K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
D

HVAC System Deficiency in Soiled Utility Rooms

Willowbrooke Court At St Andrews EstatesBoca Raton, Florida Survey Completed on 04-29-2025

Summary

The facility failed to maintain its Heating, Ventilation, and Air Conditioning (HVAC) system in accordance with NFPA 101 standards. During a facility tour conducted on April 29, 2025, between 1:15 PM and 2:45 PM, it was observed that the exhaust fans in the soiled utility holding rooms located in both the east wing of Pineapple Trail and the west wing of Lakeshore were not operational. These findings were made in the presence of the Director of Property Management. An interview with the Administrator and the Director of Property Management was conducted concurrently with the observations, during which they acknowledged the deficiencies. The findings were reviewed with both the Administrator and the Director of Property Management at the exit meeting on the same day at 3:00 PM. The report cites specific sections of NFPA 101 and NFPA 99 that were not adhered to, indicating a failure to comply with the required standards for HVAC maintenance.

Plan Of Correction

The statement made on this Plan of Correction are not and do not constitute an agreement with the alleged deficiencies herein. To remain in compliance with all federal and state regulation the center has taken or will take the actions set forth in the following plan of correction. The following plan of correction constitutes the center's allegation of compliance such that all alleged deficiencies cited have been or will be corrected by the date indicated. K521 HVAC Immediate Corrective Action: On 4/29/2025, HVAC technician assessed the exhaust fans immediately. A HVAC vendor was contracted to replace the two exhaust fans in soiled utility rooms. Identification of other residents potentially affected: All residents have the potential to be affected; however, based on inspection no residents were affected by this deficiency. HVAC system throughout the units were inspected to ensure compliance with NFPA 101 (2012 edition) and NFPA 99 (2012 edition) standards. No other HVAC system was identified out of compliance. Measures: Director of Property management and Maintenance assistance were re-educated on maintaining HVAC system by ensuring exhaust fans are inspected weekly, documented on preventative maintenance sheet and report any non-functioning HVAC system to supervisor immediately. Exhaust fans in biohazard rooms are required to be functioning to ensure ventilation to manage airborne particles and prevent contamination. Monitoring: The Director of Maintenance and Maintenance Assistants will complete weekly audits for 4 weeks and then monthly x two months to ensure in compliance with NFPA 101 (2012 edition) and NFPA 99 (2012 edition) standards. Director of Maintenance will report the findings to the Quality Assurance Performance improvement Committee Monthly X 3 months or until the committee determines substantial compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0521 citations
Lack of Required Inspection and Testing Documentation for Fire Dampers
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors determined that the facility did not maintain required documentation showing that fire dampers had been inspected and tested in accordance with NFPA 101, NFPA 90A, and NFPA 80 standards. During record review, no inspection or testing records were produced despite multiple requests, even though fire dampers were observed throughout the building. The Maintenance Director confirmed that the documentation was not available, and this deficiency had the potential to affect all 69 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Address Fire Damper Deficiencies in HVAC System
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors identified that the facility did not maintain required inspections or corrective actions for fourteen fire and smoke dampers in the HVAC system, with issues such as non-functioning motors, missing dampers, and inadequate fire wall protection remaining unaddressed at the time of survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Address Failed Fire Dampers in HVAC System
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

The facility did not maintain its HVAC system as required, as two failed fire dampers were identified in an inspection report and there was no evidence of corrective action taken at the time of the survey. This was confirmed by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Venting of Portable Air Conditioning Unit
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

A portable air conditioning unit in a large common area near the Nurses' Station was observed to be vented directly into the ceiling's interstitial space instead of to the outside, contrary to NFPA 101 and manufacturer requirements. This was confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Exercise Fire Dampers at Required Intervals
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors determined that the facility did not provide documentation showing fire dampers were exercised within the required four-year interval, as confirmed by the Maintenance Director during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation and Final Inspection for Newly Installed Boiler
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

A newly installed boiler heating unit was found to lack manufacturer information and proof of state inspection. The facility could not provide documentation that required corrections identified by a state boiler inspector had been completed, and a final inspection had not been requested.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙