K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
E

Non-compliance with NFPA 101 Egress Door Standards

Menorah HouseBoca Raton, Florida Survey Completed on 03-19-2025

Summary

The facility failed to maintain egress doors equipped with special locking arrangements in accordance with NFPA 101 standards. During a fire safety tour, it was observed that the Main Entrance double exit doors, which were equipped with a delayed egress special locking arrangement, were missing the required signage from both leaves. This lack of signage is a violation of the safety standards as it is essential for ensuring that individuals can identify and understand the function of the delayed egress system in an emergency. Additionally, the Dining Room Patio exit screen door was found to be locked at the latch and with a slide lock located 48 inches above the finished floor. This door had multiple locks engaged, and there was no documentation provided to indicate that the local authority had approved a clinical needs or security special locking arrangement for this setup. The presence of multiple locks without proper authorization or documentation is a breach of the regulations, which typically allow only one locking device unless specific conditions are met. Furthermore, the Rehabilitation double emergency exit doors, also equipped with a delayed egress special locking arrangement, were found to be locked with a hook deadbolt lock. This additional locking mechanism is not compliant with the standards for delayed egress systems, which are designed to allow for safe and timely evacuation. The Maintenance Director acknowledged these findings during the observations, and the issues were reviewed with both the Administrator and the Maintenance Director at the exit conference.

Plan Of Correction

K K222 NFPA 101 EGRESS DOORS 1. What corrective action(s) will be accomplished for those residents found to have been affected by the practice: 1) In the allegation of the Main Entrance double doors equipped with delayed egress special locking arrangements, not having the required signage on both doors. Maintenance has installed new signage on both of the front doors. 2) In the allegation of the Dining Room patio exit screen door having multiple locks on it. Maintenance has removed the extra lock and there is currently only one. 3) In the allegation of the Rehabilitation double emergency exit doors equipped with delayed egress special locking arrangements being locked with a hook deadbolt lock. Maintenance has disengaged the hook deadbolt lock. 2. How you will identify other residents having potential to be affected by the same practice and what corrective action will be taken: All residents in the facility have the potential to be affected by these practices. 3. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur: - Maintenance Director or designee will ensure that proper signage on the Main Entrance double doors is on those doors. - Maintenance Director or designee will ensure that there is only one lock on the Dining Room Patio exit door. - Maintenance Director or designee will ensure that hook deadbolt lock on the Rehabilitation double emergency exit doors is disengaged. 4. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put into place: The Director of Maintenance or a qualified Designee will monitor for substantial compliance. Findings of the audits will be reported at the Monthly QAPI meeting by the Director of Maintenance or a qualified Designee to ensure effectiveness and compliance of the plan of correction. Corrective action completion date: 4/19/25 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance. K222 EGRESS DOORS 1. What corrective action(s) will be accomplished for those residents found to have been affected by the practice: 1) In the allegation of the Main Entrance double doors equipped with delayed egress special locking arrangements, not having the required signage on both doors. Maintenance has installed new signage on both of the front doors. 2) In the allegation of the Dining Room patio exit screen door having multiple locks on it. Maintenance has removed the extra lock and there is currently only one. 3) In the allegation of the Rehabilitation double emergency exit doors equipped with delayed egress special locking arrangements being locked with a hook deadbolt lock. Maintenance has disengaged the hook deadbolt lock. 2. How you will identify other residents having potential to be affected by the same practice and what corrective action will be taken: All residents in the facility have the potential to be affected by these practices. 3. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur: - Maintenance Director or designee will ensure that proper signage on the Main Entrance double doors is on those doors. - Maintenance Director or designee will ensure that there is only one lock on the Dining Room Patio exit door. - Maintenance Director or designee will ensure that hook deadbolt lock on the Rehabilitation double emergency exit doors is disengaged. 4. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put into place: The Director of Maintenance or a qualified Designee will monitor for substantial compliance. Findings of the audits will be reported at the Monthly QAPI meeting by the Director of Maintenance or a qualified Designee to ensure effectiveness and compliance of the plan of correction.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0222 citations
Deficient Delayed Egress Door Signage and Function
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exit doors lacked the required signage with a contrasting background, and one door in the Service Hallway automatically reset when tested, both in violation of NFPA 101 standards. These deficiencies were observed during a fire safety tour and acknowledged by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Locking of Courtyard Exit Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors observed that a courtyard exit egress door was secured with a combination padlock, which did not meet NFPA 101 requirements. The issue was confirmed by facility leadership and had been previously identified earlier in the year.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Maintenance of Delayed Egress Doors
D
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exits were not properly maintained: one exit failed to operate when tested, and another required excessive force to open. These issues were confirmed by the Maintenance Director during the inspection and discussed with facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

A 15-second delayed egress door by a resident room was found without the required signage indicating the door could be opened after 15 seconds, as required by NFPA 101. This deficiency was confirmed by the Maintenance Director and could affect all occupants in the affected wing.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that a posted exit door from the solarium to the 600 wing was equipped with 15-second delayed egress hardware but lacked the required signage indicating, "PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS," as specified by NFPA 101. The Maintenance Director confirmed the absence of this signage during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Emergency Egress Door Required Multiple Actions to Unlock
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that an emergency egress door required more than one action to unlock due to a turn button lock, affecting 25 residents in one smoke compartment. The Maintenance Director confirmed the door had been in this condition for an extended period.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙