K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
D

Failure to Complete Required Fire Alarm System Sensitivity Testing

Nspire Healthcare TamaracTamarac, Florida Survey Completed on 01-22-2026

Summary

The facility failed to maintain its fire alarm system in accordance with NFPA 101 and NFPA 72 standards. During a record review with the Regional Maintenance Director, it was found that the biennial smoke detector sensitivity testing did not include 11 out of 73 smoke detectors. Additionally, the repairs inspection report did not indicate that the smoke detectors were sensitivity tested, nor did it provide the results of such testing. The annual fire alarm report listed 23 duct detectors in the inventory, but the duct detector differential pressure testing documented 24 duct detectors tested, and the smoke detector sensitivity testing only included 22 duct detectors, leaving two duct detectors untested for sensitivity. These discrepancies were identified through a combination of record review and staff interviews. The Regional Maintenance Director acknowledged the findings during the review. The records failed to demonstrate that all required smoke and duct detectors underwent the necessary sensitivity testing as mandated by the applicable codes and standards. The deficiency affects all residents and staff in the affected smoke compartments, as the fire alarm system is a critical component of the facility's safety infrastructure. The findings were reviewed with both the Administrator and the Regional Maintenance Director at the exit conference, and photographic evidence was obtained to support the observations.

Plan Of Correction

Corrective Action for Affected Residents: All smoke detectors and duct detectors identified as not sensitivity tested or inconsistently documented will be addressed/tested. The facility will be coordinating with the licensed fire alarm vendor to: complete sensitivity testing on the 11 of 73 smoke detectors that were not tested during the biennial testing dated. Complete sensitivity testing on the two (2) duct detectors that were not included in prior sensitivity testing. Reconcile and correct discrepancies between: smoke detector sensitivity testing reports, duct detector differential pressure testing reports, and annual fire alarm inspection reports. Identification of Other Residents Potentially Affected: A 100% review of fire alarm testing records was conducted to ensure all devices are included and properly documented. Measures to Prevent Recurrence: Maintenance leadership will be re-educated on NFPA 72 sensitivity testing requirements and the importance of reconciling all fire alarm testing reports for consistency and completeness prior to acceptance. Monitoring / Quality Assurance: Annual testing will be verified by the Maintenance Director and reviewed by the Administrator during Life Safety reviews. Corrective Action for Affected Residents: The facility will correct the identified sprinkler system deficiency to ensure consistent and reliable fire protection within the affected smoke compartment. Specifically, the two (2) sprinkler heads in the Main Lobby that were identified as standard response sprinklers were scheduled for replacement. These sprinkler heads will be replaced with quick response sprinkler heads to ensure uniform sprinkler response characteristics throughout the area. Replacement will be completed by a licensed fire sprinkler contractor, and documentation will be maintained on-site. Identification of Other Residents Potentially Affected: To identify any additional areas that may be affected. Corrective Action for Affected Residents: All smoke detectors and duct detectors identified as not sensitivity tested or inconsistently documented will be addressed/tested. The facility will be coordinating with the licensed fire alarm vendor to: complete sensitivity testing on the 11 of 73 smoke detectors that were not tested during the biennial testing dated. Complete sensitivity testing on the two (2) duct detectors that were not included in prior sensitivity testing. Reconcile and correct discrepancies between: smoke detector sensitivity testing reports, duct detector differential pressure testing reports, and annual fire alarm inspection reports. Identification of Other Residents Potentially Affected: A 100% review of fire alarm testing records was conducted to ensure all devices are included and properly documented. Measures to Prevent Recurrence: Maintenance leadership will be re-educated on NFPA 72 sensitivity testing requirements and the importance of reconciling all fire alarm testing reports for consistency and completeness prior to acceptance. Monitoring / Quality Assurance: Annual testing will be verified by the Maintenance Director and reviewed by the Administrator during Life Safety reviews.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0345 citations
Failure to Perform and Document Annual Duct Detector Differential Testing
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to perform and/or document the required annual Duct Detector Differential testing for the fire alarm system in accordance with NFPA 101, NFPA 70, and NFPA 72. During record review and interviews with the Director of Facilities, no documentation could be produced to show that this annual testing had been completed, and the Director acknowledged the lack of records. This deficiency was cited as potentially affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Fire Alarm System Inspection and Testing Documentation
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

The facility did not maintain required inspection and testing documentation for its fire alarm system. During surveyor review, no records could be produced to show that semi-annual visual inspections or the two-year smoke detector sensitivity testing had been completed, and the maintenance supervisor confirmed that this documentation was unavailable at the time of the survey. This deficiency affected the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Properly Test Fire Alarm System Components
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and properly test multiple fire alarm system components, including smoke detectors near the medical supply area and house laundry that could not be located, elevator fire hat and primary recall functions that could not be reset due to lack of a key, and an untested elevator control shunt trip. On revisit, the missing smoke detectors had been replaced with battery-operated units that were not connected to the building’s fire alarm notification system, and the previously identified fire alarm issues remained uncorrected.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Fire Alarm Documentation and Testing Records
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain required fire alarm system documentation and testing records. During record review with the Maintenance Director, there was no vendor-signed log book at the fire panel documenting work performed at each visit, no documentation of biennial smoke detector sensitivity testing, and no fire alarm system design plans located at the fire panel, as required by NFPA 101 and NFPA 72.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Alarm System in Proper Working Order
D
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors identified that the facility did not maintain its fire alarm system in accordance with NFPA 72 when the fire alarm control panel was observed displaying a trouble signal. During the observation, the Maintenance Director confirmed that the trouble condition was related to a faulty heat detector. This unresolved trouble indication showed that the fire alarm system was not being properly maintained to ensure it functioned as designed for the entire building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Semi-Annual Fire Alarm System Inspections
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors determined that the facility did not comply with NFPA 101 and NFPA 72 requirements for fire alarm system maintenance when record review showed incomplete fire alarm inspection reports and no documentation of required semi-annual visual inspections of fire detection components. The Director of Maintenance confirmed that these six-month inspections had not been documented and reported being unaware of the requirement, creating a deficiency that had the potential to affect all four residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙