K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
E

Failure to Maintain Smoke Barrier Doors to Resist Passage of Smoke

Accela Rehab And Care Center At SomertonPhiladelphia, Pennsylvania Survey Completed on 04-30-2026

Summary

Surveyors found that smoke barrier doors on one of two facility levels were not maintained to resist the passage of smoke as required by NFPA 101. During observation, the smoke barrier doors in the A09 hallway outside the nurse's station did not close smoke-tight when tested because the door frame was unsecured within the wall. In addition, the smoke barrier doors in the A-Wing outside the lobby failed to swing and close smoke-tight due to a broken door closer. These deficiencies were confirmed during interviews with the Administrator and Maintenance Director. On a subsequent onsite revisit survey, surveyors observed that the previously cited issue with the smoke barrier doors in the A-Wing outside the lobby, which failed to swing and close smoke-tight due to a broken door closer, had not been corrected. This uncorrected deficiency was again confirmed with the Administrator and Maintenance Director during the revisit exit interview.

Plan Of Correction

Preparation and /or execution of this plan does not constitute admission or agreement by the provider of the truths or facts alleged or conclusions set forth in the statement of deficiencies. The plan of correction is prepared and/or executed with federal and state law requirements. Identification of other residents or areas having the potential to be affected due to the nature of the deficiency: The deficient practice has the potential to affect all residents. Corrective action 1. Smoke barrier door closures repaired and adjusted to ensure appropriate closure 4/30/26. 2. Maintenance director or designee to re-educate maintenance staff on the importance of maintaining facility smoke barrier doors 3. Maintenance director or designee to audit facility smoke barrier doors to ensure appropriate closure. Weekly X4 monthly X2 4. Maintenance director or designee to audit laundry rooms and medical supply rooms for smoke detectors weekly X4 monthly X2 5. Results will be reviewed at the quarterly QAPI meeting.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0374 citations
Smoke Barrier Doors Failed to Close Smoke-Tight
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Smoke barrier doors near the Laundry Area did not fully close when released from hold-open devices, resulting in a failure to maintain smoke-tight conditions as required. Facility leadership confirmed the deficiency during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Self-Close and Latch
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a third-floor room failed to self-close and latch when tested, affecting two smoke compartments. Facility leadership confirmed the deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Door Hardware Failed to Latch Properly
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that the double smoke barrier door between two compartments did not latch as required, with the hardware failing to function per manufacturer specifications. This issue was confirmed by the Director of Facilities and affected two smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure of Fire/Smoke Barrier Doors to Close as Required
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors found that several fire/smoke barrier doors, including those near the DON office and in resident rooms, were unable to close properly during both routine checks and a fire alarm test. Staff confirmed they were unaware of the closure requirements for these doors, resulting in noncompliance with NFPA 101-2012 standards and potentially affecting multiple residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Achieve Smoke-Tight Fit
F
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a resident room and by a nurses station leading to the dining room did not fully close and latch to a smoke-tight fit as required by LSC. The Maintenance Director confirmed these findings.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Close During Fire Alarm Testing
F
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors found that smoke barrier doors in three compartments did not release from magnetic holders and close during fire alarm testing, despite activation of smoke detectors, pull stations, and waterflow tests. Staff and a vendor had differing understandings of the door operation, and the malfunction affected all residents in the affected areas.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer