K0351 K351: Install an approved automatic sprinkler system.
D

Sprinkler System Installation Noncompliance Due to Ceiling Modification

Rehabilitation Center Of The Palm Beaches, TheWest Palm Beach, Florida Survey Completed on 03-31-2025

Summary

During an unannounced Fire & Life Safety recertification survey, it was observed that the facility failed to maintain their sprinkler system installation in accordance with NFPA 101 and NFPA 13 standards. Specifically, in Electrical Room #5, the drop ceiling had been removed, resulting in two sprinkler heads being positioned too far below the new ceiling level. This alteration led to inadequate coverage by the sprinkler system in that room, as the sprinkler heads were no longer properly aligned with the ceiling as required by code. The deficiency was identified during a facility tour conducted with the Maintenance Director, who confirmed the findings during an interview. The issue was reviewed with both the Administrator and the Maintenance Director at the exit conference, and photographic evidence was obtained to document the noncompliance. No information regarding residents or their medical conditions was included in the report, and the deficiency was limited to the physical plant and fire safety systems.

Plan Of Correction

Preparation and/or execution of this plan of correction does not constitute admission or agreement of the provider of the truth of the alleged or conclusion set forth in the CMS measured star ratings. The plan of correction is prepared and executed solely because it is required by Federal and State Laws. K351 What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: 1. No residents were affected by this alleged deficient practice. How you will identify other residents having potential to be affected by the same deficient practice and what corrective action will be taken: 2. The facility will maintain the supervised automatic fire sprinkler system in accordance with NFPA 101. Electrical Room #5 is scheduled to be corrected on 4/15/25 to ensure adequate coverage of the automatic fire sprinkler system protection in accordance with NFPA 101. What measures will be put into place or what systematic changes you will make to ensure that the deficient practice does not recur: 3. Maintenance staff re-educated on ensuring inspection of every compartment for sprinkler system. How the corrective action(s) will be monitored to ensure the deficient practice will not recur, i.e., what quality assurance program will be put in place: 4. Maintenance Director or Designee will report the findings of the automatic fire sprinkler audits to the QAA&C monthly times three months or until substantial compliance is met.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0351 citations
Incomplete Sprinkler Coverage for Built-In Dining Room Cabinetry
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that floor-to-ceiling built-in millwork cabinetry with doors in the first floor dining room was installed and in use without interior sprinkler coverage or other required fire protection measures, and this cabinetry was not shown on the approved DOH renovation and sprinkler plans, preventing verification of proper sprinkler coverage; on revisit, the same lack of fire protection within the closed-door storage cabinetry remained uncorrected, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Sprinkler System Installation
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A deficiency was cited due to the facility not being fully protected by an approved automatic sprinkler system as required by the 2012 standards for existing nursing homes and hospitals.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Obstructions and Missing Ceiling Tiles
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that shower curtains in multiple resident rooms were within 18 inches of sprinkler heads, violating NFPA 13 requirements, and also noted missing ceiling tiles in two utility areas. These issues were confirmed by the Facilities Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Sprinkler Pipe for Mechanical Support
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A hot water pipe was observed being supported and hanging from a sprinkler pipe in the 300 wing mechanical room, contrary to NFPA 13 requirements for sprinkler system installation. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler System Installation in Electrical Room
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to install an automatic sprinkler system in the Main electrical (switchgear) Room in the basement, affecting one of three levels. This deficiency was confirmed during an exit interview with the Administrator, Maintenance Director, and Regional VP of Operations, indicating incomplete sprinkler protection as per NFPA standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Deficiency in Elevator Pit
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to maintain sprinkler system requirements as the hydraulic elevator pit lacked a sidewall sprinkler installed within two feet of the floor. This deficiency was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙