K0324 K324: Provide properly protected cooking facilities.
F

Deficiency in Fire Suppression System Maintenance

Briarcliff Manor Center For Rehab And Nursing CareBriarcliff Manor, New York Survey Completed on 03-20-2025

Summary

The facility failed to ensure that the Ansul fire suppression system and the K extinguisher in the kitchen were inspected and maintained according to the relevant NFPA standards. During a Life Safety recertification survey, it was observed that the monthly inspection tag for the Ansul system was blank, indicating that inspections were not documented as required. This lack of documentation suggests that the necessary monthly inspections may not have been conducted, which is a violation of NFPA 101, NFPA 10, and NFPA 17 A standards. Additionally, the K extinguisher located adjacent to the stove was found with its pressure gauge needle in the recharge zone, rather than the full zone, indicating that it was not in proper working condition. The service tag on the extinguisher showed that it was last recharged in 2024, yet it was not adequately maintained to ensure it remained operational. These deficiencies were identified during a tour of the kitchen, and the Director of Maintenance acknowledged the findings.

Plan Of Correction

Plan of Correction: Approved April 11, 2025 K324 I. Immediate Corrective Action: 1. Ansul System Inspection Tag: - On 3/20/25, the Director of Maintenance immediately addressed the issue with the Ansul system inspection tag and signed for the current month. 2. K Extinguisher Pressure Gauge: - The K extinguisher was immediately removed from service and replaced with a fully charged extinguisher, ensuring it was in the full zone (green). - The service company was contacted to inspect and recharge the K extinguisher. The fire extinguisher has been replaced and recharged. II. Identification of Others: - All residents have the potential to be affected. - The Director of Maintenance conducted a review of all fire suppression systems and extinguishers in the facility to ensure compliance with NFPA 101, NFPA 10, and NFPA 17 A. III. Systemic Changes: 1. The Director of Maintenance reviewed the facility's fire safety and inspection procedures. - The policy was updated and reviewed to ensure that all fire suppression system inspection tags are completed and signed monthly. - Maintenance staff were in serviced to consistently monitor and document inspections monthly. A checklist was updated for fire extinguishers, including monthly checks of pressure gauges to ensure that all extinguishers are within the full zone. This checklist will be used by staff during routine inspections. IV. Quality Assurance: 1. An audit tool was updated to track the completion and accuracy of monthly fire suppression system inspections and extinguisher checks. 2. Monthly audits will be performed for six months of all ansul systems and fire extinguishers to ensure compliance with NFPA 101, NFPA 10, and NFPA 17 A. 3. The results of the monthly audits will be reviewed during QAPI and reported quarterly. V. Person Responsible: - Director of Maintenance

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0324 citations
Commercial Cooking Hood Not Maintained Grease Tight per NFPA Standards
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility’s only commercial cooking hood was not maintained in accordance with NFPA 101 and NFPA 96 requirements. During a kitchen tour with the Maintenance Director, the hood was observed to be not grease tight due to missing fire-resistant caulk, and the Maintenance Director acknowledged this condition at the time of the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Kitchen Hood Inspections and Gas Appliance Restraints
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility failed to maintain the kitchen fire suppression system in accordance with NFPA standards, with only one documented kitchen hood inspection in the prior year and no additional inspection records available despite multiple requests. During the kitchen tour, surveyors also observed that gas-fired appliances lacked restraints to prevent overextension of gas lines when moved for cleaning or service, a finding confirmed by the Maintenance Director. This deficiency had the potential to affect 22 of the 69 residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Kitchen Hood Suppression System
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation of the required semi-annual inspection for the kitchen hood suppression system, as confirmed during a review and interview with facility leadership. This deficiency affected one of two inspection reports.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Kitchen Suppression System Inspections and Cleanings
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation for a semi-annual kitchen suppression system inspection and two semi-annual kitchen hood cleanings, as confirmed during interviews with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Commercial Cooking Equipment Not Properly Secured
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Three gas-fed appliances on casters under the commercial cooking hood were found with restraint tethers attached but not secured to the wall attachments, as confirmed by the DOM during inspection. This failure to properly limit appliance movement resulted in non-compliance with NFPA 101, NFPA 96, and NFPA 54 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Staff Unaware of Hood Fire Suppression System Operation
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Kitchen staff were unable to identify or operate the manual activation for the kitchen hood fire suppression system, and this deficiency was confirmed by the administrator during interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙