K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Deficiencies in Sprinkler System Maintenance and Documentation

River's Bend Health & Rehab CenterHarrisburg, Pennsylvania Survey Completed on 03-13-2025

Summary

The facility failed to maintain proper documentation and maintenance of its sprinkler system, as evidenced by the absence of 5-year sprinkler gauge replacement/calibration and internal pipe and valve inspection records. During a review of documentation, it was confirmed that the facility lacked these critical maintenance records. Additionally, the facility did not address the failure of the annual main drain test due to low water pressure, which was identified on August 28, 2024. This failure was confirmed during an interview with the Administrator and Maintenance Director. Further observations revealed physical obstructions and debris affecting the sprinkler system. Multiple items, such as wires and flex conduits, were found laying across the sprinkler pipes in various locations throughout the facility. Additionally, several sprinkler heads in the Laundry Room were covered with debris, which could impede their functionality. These issues were confirmed during an exit conference with the facility's Administrator and Maintenance Director.

Plan Of Correction

The 5-year sprinkler inspection report was located with last inspection performed on June 30, 2021. Results posted in Life Safety Book. The failed main drain test performed on August 28, 2024 due to low water pressure will be followed up to make necessary repairs as recommended by a qualified sprinkler company. The sprinkler company will be at the facility on April 1, 2025 to provide the facility with a remedy and work will be scheduled as soon as possible thereafter. Items laying across sprinkler pipes in the following areas have been removed from the sprinkler pipes: 1st floor, above ceiling by Resident Room D15 1st floor, above ceiling by Resident Room C1 2nd floor, above ceiling by Physical Therapy 2nd floor, above ceiling by Resident Room F18 The Maintenance Director will spot check other areas above the ceiling throughout the facility on a monthly basis to check for items laying on sprinkler pipes. After any vendor work above the ceiling, the Maintenance Director or NHA will inspect the area before the vendor leaves the facility. The sprinkler heads in the laundry area have been cleaned and will be inspected monthly by the NHA or designee. The Maintenance Director was re-educated on the need to maintain documentation so that it is easily retrievable; to follow up with repairs to any failed inspections and to not have anything laying across sprinkler pipes. The Maintenance Director or designee will audit inspection reports for timeliness and follow up repairs weekly for four weeks and then monthly for 3 months and report the results to the facility's QAPI committee. The NHA or designee will audit inspection reports on a quarterly basis to make sure recommended repairs are completed and that all inspection reports are timely and filed in the Life Safety Book.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙