K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Failure to Perform and Document Required 20-Year Sprinkler Head Testing

Claremont Manor Care CenterClaremont, California Survey Completed on 03-12-2026

Summary

Surveyors identified a deficiency related to the facility’s failure to conduct the required 20-year testing of quick-response sprinkler heads in accordance with NFPA 25. During an interview and record review with the Director of Environmental Services (DES), the facility’s Life Safety materials binder was found to lack any record of a 20-year sprinkler test for the quick-response sprinkler heads installed throughout all four smoke compartments. The DES reported that the sprinklers were original to the building, which was constructed in 1999, and stated that the required testing may have been done in 2009, but there was no documentation on site to verify that the test had occurred. Further observation and interview showed that spare quick-response sprinkler heads in the facility’s stock had manufacturing dates such as 1996 and 1999 printed on them, confirming the age of the system components. The DES indicated that the outside testing company was unable to locate records from that time period to confirm whether the 20-year sprinkler testing had been performed. As a result, there was no evidence available to demonstrate that the required 20-year sprinkler head testing had been completed for the sprinkler system serving all four smoke compartments, as required by NFPA 25 and related Life Safety Code provisions.

Plan Of Correction

K353 – Sprinkler System Maintenance and Testing (NFPA 25) How corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice. There were no residents identified as directly affected by this deficient practice. Upon identification on 3/12/2026, the facility immediately contacted a licensed fire protection vendor to schedule the required 20-year sprinkler head testing. The sprinkler system remains fully operational and monitored, ensuring continued fire protection coverage while corrective actions are implemented. How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken. On 3/13/2026, the Director of Environmental Services (DES) conducted a review of all available Life Safety documentation to confirm the absence of records for the 20-year sprinkler testing across all smoke compartments. The contracted licensed vendor has been engaged and performed testing on representative sprinkler heads throughout the facility in accordance with NFPA 25 standards on 3/19/2026. Response time, response time index and water seal release all passed. The report is dated 3/20/2026. What measures will be put into place or what systemic changes will the facility make to ensure that the deficient practice does not recur. To prevent recurrence, the facility has implemented a Life Safety compliance tracking system that includes all required inspection, testing, and maintenance schedules in accordance with NFPA 25. On 3/13/2026, the DES re-educated staff on regulatory requirements for sprinkler system testing, including 20-year testing requirements for quick-response sprinkler heads. The facility will maintain all Life Safety documentation in a centralized, secure, and readily accessible binder and electronic file. Additionally, the facility will contract with a licensed fire protection vendor to ensure ongoing compliance with all inspection and testing requirements. How the facility plans to monitor its performance to make sure that solutions are sustained. The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system. The DES or designee will track all required Life Safety inspections and testing through a compliance calendar and conduct monthly audits to ensure all required documentation is current and on file. Results of these audits will be reported to the Administrator and reviewed quarterly in the Quality Assurance and Performance Improvement (QAPI) committee meeting. Any identified gaps will be addressed immediately. The QAPI committee will monitor compliance until sustained. Include dates when corrective actions will be completed. The corrective action completion dates must be acceptable to the State Agency.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙