K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
E

Failure to Address Failed Fire Dampers in HVAC System

Sanatoga CenterPottstown, Pennsylvania Survey Completed on 08-06-2025

Summary

The facility failed to maintain its Heating, Ventilating, and Air Conditioning (HVAC) equipment as required. During a document review, it was found that the April 2025 Fire Damper Inspection Report identified two failed dampers. At the time of the survey, there was no evidence available to show that corrective action had been taken to address these failed dampers. This deficiency was confirmed during the exit interview with the Administrator and Maintenance Director. No information about residents or their medical conditions was included in the report.

Plan Of Correction

Vendor scheduled for damper repair. The Maintenance Director will be reeducated by the NHA/Designee on K0521 with focus on the importance of ensuring fire damper inspections are being completed and checking to ensure building is in compliance. Monthly audits to be completed x 4 to ensure valid fire damper inspection in place. Maintenance director/Designee will report findings of inspection at QAPI meeting.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0521 citations
Lack of Required Inspection and Testing Documentation for Fire Dampers
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors determined that the facility did not maintain required documentation showing that fire dampers had been inspected and tested in accordance with NFPA 101, NFPA 90A, and NFPA 80 standards. During record review, no inspection or testing records were produced despite multiple requests, even though fire dampers were observed throughout the building. The Maintenance Director confirmed that the documentation was not available, and this deficiency had the potential to affect all 69 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Address Fire Damper Deficiencies in HVAC System
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors identified that the facility did not maintain required inspections or corrective actions for fourteen fire and smoke dampers in the HVAC system, with issues such as non-functioning motors, missing dampers, and inadequate fire wall protection remaining unaddressed at the time of survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Venting of Portable Air Conditioning Unit
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

A portable air conditioning unit in a large common area near the Nurses' Station was observed to be vented directly into the ceiling's interstitial space instead of to the outside, contrary to NFPA 101 and manufacturer requirements. This was confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Exercise Fire Dampers at Required Intervals
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors determined that the facility did not provide documentation showing fire dampers were exercised within the required four-year interval, as confirmed by the Maintenance Director during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation and Final Inspection for Newly Installed Boiler
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

A newly installed boiler heating unit was found to lack manufacturer information and proof of state inspection. The facility could not provide documentation that required corrections identified by a state boiler inspector had been completed, and a final inspection had not been requested.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Required HVAC Damper Inspection
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

The facility was unable to provide documentation confirming that the mandatory four-year HVAC damper inspection had been completed, as discovered during a record review and confirmed by the maintenance director. This left the operational status of the dampers unverified.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer