K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
F

Failure to Provide Timely Fire Damper Inspection Documentation

Shorepointe Nursing CenterSt. Clair Shores, Michigan Survey Completed on 04-15-2025

Summary

The facility failed to provide evidence of the required quadrennial (every four years) servicing and inspection of their installed fire dampers, as mandated by regulatory standards. During a record review on April 15, 2025, it was found that the last recorded servicing of the fire dampers was dated June 16, 2020, and no documentation supporting compliance with the current inspection requirement was available for review. This deficiency was confirmed with the facility Maintenance Director at the time of the record review. The lack of current inspection documentation could affect all 175 residents in the event of a fire, as noted in the findings.

Plan Of Correction

K521 - HVAC 1. The facility failed to ensure heating, ventilation, and air conditioning in compliance with 9.2. a. The facility scheduled the required quadrennial serving and inspection of the installed Fire Dampers. 2. The Maintenance Director was educated on the required quadrennial serving and inspection of the installed fire dampers and proper documentation following required fire drills. 3. To ensure compliance is maintained, the Maintenance Director/designee will complete an audit monthly following each fire drill with proper documentation. Findings will be reported to the QAPI committee. 4. The facility Administrator will be responsible for assuring substantial compliance is attained through this plan of correction by 5/13/2025 and for sustained compliance thereafter.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0521 citations
Lack of Required Inspection and Testing Documentation for Fire Dampers
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors determined that the facility did not maintain required documentation showing that fire dampers had been inspected and tested in accordance with NFPA 101, NFPA 90A, and NFPA 80 standards. During record review, no inspection or testing records were produced despite multiple requests, even though fire dampers were observed throughout the building. The Maintenance Director confirmed that the documentation was not available, and this deficiency had the potential to affect all 69 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Address Fire Damper Deficiencies in HVAC System
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors identified that the facility did not maintain required inspections or corrective actions for fourteen fire and smoke dampers in the HVAC system, with issues such as non-functioning motors, missing dampers, and inadequate fire wall protection remaining unaddressed at the time of survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Address Failed Fire Dampers in HVAC System
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

The facility did not maintain its HVAC system as required, as two failed fire dampers were identified in an inspection report and there was no evidence of corrective action taken at the time of the survey. This was confirmed by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Venting of Portable Air Conditioning Unit
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

A portable air conditioning unit in a large common area near the Nurses' Station was observed to be vented directly into the ceiling's interstitial space instead of to the outside, contrary to NFPA 101 and manufacturer requirements. This was confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Exercise Fire Dampers at Required Intervals
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors determined that the facility did not provide documentation showing fire dampers were exercised within the required four-year interval, as confirmed by the Maintenance Director during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation and Final Inspection for Newly Installed Boiler
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

A newly installed boiler heating unit was found to lack manufacturer information and proof of state inspection. The facility could not provide documentation that required corrections identified by a state boiler inspector had been completed, and a final inspection had not been requested.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer