K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Deficiencies in Fire Sprinkler System Maintenance

Palm Garden Of Vero BeachVero Beach, Florida Survey Completed on 04-30-2025

Summary

The facility failed to maintain its Automatic Fire Sprinkler System (AFSS) in accordance with NFPA 101 standards. During an inspection on April 30, 2025, it was discovered that the annual AFSS inspection conducted on February 17, 2025, identified deficiencies, specifically that the water flow was not reporting to the fire panel. No documentation was provided to show that this deficiency had been repaired. This issue was acknowledged by the Director of Plant Operations during the review. Further observations during the fire safety tour revealed multiple issues with the sprinkler system. At the Reflections Nurses Station, a white wire was found laying on top of the AFSS piping. In the Reflections Television Cable Room, a fire sprinkler head was loaded with paint on the deflector. The Kitchen had two out of three loaded dry sprinkler heads in the walk-in coolers, and the Beauty Supply Room had one of two loaded fire sprinkler heads. Additionally, the Phone Room in the Laundry corridor had a sprinkler surrounded by a ceiling with open seams, exposing the interstitial space above. Additional deficiencies included a red tag in the Fire Riser Room indicating the water flow issue, an illegible hydraulic design calculation sign, and a missing spare concealed sprinkler wrench. Insulation was found on top of the sprinkler piping near Room 206 in the Seaway Wing. The Physical Therapy Riser Room's spare sprinkler head box lacked a list of spare fire sprinkler heads, and the Independent Wing Riser Room had an illegible hydraulic design sign. These findings were acknowledged by the Director of Plant Operations and explained to the Administrator during the exit conference.

Plan Of Correction

No residents were affected by this alleged deficient practice as of 05/16/2025 and none can be identified as of 05/16/2025. The maintenance director and assistants were educated by the Executive Director on 05/16/2025 on K353. 1. Above the ceiling of the Reflections Nurses Station, the wire was removed on 05/16/2025 by the maintenance director/designee. 2. Dynafire was notified to replace the Reflections Television Cable Room had 1 of 1 loaded fire sprinkler heads on 05/16/2025 by the maintenance director/designee. 3. Kitchen 2 of 3 loaded dry sprinkler heads in the walk-in coolers were cleaned on 05/15/2025 by the maintenance director/designee. 4. Dynafire was notified to replace the Beauty Supply Room loaded sprinkler head on 05/16/2025 by the maintenance director/designee. 5. The Phone Room, in the Laundry corridor will have the ceiling repaired by 05/24/2025 by the maintenance director/designee. 6. The Fire Riser Room, in the Laundry corridor, was inspected by Dynafire before 05/24/2025 and the red tag was removed by Dynafire. The sprinkler wrench was ordered from Dynafire on 05/15/2025. The hydraulic sign will have a repair estimate by 05/24/25 to make the sign legible. 7. The Seaway Wing, near Room 206, had the insulation removed from on top of the sprinkler pipe by the maintenance director/designee. 8. The Physical Therapy Riser Room spare sprinkler head box had a list of all of the required items posted on the wall next to the box at the time of survey. The list is posted as it does not fit inside the box. 9. The Independent Wing Riser Room hydraulic sign was inspected by Dynafire, and the center has contacted the original manufacturer Brown, on 05/13/25. The original data is unable to be retrieved. Dynafire is unable to update the data as of 05/13/25. The center will have the repair estimates to replace the signage by 05/24/25 for the Independence and Laundry corridor signs. This was completed by the maintenance director/designee. Sprinkler heads, ceilings surrounding sprinkler heads, fire riser rooms, and sprinkler piping and hydraulic signs will be audited weekly x4 weeks and monthly x6 months for compliance with K353 by the maintenance director/designee. The results of these audits and any necessary repairs will be brought to QAPI for review. No residents were affected by this alleged deficient practice as of 05/16/2025 and none can be identified as of 05/16/2025. The maintenance director and assistants were educated by the Executive Director on 05/16/2025 on K353. 1. Above the ceiling of the Reflections Nurses Station, the wire was removed on 05/16/2025 by the maintenance director/designee. 2. Dynafire was notified to replace the Reflections Television Cable Room had 1 of 1 loaded fire sprinkler heads on 05/16/2025 by the maintenance director/designee. 3. Kitchen 2 of 3 loaded dry sprinkler heads in the walk-in coolers were cleaned on 05/15/2025 by the maintenance director/designee. 4. Dynafire was notified to replace the Beauty Supply Room loaded sprinkler head on 05/16/2025 by the maintenance director/designee. 5. The Phone Room, in the Laundry corridor will have the ceiling repaired by 05/24/2025 by the maintenance director/designee. 6. The Fire Riser Room, in the Laundry corridor, was inspected by Dynafire before 05/24/2025 and the red tag was removed by Dynafire. The sprinkler wrench was ordered from Dynafire on 05/15/2025. The hydraulic sign will have a repair estimate by 05/24/25 to make the sign legible. 7. The Seaway Wing, near Room 206, had the insulation removed from on top of the sprinkler pipe by the maintenance director/designee. 8. The Physical Therapy Riser Room spare sprinkler head box had a list of all of the required items posted on the wall next to the box at the time of survey. The list is posted as it does not fit inside the box. 9. The Independent Wing Riser Room hydraulic sign was inspected by Dynafire, and the center has contacted the original manufacturer Brown, on 05/13/25. The original data is unable to be retrieved. Dynafire is unable to update the data as of 05/13/25. The center will have the repair estimates to replace the signage by 05/24/25 for the Independence and Laundry corridor signs. This was completed by the maintenance director/designee. Sprinkler heads, ceilings surrounding sprinkler heads, fire riser rooms, and sprinkler piping and hydraulic signs will be audited weekly x4 weeks and monthly x6 months for compliance with K353 by the maintenance director/designee. The results of these audits and any necessary repairs will be brought to QAPI for review.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙