K0324 K324: Provide properly protected cooking facilities.
D

Deficiencies in Cooking Hood Maintenance and Fire Suppression Inspections

Alhambra Healthcare & Rehabilitation Center Saint Petersburg, Florida Survey Completed on 03-31-2025

Summary

The facility failed to maintain compliance with NFPA 101 and NFPA 96 standards regarding the maintenance of its commercial cooking hood and fire suppression system. During a record review, it was discovered that the facility did not provide evidence of one of the two required semi-annual inspections of the fire suppression system for the year 2024, with the only available inspection dated January 9, 2024. Additionally, the facility failed to conduct the 8-point monthly kitchen quick check inspection regularly, as the only record available was from March 2025. These lapses were acknowledged by the Maintenance Director and the Regional Maintenance Consultant during the review. Furthermore, during a facility tour, it was observed that the commercial cooking hood was not grease-tight, as the seams of the hood were not properly sealed. This deficiency was also acknowledged by the Maintenance Director and the Regional Maintenance Consultant. These findings were discussed with the Administrator, the Maintenance Director, and the Regional Maintenance Consultant during the exit conference, and photographic evidence was obtained to document the issues.

Plan Of Correction

1. Education was provided to the Maintenance Director on ensuring the two semi-annual inspections of the fire suppression system are completed, completing the monthly 8-point kitchen quick check by NHA on 4/1/2025. The commercial cooking hoods seams were resealed to be made grease tight on 04/01/2025 by the Maintenance Director. 2. No other areas or residents were affected by deficient practice. 3. Education was provided to the Maintenance Director by the NHA on 4/1/2025 on ensuring the two semi-annual inspections of the fire suppression system are completed, completing the 8-point monthly kitchen quick check and ensuring the commercial cooking hood seams are sealed and grease tight. The Maintenance Director will conduct quality assurance checks on the commercial cooking hood to ensure seams are sealed and grease tight weekly for 12 weeks. 4. All results of the quality assurance checks will be monitored and reviewed by the QA&A committee monthly until substantial compliance is assured.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0324 citations
Commercial Cooking Hood Not Maintained Grease Tight per NFPA Standards
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility’s only commercial cooking hood was not maintained in accordance with NFPA 101 and NFPA 96 requirements. During a kitchen tour with the Maintenance Director, the hood was observed to be not grease tight due to missing fire-resistant caulk, and the Maintenance Director acknowledged this condition at the time of the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Kitchen Hood Inspections and Gas Appliance Restraints
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility failed to maintain the kitchen fire suppression system in accordance with NFPA standards, with only one documented kitchen hood inspection in the prior year and no additional inspection records available despite multiple requests. During the kitchen tour, surveyors also observed that gas-fired appliances lacked restraints to prevent overextension of gas lines when moved for cleaning or service, a finding confirmed by the Maintenance Director. This deficiency had the potential to affect 22 of the 69 residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Kitchen Hood Suppression System
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation of the required semi-annual inspection for the kitchen hood suppression system, as confirmed during a review and interview with facility leadership. This deficiency affected one of two inspection reports.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Kitchen Suppression System Inspections and Cleanings
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation for a semi-annual kitchen suppression system inspection and two semi-annual kitchen hood cleanings, as confirmed during interviews with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Commercial Cooking Equipment Not Properly Secured
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Three gas-fed appliances on casters under the commercial cooking hood were found with restraint tethers attached but not secured to the wall attachments, as confirmed by the DOM during inspection. This failure to properly limit appliance movement resulted in non-compliance with NFPA 101, NFPA 96, and NFPA 54 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Staff Unaware of Hood Fire Suppression System Operation
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Kitchen staff were unable to identify or operate the manual activation for the kitchen hood fire suppression system, and this deficiency was confirmed by the administrator during interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙