K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Sprinkler System Maintenance Deficiencies

Westgate Hills Rehabilitation And Nursing CtrHavertown, Pennsylvania Survey Completed on 01-08-2025

Summary

The facility failed to maintain and inspect its sprinkler system as required, affecting the entire facility. During a document review on November 20, 2024, it was found that the fourth quarter sprinkler inspection revealed several deficiencies that had not been corrected. Specifically, the tampers in the backflow preventer pit were not reporting to the fire alarm panel, the FDC hydrotest was overdue, and the dry system main drain was improperly piped to a shower drain that could not handle the full flow from the drain. These issues were confirmed during an exit interview with the Administrator and the Maintenance Director. A follow-up onsite revisit conducted on January 8, 2025, confirmed that the same deficiencies remained unaddressed. The tampers in the backflow preventer pit still did not report to the fire alarm panel, the FDC hydrotest was still overdue, and the dry system main drain continued to be piped to a shower drain incapable of handling the full flow. These ongoing deficiencies were again confirmed during an exit interview with the Administrator and the Regional Maintenance Director.

Plan Of Correction

Plan of Correction for TAG K353: Sprinkler System Maintenance and Inspection 1. Deficiency: Based on document review and interview, it was determined the facility failed to maintain and inspect the sprinkler system, affecting the entire facility. Document review on November 20, 2024, at 8:00 a.m., revealed the following deficiencies noted during the fourth quarter sprinkler inspection, with no documentation of the correction of these issues: a. Tampers in the backflow preventer pit were not reporting to the fire alarm panel. b. FDC hydrotest is overdue. c. Dry system main drain is piped to a shower drain, which cannot handle the full flow from the drain (note: this was not considered a deficiency, but a note). Residents Affected: No residents were directly affected by these deficiencies. However, all residents have the potential to be affected if these issues with the sprinkler system are not addressed properly, as the sprinkler system is a key safety feature for the entire facility. 2. Corrective Action: a. The necessary repairs will be made to ensure that the tampers in the backflow preventer pit report to the fire alarm panel. This repair will be completed by 02/08/25. b. The FDC hydrotest was completed on 12/27/24. c. The issue with the dry system main drain was identified as a note by the inspector and is not considered a deficiency. An addendum to the original report will be obtained from the sprinkler inspection vendor indicating that the main drain item is not considered a "deficiency" and was identified as a note. This documentation will be available to review by the life safety inspector on the day of the revisit. 3. Monitoring: The Maintenance Director will ensure that the sprinkler system, including the backflow preventer and fire alarm panel connections, is fully functional and reporting correctly. A follow-up audit will be conducted on 02/08/25 to ensure all necessary corrections have been completed and that the sprinkler system is in full compliance. 4. Timeline: The repairs for the tampers in the backflow preventer pit will be completed by 02/08/25. The FDC hydrotest has been completed as of 12/27/24.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙