K0324 K324: Provide properly protected cooking facilities.
E

Failure to Maintain Kitchen Hood Inspections and Gas Appliance Restraints

Adams County ManorWest Union, Ohio Survey Completed on 03-25-2026

Summary

The deficiency involves the facility’s failure to maintain the kitchen fire suppression system and related equipment in accordance with NFPA 101, NFPA 96, NFPA 17A, NFPA 10, and NFPA 54 requirements. During record review, surveyors determined that only one kitchen hood inspection had been documented in the previous 12 months, with the sole inspection dated 04/23/25. Additional documentation of required inspections was requested multiple times during the survey, including at the entrance conference and later in the morning, but no further records were provided by the time of exit. During the physical tour of the facility’s kitchen, surveyors observed that the gas-fired kitchen appliances were not equipped with restraints to prevent overextension of the gas lines if the appliances were moved for service or cleaning. The Maintenance Director confirmed the absence of these restraints at the time of observation. This deficient practice had the potential to affect 22 of the 69 residents residing in the facility.

Plan Of Correction

1. Based on record review, observation and staff interview, no residents experienced negative outcomes related to failure to maintain kitchen fire suppression system and equipment safeguards. 2. The Medical Director was notified by LNHA on 03/26/2026 of the deficiency including incomplete hood inspection frequency and lack of appliance restraints. 3. Hood inspection will be completed by Grexen (contracted company) on or before 04/30/2026. Appliance restraints will be installed by Maintenance Director/designee on or before 04/30/2026. Hood inspections will be added to an every six (6) month automatically recurring schedule by Administrator/designee. 4. Compliance will be reviewed in QAPI every quarter and as needed. 5. LNHA educated Maintenance Director on 03/26/2026 regarding the requirements for maintaining the kitchen hood and kitchen equipment.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0324 citations
Commercial Cooking Hood Not Maintained Grease Tight per NFPA Standards
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility’s only commercial cooking hood was not maintained in accordance with NFPA 101 and NFPA 96 requirements. During a kitchen tour with the Maintenance Director, the hood was observed to be not grease tight due to missing fire-resistant caulk, and the Maintenance Director acknowledged this condition at the time of the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Kitchen Hood Suppression System
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation of the required semi-annual inspection for the kitchen hood suppression system, as confirmed during a review and interview with facility leadership. This deficiency affected one of two inspection reports.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Kitchen Suppression System Inspections and Cleanings
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation for a semi-annual kitchen suppression system inspection and two semi-annual kitchen hood cleanings, as confirmed during interviews with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Commercial Cooking Equipment Not Properly Secured
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Three gas-fed appliances on casters under the commercial cooking hood were found with restraint tethers attached but not secured to the wall attachments, as confirmed by the DOM during inspection. This failure to properly limit appliance movement resulted in non-compliance with NFPA 101, NFPA 96, and NFPA 54 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Staff Unaware of Hood Fire Suppression System Operation
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Kitchen staff were unable to identify or operate the manual activation for the kitchen hood fire suppression system, and this deficiency was confirmed by the administrator during interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missed Semi-Annual Kitchen Hood Cleaning
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not complete one of the two required semi-annual kitchen exhaust hood cleanings, as documentation showed only one cleaning was performed and staff confirmed the lack of records for the second cleaning. This affected one smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙