K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Failure to Maintain Sprinkler System Testing and Fire Drill Documentation

Glades Health Care CenterPahokee, Florida Survey Completed on 04-29-2026

Summary

Surveyors identified deficiencies related to the facility’s failure to maintain and test its automatic sprinkler and associated fire protection systems in accordance with NFPA 101 and NFPA 25. During record review between 9:15 AM and 1:30 PM with the Maintenance Director, the facility was unable to provide documentation that an annual flow test had been performed on the on-site fire hydrant as required. The Maintenance Director acknowledged that the facility failed to provide documentation that this annual hydrant flow test was completed. Further record review during the same time period showed that the facility also lacked documentation of the required five-year gallons-per-minute (GPM) testing of the fire hydrant. In addition, the facility could not produce records showing that a five-year internal inspection of the fire riser had been performed. The Maintenance Director acknowledged the absence of documentation for the five-year internal riser inspection. Surveyors also found that the facility failed to provide documentation that a five-year hydrostatic test of the Fire Department Connection (FDC) had been completed. Separately, the surveyors reviewed fire drill records and determined that the facility did not have documentation of required fire drills for each shift per quarter. Specifically, fire drills were missing for the third shift of the first quarter of one year and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that the facility failed to provide documentation that these fire drills were performed.

Plan Of Correction

The five year gallon per minute testing was completed on [R] The five year internal inspection was performed on the riser on [R] The five year hydrostatic testing was performed and completed on [R] The five year gallon per minute testing on the fire hydrant was completed on [R] The facility has determined that all residents have the potential to be affected. An in-service education program will be conducted by the administrator. The administrator will conduct for a period of three months a random audit of completed documentation. The five year gallon per minute testing was completed on [R] The five year internal inspection was performed on the riser on [R] The five year hydrostatic testing was performed and completed on [R] The five year gallon per minute testing on the fire hydrant was completed on [R] The facility has determined that all residents have the potential to be affected. An in-service education program will be conducted by the administrator. The administrator will conduct for a period of three months a random audit of completed documentation.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Required 20-Year Sprinkler Head Testing
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to perform and/or document the required 20-year testing of quick-response sprinkler heads throughout all smoke compartments, as required by NFPA 25. During review of Life Safety records with the Director of Environmental Services, no documentation of a 20-year sprinkler test was available, despite the sprinklers being original to the building. Spare sprinkler heads in stock showed manufacturing dates from the late 1990s, and the outside testing company could not provide historical records to confirm that the mandated 20-year testing had ever been completed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙