K0351 K351: Install an approved automatic sprinkler system.
D

Deficient Sprinkler Coverage in Key Areas

Briarcliff Manor Center For Rehab And Nursing CareBriarcliff Manor, New York Survey Completed on 03-20-2025

Summary

During a life safety recertification survey, several deficiencies were identified in the facility's sprinkler system coverage, which did not comply with NFPA 101 and NFPA 13 standards. Specifically, the survey revealed that sprinkler coverage was missing in the alcove area of the soiled utility discharge linen chute room. Additionally, the walk-in box used for dry storage in the storage room on corridor D lacked sprinkler coverage. Furthermore, in one of the emergency exit stairwells, sprinkler coverage was not observed under the first accessible landing, affecting two resident floors and the basement. These deficiencies were noted during a survey conducted between 9:30 AM and 3:30 PM. At approximately 11:40 AM, the absence of sprinkler coverage in the alcove area was observed. By 12:00 PM, the lack of sprinkler coverage in the walk-in box was identified, and at 12:50 PM, the deficiency in the stairwell was noted. The Director of Maintenance acknowledged these findings during an interview and mentioned that a vendor would be contacted to address the issues.

Plan Of Correction

Plan of Correction: Approved April 10, 2025 K351 I. Immediate Corrective Action: 1. Soiled Utility Discharge Linen Chute Room (Alcove Area): - On 3/19/25, the Director of Maintenance immediately arranged for an inspection and installation of sprinkler coverage in the alcove area adjacent to the discharge chute in the soiled utility room. - Sprinkler coverage was installed and tested by a certified sprinkler contractor on 3/19/25, ensuring compliance with NFPA 101 and NFPA 13 standards. 2. Walk-In Storage Box: - On 3/19/25, the Director of Maintenance contacted a certified contractor to install the missing dry sprinkler coverage in the walk-in box used for storage in the storage room on corridor D. - Sprinkler coverage was installed and tested by the contractor on 3/19/25, ensuring full compliance with NFPA 101 and NFPA 13. 3. Stairwell Landing (Basement): - A sprinkler contractor was contacted to install sprinkler coverage under the first accessible landing in the emergency exit stairwell located in corridor 4 in the basement. - The missing sprinkler coverage was installed and tested ensuring compliance with NFPA 101 and NFPA 13. II. Identification of Others: - All residents have the potential to be affected. - The Director of Maintenance conducted a thorough inspection of all other stairwells, utility rooms, and storage areas on the premises to ensure there are no further gaps in sprinkler coverage. - Additional checks were made to verify compliance in all areas, and no further issues were found. III. Systemic Changes: 1. The Director of Maintenance reviewed the facility’s sprinkler system installation policy to ensure that all areas, including utility rooms, storage spaces, and stairwells, are covered in accordance with NFPA 101 and NFPA 13. - A new protocol was implemented for regular, detailed inspections of sprinkler coverage during routine maintenance rounds to ensure no areas are missed in the future. 2. A review of all floor plans was conducted to verify that sprinkler coverage is properly indicated and confirmed for all spaces. 3. The Director of Maintenance in-serviced to understand the importance of compliance with sprinkler installation standards and the process for identifying and addressing gaps in coverage. IV. Quality Assurance: 1. A new audit tool was created by the Director of Maintenance to track the status of sprinkler system coverage throughout the facility, ensuring ongoing compliance with NFPA 101 and NFPA 13. - Monthly inspections and audits of all sprinkler systems, including utility rooms, storage areas, and stairwells, will be conducted with findings documented for review. 2. The results of the audits and any corrective actions will be reported to QAPI quarterly. V. Person Responsible: - Director of Maintenance

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0351 citations
Incomplete Sprinkler Coverage for Built-In Dining Room Cabinetry
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that floor-to-ceiling built-in millwork cabinetry with doors in the first floor dining room was installed and in use without interior sprinkler coverage or other required fire protection measures, and this cabinetry was not shown on the approved DOH renovation and sprinkler plans, preventing verification of proper sprinkler coverage; on revisit, the same lack of fire protection within the closed-door storage cabinetry remained uncorrected, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Sprinkler System Installation
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A deficiency was cited due to the facility not being fully protected by an approved automatic sprinkler system as required by the 2012 standards for existing nursing homes and hospitals.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Obstructions and Missing Ceiling Tiles
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that shower curtains in multiple resident rooms were within 18 inches of sprinkler heads, violating NFPA 13 requirements, and also noted missing ceiling tiles in two utility areas. These issues were confirmed by the Facilities Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Sprinkler Pipe for Mechanical Support
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A hot water pipe was observed being supported and hanging from a sprinkler pipe in the 300 wing mechanical room, contrary to NFPA 13 requirements for sprinkler system installation. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler System Installation in Electrical Room
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to install an automatic sprinkler system in the Main electrical (switchgear) Room in the basement, affecting one of three levels. This deficiency was confirmed during an exit interview with the Administrator, Maintenance Director, and Regional VP of Operations, indicating incomplete sprinkler protection as per NFPA standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Deficiency in Elevator Pit
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to maintain sprinkler system requirements as the hydraulic elevator pit lacked a sidewall sprinkler installed within two feet of the floor. This deficiency was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙