K0351 K351: Install an approved automatic sprinkler system.
E

Improper Use of Sprinkler Pipe for Mechanical Support

Marquette County Medical Care FacilityIshpeming, Michigan Survey Completed on 05-19-2025

Summary

A deficiency was identified when, during an observation in the 300 wing mechanical room, a hot water pipe was found being supported and hanging from a sprinkler pipe. This setup was not in accordance with NFPA 13, the Standard for the Installation of Sprinkler Systems, which requires that sprinkler systems be installed as specified and not used to support other building systems. The Maintenance Director confirmed this finding at the time of discovery. No information regarding specific residents, their medical history, or their condition at the time of the deficiency was provided in the report.

Plan Of Correction

Element 1: Hot water pipe was supported and hanging from sprinkler pipe. Hot water pipe will be removed from sprinkler pipe and supported from ceiling. Element 2: All residents/visitors/staff of the 300 wing have the potential to be impacted by this deficient practice in the event of need for sprinkler use. Element 3: On 06/03/2025 the hanger was removed from the sprinkler pipe and the hot water pipe was secured directly to the ceiling. Element 4: Physical Plant Manager will be responsible for sustained compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0351 citations
Incomplete Sprinkler Coverage for Built-In Dining Room Cabinetry
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that floor-to-ceiling built-in millwork cabinetry with doors in the first floor dining room was installed and in use without interior sprinkler coverage or other required fire protection measures, and this cabinetry was not shown on the approved DOH renovation and sprinkler plans, preventing verification of proper sprinkler coverage; on revisit, the same lack of fire protection within the closed-door storage cabinetry remained uncorrected, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Sprinkler System Installation
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A deficiency was cited due to the facility not being fully protected by an approved automatic sprinkler system as required by the 2012 standards for existing nursing homes and hospitals.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Obstructions and Missing Ceiling Tiles
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that shower curtains in multiple resident rooms were within 18 inches of sprinkler heads, violating NFPA 13 requirements, and also noted missing ceiling tiles in two utility areas. These issues were confirmed by the Facilities Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler System Installation in Electrical Room
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to install an automatic sprinkler system in the Main electrical (switchgear) Room in the basement, affecting one of three levels. This deficiency was confirmed during an exit interview with the Administrator, Maintenance Director, and Regional VP of Operations, indicating incomplete sprinkler protection as per NFPA standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Deficiency in Elevator Pit
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to maintain sprinkler system requirements as the hydraulic elevator pit lacked a sidewall sprinkler installed within two feet of the floor. This deficiency was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Attic Sprinkler System Not Installed per NFPA 13
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A review of facility records revealed that the dry sprinkler system in the attic had been capped off, leaving the attic without full sprinkler protection as required by NFPA 13. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙