K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
E

Failure of Fire/Smoke Barrier Doors to Close as Required

Urbana Health & Rehabilitation CenterUrbana, Ohio Survey Completed on 06-05-2025

Summary

During a facility tour, surveyors observed that several fire/smoke barrier doors did not function as required by NFPA 101-2012 standards. Specifically, the double corridor fire/smoke barrier door near the Director of Nursing office and a resident room was unable to close. Additionally, fire/smoke barrier doors in two resident rooms failed to close correctly. When the fire alarm system was tested, these doors were also unable to close completely, indicating a persistent issue with the self-closing or automatic-closing mechanisms required for smoke barrier doors. Staff interviews confirmed the findings at the time of discovery. A staff member acknowledged being unaware of the specific requirements for fire/smoke barrier doors as outlined in the NFPA 101-2012 Edition. The observed deficiencies directly contravened the standards, which mandate that such doors must be self-closing or automatic-closing and able to close fully upon activation of the fire alarm or loss of power to the hold-open device. The report also notes a failure to maintain smoking areas in accordance with NFPA 101-2012 Edition, Section 19.7.4. However, the detailed findings and observations related to the smoking area deficiency are not fully included in the provided excerpt. The primary documented deficiency centers on the inability of fire/smoke barrier doors to close as required, potentially affecting 13 out of 46 residents in the facility.

Plan Of Correction

K741 Urbana Health and Rehab wishes to point out to any person who reviews this document that we do not necessarily agree with the citations with which we were cited. However, the law requires us to prepare a plan of correction for the citations regardless of whether we agree with them or not. Thus, we have prepared such a plan as noted below. Please note though, that this plan does not constitute an admission that the citations are either legally or factually correct. This plan of correction is not meant to establish any standard of care, contract, obligation, or position, and Urbana Health and Rehab reserves all rights to raise all possible contentions and defenses in any civil or criminal action or proceeding. Please accept 7/30/25 as the facility's allegation of compliance date. The facility failed to ensure safe smoking as evidenced by cigarette butts on the ground around staff smoking area, lining the emergency lane parking, yellow line on sidewalk, floor of employee smoking area, in front of storage area that stored combustible materials. Additionally, there were no self-closing metal containers into which ashtrays could be emptied. Step 1: Director of Maintenance cleaned the staff smoking area on 6-6-25. A 16 qt. covered, self-closing, metal receptacle was obtained for placement of cigarette butts and placed in the smoking area on 6/15/25. Step 2: Audit was completed by DON/ADON on designated smoking areas on 6-6-25 for compliance issues, with no negative findings. Step 3: All staff educated on NFPA 101 Smoking Regulations: safe smoking practices and the importance of proper disposal of used smoking materials.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0374 citations
Failure to Maintain Smoke Barrier Doors to Resist Passage of Smoke
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors identified that smoke barrier doors in two areas of the facility were not maintained to resist the passage of smoke. In one hallway outside a nurse's station, the smoke barrier doors did not close smoke-tight because the door frame was unsecured within the wall. In another area outside the lobby, the smoke barrier doors failed to swing and close smoke-tight due to a broken door closer, and this problem remained uncorrected at a later revisit survey, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Close Smoke-Tight
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Smoke barrier doors near the Laundry Area did not fully close when released from hold-open devices, resulting in a failure to maintain smoke-tight conditions as required. Facility leadership confirmed the deficiency during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Self-Close and Latch
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a third-floor room failed to self-close and latch when tested, affecting two smoke compartments. Facility leadership confirmed the deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Door Hardware Failed to Latch Properly
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that the double smoke barrier door between two compartments did not latch as required, with the hardware failing to function per manufacturer specifications. This issue was confirmed by the Director of Facilities and affected two smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Achieve Smoke-Tight Fit
F
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a resident room and by a nurses station leading to the dining room did not fully close and latch to a smoke-tight fit as required by LSC. The Maintenance Director confirmed these findings.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Close During Fire Alarm Testing
F
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors found that smoke barrier doors in three compartments did not release from magnetic holders and close during fire alarm testing, despite activation of smoke detectors, pull stations, and waterflow tests. Staff and a vendor had differing understandings of the door operation, and the malfunction affected all residents in the affected areas.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙