K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
E

Emergency Egress Door Required Multiple Actions to Unlock

Ceres Postacute CareCeres, California Survey Completed on 05-19-2025

Summary

During a facility tour and interview with the Maintenance Director, surveyors observed that an emergency egress door near Room 1 was equipped with a door knob featuring a turn button lock. When tested, the door required two separate actions to unlock from the egress side. This configuration does not comply with NFPA 101 Life Safety Code requirements, which mandate that egress doors must be readily openable from the egress side without the use of a tool, key, or more than one action. The Maintenance Director confirmed during the interview that the door had been in this condition for some time. This deficiency affected 25 out of 46 residents located in one of the facility's three smoke compartments. The report does not mention any specific medical history or conditions of the residents involved at the time of the deficiency.

Plan Of Correction

How corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice. The egress door near Room 1 was immediately repaired to eliminate the need for more than one action to open. A single-action, code-compliant push bar has been installed. How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken. All residents have the potential to be affected by this deficient practice. No residents were found to be affected by this deficient practice. What measures will be put into place or what systemic changes in the facility will make to ensure that the deficient practice does not recur: All door hardware was checked, and visual checks will be part of the preventive maintenance schedule to inspect egress hardware monthly. How the facility plans to monitor its performance to make sure that solutions are sustained. The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system. The log will be part of the facility QA program, and any deficient practices identified will have a QAPI developed to monitor and/or correct the deficient practice. Date of Completion of Corrective Action: 05/19/25 How the facility plans to monitor its performance to make sure that solutions are sustained. The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system. The log will be part of the facility QA program, and any deficient practices identified will have a QAPI developed to monitor and/or correct the deficient practice. Date of Completion of Corrective Action: 05/19/25 K 222

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0222 citations
Deficient Delayed Egress Door Signage and Function
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exit doors lacked the required signage with a contrasting background, and one door in the Service Hallway automatically reset when tested, both in violation of NFPA 101 standards. These deficiencies were observed during a fire safety tour and acknowledged by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Locking of Courtyard Exit Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors observed that a courtyard exit egress door was secured with a combination padlock, which did not meet NFPA 101 requirements. The issue was confirmed by facility leadership and had been previously identified earlier in the year.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Maintenance of Delayed Egress Doors
D
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exits were not properly maintained: one exit failed to operate when tested, and another required excessive force to open. These issues were confirmed by the Maintenance Director during the inspection and discussed with facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

A 15-second delayed egress door by a resident room was found without the required signage indicating the door could be opened after 15 seconds, as required by NFPA 101. This deficiency was confirmed by the Maintenance Director and could affect all occupants in the affected wing.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that a posted exit door from the solarium to the 600 wing was equipped with 15-second delayed egress hardware but lacked the required signage indicating, "PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS," as specified by NFPA 101. The Maintenance Director confirmed the absence of this signage during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Delayed Egress Door Locking System Not Maintained per NFPA Standards
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors observed that the delayed egress door locking system at the main entrance near nurse's station 1 did not enter an irreversible opening sequence when the panic bar was activated, as required by NFPA 101. This deficiency, confirmed by the Maintenance Director, could affect approximately 15 occupants in the event of a fire emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙