K0353 K353: Inspect, test, and maintain automatic sprinkler systems.

Failure to Maintain Fire Sprinkler System per NFPA Standards

Lexington Healthcare And Rehabilitation CenterSaint Petersburg, Florida Survey Completed on 07-16-2025

Summary

The facility failed to maintain its automatic fire sprinkler system (AFSS) in accordance with NFPA 101 and NFPA 25 standards. During a facility tour with the Facility Manager, surveyors observed multiple deficiencies in the sprinkler system, including corroded and dust-loaded sprinkler heads. Specifically, all 14 pendant sprinkler heads in the front porch and exterior covered drive were found to be corroded, as well as 2 of 3 pendant sprinkler heads in the laundry washroom. Additionally, 1 of 2 upright sprinkler heads behind the dryers was corroded, and another upright sprinkler head in the same area was loaded with dust. These findings were confirmed through interviews with the Facility Manager conducted at the time of observation. The report documents that the facility did not meet the required standards for inspection, testing, and maintenance of the AFSS, as outlined in the referenced NFPA codes. No information about residents or their medical conditions is included in the report.

Plan Of Correction

The facility Administrator/Designee contacted a vendor to service the 14 pendant sprinkler heads located at the front porch and cover drive, the 2 pendant sprinkler heads located in the laundry washroom, the 1 upright sprinkler head located behind the dryers, and the 1 sprinkler head covered with dust behind the dryers, as it relates to meeting compliance with NFPA 101. No residents were found to be affected by this alleged deficient practice. The Nursing Home Administrator educated the Maintenance staff on maintaining sprinkler heads in accordance with NFPA 101, which includes maintaining them free of dust or corrosion. The Nursing Home Administrator/Designee will conduct weekly audits for 3 months on 5 sprinkler heads to ensure they are maintained in accordance with NFPA 101, including being free of dust and corrosion. The findings of these audits will be reported in the next risk management/Quality assurance committee meeting until the committee determines substantial compliance has been met and recommends quarterly monitoring. The facility Administrator/Designee contacted a vendor to service the 14 pendant sprinkler heads located at the front porch and cover drive, the 2 pendant sprinkler heads located in the laundry washroom, the 1 upright sprinkler head located behind the dryers, and the 1 sprinkler head covered with dust behind the dryers, as it relates to meeting compliance with NFPA 101. No residents were found to be affected by this alleged deficient practice. The Nursing Home Administrator educated the Maintenance staff on maintaining sprinkler heads in accordance with NFPA 101, which includes maintaining them free of dust or corrosion. The Nursing Home Administrator/Designee will conduct weekly audits for 3 months on 5 sprinkler heads to ensure they are maintained in accordance with NFPA 101, including being free of dust and corrosion. The findings of these audits will be reported in the next risk management/Quality assurance committee meeting until the committee determines substantial compliance has been met and recommends quarterly monitoring.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙