K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Facility Fails to Maintain Sprinkler System

Valley Manor Rehabilitation And Healthcare CenterCoopersburg, Pennsylvania Survey Completed on 03-12-2025

Summary

The facility failed to maintain its sprinkler system, affecting the entire facility. Documentation reviewed on March 12, 2025, revealed that only two quarterly external water tank inspections and two quarterly wet sprinkler inspections were recorded for the year 2024. During an exit interview, the Administrator, Director of Maintenance, and Assistant confirmed the absence of necessary report documentation. Additionally, the 4th quarter sprinkler inspection report from December 23, 2024, indicated several issues: a corroded sprinkler in the Dietary area needed replacement, a hydro test for the fire department connection was pending, and the fire pump room's temperature was below the required 40 degrees Fahrenheit, risking pipe damage due to potential freezing. Furthermore, the facility was advised to monitor and maintain the water level in the tank consistently. Observations made on March 12, 2025, revealed additional deficiencies. Two sprinkler heads in the basement laundry chute room were recessed into the ceiling, potentially hindering immediate water spread. Moreover, the fire alarm panel indicated a supervisory alert for low water in the water tower. These findings were confirmed during an exit interview with the facility's administration and maintenance team, highlighting the facility's failure to ensure proper maintenance and functionality of its sprinkler system.

Plan Of Correction

1. The Sprinkler system will be scheduled with Tustin for testing annually. Sprinkler heads will be adjusted. At the time of the survey, the fire pump was in test mode and was discharging water, and the facility ensures proper water is filled in the water tower. The facility will inspect the external water tank at least quarterly. 2. A. Facility will schedule replacement sprinkler with Tustin. B. Facility will contact the fire department to get hydro test scheduled. C. Report was from 2024. The temperatures were good during the site visit on 3/12/25. D. Facility currently monitors the water tank daily. E. Water was flowing during the site visit on 3/12/25. 3. Tustin will be scheduled to come in and turn sprinkler heads downwards. 4. The fire alarm panel is working properly and was completing a test which led to the low water notification. The facility has a working heater that maintains adequate temperature throughout.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙