K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
F

Failure to Conduct Timely Fire Door and Damper Inspections

Rehab & Healthcare Center Of Cape CoralCape Coral, Florida Survey Completed on 02-11-2025

Summary

The facility failed to conduct timely inspections and testing of fire doors and fire and smoke dampers as required by NFPA 80 standards. During a records review, it was found that the last maintenance and testing reports for fire and smoke dampers were dated over four years ago, on 3/5/20, which exceeds the maximum interval of four years for testing these devices. Additionally, the inspection report for fire doors was dated 7/4/22, indicating a lapse in the annual inspection requirement. The Director of Maintenance acknowledged the backlog in maintenance tasks, attributing it to the previous maintenance director. This deficiency in maintenance practices could lead to the failure of fire and smoke dampers during fire conditions, potentially allowing the spread of fire, smoke, and gases throughout the building's smoke compartments. This oversight affects all smoke compartments within the facility, posing a risk to the safety of its occupants. The individuals responsible for performing these inspections and tests are required to have the necessary knowledge, training, or experience, and written records of these activities must be maintained and available for review.

Plan Of Correction

K761 Maintenance Inspection & Testing - Doors 1. Fire doors and fire and smoke dampers were inspected and current. 2. All fire doors and dampers were audited and inspected. 3. A. Cintas has been retained, and inspection has been placed on their schedule to maintain compliance with regulatory guidelines. B. Maintenance director and maintenance staff educated on K761. 4. Maintenance director will audit to ensure facility remains in compliance and report findings to QAPI. K761 Maintenance Inspection & Testing - Doors 1. Fire doors and fire and smoke dampers were inspected and current. 2. All fire doors and dampers were audited and inspected. 3. A. Cintas has been retained, and inspection has been placed on their schedule to maintain compliance with regulatory guidelines. B. Maintenance director and maintenance staff educated on K761. 4. Maintenance director will audit to ensure facility remains in compliance and report findings to QAPI.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0761 citations
Failure to Maintain Self-Closing Fire Door Mechanism
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

A corridor door with a self-closing mechanism leading to the clean utility room by the nurse's station failed to close or self-latch when tested, as confirmed by the Facility Manager. This failure to maintain the fire door in accordance with NFPA 101 and NFPA 80 standards resulted in a deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Fire Door Inspections
C
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

Surveyors found that the facility did not provide documentation confirming that fire doors had been inspected within the required 12-month period. The Director of Maintenance confirmed that records of these inspections were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Annual Fire Door Inspections
F
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility did not perform a full annual inspection and testing of all rated swinging fire doors, as only the cross corridor fire doors were included while other rated doors, such as those for storage and utility rooms, were omitted. This was confirmed by the maintenance director during record review.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Inspect Fire-Rated Attic Access Doors
F
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility failed to inspect and maintain its fire-rated attic access doors according to NFPA 101 standards. During a fire safety tour, it was found that these doors were not included in the annual inspection, and the Plant Operations Technician was unsure of their inspection status. The Director of Plant Operations confirmed the oversight, acknowledging the findings during an exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Fire Door Inspections
C
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility failed to provide documentation of the annual fire-rated door inspection for six smoke compartments. This deficiency was identified during a document review, and the absence of documentation was confirmed during an interview with the Assistant Director of Nursing and the Maintenance Director. The lack of documentation indicates non-compliance with NFPA 80 requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Test Fire Doors Annually
D
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility did not maintain and test their fire doors as required by NFPA 101, with the last inspection recorded in December 2023. During a review, the Director of Continuum and Maintenance Supervisor acknowledged the absence of documentation for the annual inspection, indicating non-compliance with fire safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙