation doors throughout the facility were audited and fully latch. NHA/Designee educated the Maintenance Director on NFPA 101 Subdivision of Building Spaces-Smoke Barrier. Maintenance Director will randomly audit Smoke barrier separation doors 1x week for 4 weeks then monthly x2.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0374 citations
Failure to Maintain Smoke Barrier Doors to Resist Passage of Smoke
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors identified that smoke barrier doors in two areas of the facility were not maintained to resist the passage of smoke. In one hallway outside a nurse's station, the smoke barrier doors did not close smoke-tight because the door frame was unsecured within the wall. In another area outside the lobby, the smoke barrier doors failed to swing and close smoke-tight due to a broken door closer, and this problem remained uncorrected at a later revisit survey, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Close Smoke-Tight
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Smoke barrier doors near the Laundry Area did not fully close when released from hold-open devices, resulting in a failure to maintain smoke-tight conditions as required. Facility leadership confirmed the deficiency during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Self-Close and Latch
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a third-floor room failed to self-close and latch when tested, affecting two smoke compartments. Facility leadership confirmed the deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Door Hardware Failed to Latch Properly
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that the double smoke barrier door between two compartments did not latch as required, with the hardware failing to function per manufacturer specifications. This issue was confirmed by the Director of Facilities and affected two smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure of Fire/Smoke Barrier Doors to Close as Required
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors found that several fire/smoke barrier doors, including those near the DON office and in resident rooms, were unable to close properly during both routine checks and a fire alarm test. Staff confirmed they were unaware of the closure requirements for these doors, resulting in noncompliance with NFPA 101-2012 standards and potentially affecting multiple residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Achieve Smoke-Tight Fit
F
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a resident room and by a nurses station leading to the dining room did not fully close and latch to a smoke-tight fit as required by LSC. The Maintenance Director confirmed these findings.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙