K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
C

Failure to Document Annual Fire Door Inspections

Preston ResidenceWest Grove, Pennsylvania Survey Completed on 06-25-2025

Summary

The facility failed to provide documentation verifying that fire doors had been inspected within the previous 12 months, as required by NFPA 101 and NFPA 80 standards. During an observation and document review, surveyors requested records of annual fire door inspections, but the facility was unable to produce documentation confirming that these inspections had occurred. An interview with the Director of Maintenance confirmed the absence of such documentation for the required period. No information regarding specific residents, their medical history, or their condition at the time of the deficiency was included in the report.

Plan Of Correction

The Fire Door inspection documentation was verified to exist and to have occurred in the last 12 months for the date of 11/12/24. The Fire Door inspections will be conducted annually. Annual inspections will be scheduled through the work order system and maintain NFPA compliance. A notification will be generated through this work order system (TELS). Inspections will be monitored through the work order system for completion and documentation reported to QAPI as completed. An audit of the Life Safety Book will be completed annually to ensure compliance. The completion date is 8/24/25.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0761 citations
Failure to Maintain Self-Closing Fire Door Mechanism
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

A corridor door with a self-closing mechanism leading to the clean utility room by the nurse's station failed to close or self-latch when tested, as confirmed by the Facility Manager. This failure to maintain the fire door in accordance with NFPA 101 and NFPA 80 standards resulted in a deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Annual Fire Door Inspections
F
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility did not perform a full annual inspection and testing of all rated swinging fire doors, as only the cross corridor fire doors were included while other rated doors, such as those for storage and utility rooms, were omitted. This was confirmed by the maintenance director during record review.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Inspect Fire-Rated Attic Access Doors
F
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility failed to inspect and maintain its fire-rated attic access doors according to NFPA 101 standards. During a fire safety tour, it was found that these doors were not included in the annual inspection, and the Plant Operations Technician was unsure of their inspection status. The Director of Plant Operations confirmed the oversight, acknowledging the findings during an exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Fire Door Inspections
C
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility failed to provide documentation of the annual fire-rated door inspection for six smoke compartments. This deficiency was identified during a document review, and the absence of documentation was confirmed during an interview with the Assistant Director of Nursing and the Maintenance Director. The lack of documentation indicates non-compliance with NFPA 80 requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Test Fire Doors Annually
D
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility did not maintain and test their fire doors as required by NFPA 101, with the last inspection recorded in December 2023. During a review, the Director of Continuum and Maintenance Supervisor acknowledged the absence of documentation for the annual inspection, indicating non-compliance with fire safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Door Labeling Deficiency
E
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility did not maintain fire doors according to NFPA standards, as fire-rated labels were covered with paint or illegible in the basement and on one resident floor. The Director of Maintenance acknowledged the issue during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙