K0351 K351: Install an approved automatic sprinkler system.
E

Improper Sprinkler Installation and Coverage

Kings Harbor Multicare CenterBronx, New York Survey Completed on 12-09-2024

Summary

The facility failed to ensure proper installation and coverage of the automatic sprinkler system as required by the 2012 NFPA 101 and 2010 NFPA 13 standards. During a recertification survey, it was observed that the sprinkler coverage was inadequate at the bottom landing of Stairwell D near a discharge door and in the emergency laundry storage room located in the basement. Additionally, a pendent sprinkler in the Soiled Utility Room was installed closer than four inches from the wall, which does not comply with the minimum distance requirements. Further deficiencies were noted during a tour of the kitchen, where a sidewall sprinkler was improperly installed on the ceiling of the dessert refrigerator. On the 3rd Floor of the Manor building, a sidewall sprinkler was also incorrectly installed on the ceiling of the Staff Restroom, and a pendent sprinkler was positioned closer than four inches from the wall in the resident's Shower Room. These observations indicate a failure to adhere to the specified guidelines for sprinkler installation, potentially compromising the effectiveness of the fire protection system.

Plan Of Correction

Plan of Correction: Approved December 31, 2024 1. What corrective actions will be accomplished for those residents found to have been affected by the deficient practice? a. No residents were identified as affected by the deficient practice. b. To comply with 2010 NFPA 13, the Director of Engineering contacted the Fire Safety Sprinkler Company to: 1. Install the lacking fire sprinklers at the bottom landing of stairwell D and the emergency laundry storage room. 2. Appropriate sprinkler will be installed in the soiled utility room, 3rd floor Manor building staff restroom and the residents shower room. 3. The facility has signed a contract for installation and work has commenced. 2. How would you identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken? a. The facility states that all residents have the potential to be affected by deficient practice. b. The contracted company reviewed sprinkler coverage throughout the facility and no additional areas were identified. 3. What measures will be put in place or what systemic changes you will make to ensure that the deficient practice does not recur? a. All Engineering staff will be informed and educated regarding sprinkler heads that were installed and their location, as well as overview of requirements for sprinkler coverage as per K351. b. The education will concentrate on the requirements to maintain sprinklers in all needed areas as well as ensure sprinkler heads are installed as required. c. A copy of the attendance will be maintained for reference and validation. 4. How the corrective actions will be monitored to ensure the deficient practice will not recur. i.e. what quality assurance program will be put into practice: a. The Director of Engineering has reviewed and revised the Environment Care Audit tool to ensure proper sprinkler coverage. b. Audits will be performed monthly by the Engineering Director/designee x 5 months and then annually thereafter to ensure compliance. c. Any issues identified by the audit will be corrected by the Engineering Department or our contracted sprinkler company as needed. d. Audit findings will be presented to the QA Committee quarterly for evaluation. 5. Completion Date: (MONTH) 7, 2025 Responsible Person: Director of Engineering

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0351 citations
Incomplete Sprinkler Coverage for Built-In Dining Room Cabinetry
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that floor-to-ceiling built-in millwork cabinetry with doors in the first floor dining room was installed and in use without interior sprinkler coverage or other required fire protection measures, and this cabinetry was not shown on the approved DOH renovation and sprinkler plans, preventing verification of proper sprinkler coverage; on revisit, the same lack of fire protection within the closed-door storage cabinetry remained uncorrected, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Sprinkler System Installation
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A deficiency was cited due to the facility not being fully protected by an approved automatic sprinkler system as required by the 2012 standards for existing nursing homes and hospitals.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Obstructions and Missing Ceiling Tiles
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that shower curtains in multiple resident rooms were within 18 inches of sprinkler heads, violating NFPA 13 requirements, and also noted missing ceiling tiles in two utility areas. These issues were confirmed by the Facilities Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Sprinkler Pipe for Mechanical Support
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A hot water pipe was observed being supported and hanging from a sprinkler pipe in the 300 wing mechanical room, contrary to NFPA 13 requirements for sprinkler system installation. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler System Installation in Electrical Room
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to install an automatic sprinkler system in the Main electrical (switchgear) Room in the basement, affecting one of three levels. This deficiency was confirmed during an exit interview with the Administrator, Maintenance Director, and Regional VP of Operations, indicating incomplete sprinkler protection as per NFPA standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Deficiency in Elevator Pit
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to maintain sprinkler system requirements as the hydraulic elevator pit lacked a sidewall sprinkler installed within two feet of the floor. This deficiency was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙