K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
D

Failure to Maintain Fire Sprinkler System Free of Foreign Material

Ceres Postacute CareCeres, California Survey Completed on 05-19-2025

Summary

The facility failed to maintain its automatic fire sprinkler system in accordance with NFPA 25 standards, as evidenced by the presence of foreign material on sprinkler heads. During a facility tour, surveyors observed a sprinkler head on the overhang of the Southwest Emergency Exit by Room 21 that was covered with spider webs and dirt. The Maintenance Director acknowledged that this sprinkler head had been ignored and may have been in that condition for some time. Additionally, a sprinkler head located in the closet of the Administrator Room was found to have paint covering it. The Maintenance Assistant stated that he had never paid attention to the closet sprinkler heads and that the condition may have persisted for a while. These deficiencies affected 18 of 43 residents in one of three smoke compartments and were identified through direct observation and staff interviews.

Plan Of Correction

How corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: Sprinkler head located on the overhang of the Southwest Emergency Exit by Room 21 was thoroughly cleaned on 5/20/25. Fire sprinkler vendor was notified and on 6/2/25 the sprinkler head located in closet of administrative DSD office is scheduled to be replaced by vendor. How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken: All residents have the potential to be affected by this deficient practice. No residents were found to be affected by this deficient practice. What measures will be put into place or what systemic changes in the facility will make to ensure that the deficient practice does not recur: Administrator will audit the reports from the sprinkler system vendor to check for accuracy and completion. How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken: All residents have the potential to be affected by this deficient practice. No residents were found to be affected by this deficient practice. What measures will be put into place or what systemic changes in the facility will make to ensure that the deficient practice does not recur: Administrator will audit the reports from the sprinkler system vendor to check for accuracy and completion. How the facility plans to monitor its performance to make sure that solutions are sustained: The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system. The Administrator shall report the outcome of the checks/inspections to the Quality Assurance and Assessment Committee (QA&A) during its monthly meeting. If determined that the facility has accomplished the objectives in the plan of correction as aforementioned and the results are successful, then the facility shall consider the matter resolved. The QA&A Committee shall continue to review until such time that the deficiency has been proven to be resolved for 3 consecutive months and/or as advised by the QA&A Committee. Date of Completion of Corrective Action: 06/02/2025

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙