Citation history
Health deficiencies cited at Liberty Pointe Rehabilitation And Healthcare Ctr during CMS and state inspections, most recent first.
The facility failed to maintain the fire resistance rating of fire doors on the first floor due to the absence of a bottom latching device. This issue was initially observed and confirmed during an inspection in December and remained unresolved during a follow-up revisit in February.
The facility's building exceeds the maximum allowable story height for its Type V(III) protected wood frame construction, which is fully sprinklered. The building is three stories high, while the construction type permits only one story when sprinklered. This deficiency was confirmed during a document review and interview, and remains unresolved as of a follow-up visit.
The facility's dietary department was found to have several sanitation and food storage deficiencies. Observations included a large hole in the recycling area paneling, soiled convection ovens with grease and burnt debris, improper storage of a metal scoop in a flour bin, debris on the floor near the steamer and dry goods bins, a brown substance inside the ice machine, and cracked floor tiles near the utility hallway entrance.
The facility failed to maintain the fire resistance rating of fire doors, as observed when a fire door on the first floor lacked bottom latching. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director.
The facility failed to maintain clear means of egress as required by NFPA 101 standards. The headroom clearance of Exit Stairway Five was below the required minimum, and obstructions were found in exit pathways on two floors, including storage and trash on landings. These deficiencies were confirmed during an exit interview with the facility's administration.
The facility did not maintain and inspect portable fire extinguishers as required, specifically missing monthly inspections for the extinguisher on the first floor next to a resident room. This was confirmed during an exit interview with the Administrator and Maintenance Director.
The facility failed to ensure that corridor doors were properly latched, affecting fire safety and smoke containment. Observations revealed that doors on the first and second floors, including the Housekeeping Closet, Employee Storage Room, Nourishment Room, and Storage Room near resident room 106, failed to latch. These deficiencies were confirmed during an exit interview with the Administrator and Maintenance Director.
The facility did not maintain the smoke resistance of smoke barriers, as observed by an open penetration by a data wire in the smoke barrier on the third floor near a resident room. This was confirmed during an exit interview with the Administrator and Maintenance Director.
The facility did not maintain the smoke resistance of smoke barrier doors on the third floor, as holes were found in the door frame. This issue was confirmed during an exit interview with the Administrator and Maintenance Director.
The facility failed to maintain fire resistance in soiled linen and trash chutes, with doors on the third and second floors failing to close and latch. This was confirmed during an exit interview with the Administrator and Maintenance Director.
A resident with dementia and other health conditions did not have physician-ordered compression stockings applied as required. Observations over two days showed the resident without the Tubigrips, despite orders for daily application during morning care. Both an LPN and the DON confirmed the oversight.
Two residents experienced issues with the call bell system, as one resident's call bell did not activate the light outside her door, and another's produced no sound or light, requiring him to yell for help. Observations confirmed these deficiencies in the call bell system.
The facility was found to have a building classified as a three-story, Type V(III), protected wood frame construction, which is fully sprinklered. This classification exceeds the maximum allowable story height for this type of construction by one story, affecting the entire component of the facility.
A resident with dementia, difficulty walking, and osteoporosis experienced a fall, resulting in increased pain levels. Despite the facility's policy requiring notification of changes in clinical condition, the resident's physician was not informed of the increased pain following the fall.
A resident with dementia and osteoporosis was not properly assessed for pain medication effectiveness after a fall. Despite worsening pain, the resident was given acetaminophen without notifying the physician for additional pain management. The DON confirmed the lack of documentation on medication effectiveness.
The facility failed to monitor weight changes for two residents as per policy and physician orders. One resident with dementia and diabetes was not weighed weekly as required, and another with dementia and dysphagia lacked a documented weight schedule and weekly monitoring. The DON confirmed the absence of required documentation.
The facility failed to provide food that was palatable and at appetizing temperatures on three of five nursing units. Residents reported that the food was often cold and not palatable. A test tray audit confirmed that food temperatures were significantly below the required 130 degrees Fahrenheit, and further interviews indicated that this issue was consistent across both room service and dining room meals.
Fire Door Deficiency Due to Lack of Bottom Latching
Penalty
Summary
The facility failed to maintain the fire resistance rating of fire doors, specifically on the first floor, where the fire door did not have a bottom latching device. This deficiency was initially observed on December 12, 2024, during an inspection at 10:00 a.m. The absence of the bottom latching was confirmed during an exit interview with the Administrator and Maintenance Director at 10:30 a.m. on the same day. During a follow-up onsite revisit conducted on February 4, 2025, between 08:15 a.m. and 11:00 a.m., it was determined that the issue had not been resolved. The component separation fire door on the first floor still lacked a bottom latching device, as confirmed in an exit interview with the Administrator at 11:00 a.m.
Plan Of Correction
The first-floor fire door bottom latching has been repaired. Maintenance staff to be educated on the importance of maintaining fire resistance rating of fire doors. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee.
Building Construction Type and Height Deficiency
Penalty
Summary
The facility was found to be non-compliant with building construction requirements as per NFPA 101 standards. During a document review and interview on December 12, 2024, it was revealed that the building is classified as a three-story, Type V(III), protected wood frame construction, which is fully sprinklered. However, this construction type is only permitted to have a maximum of one story when sprinklered, indicating that the facility exceeds the allowable story height by two stories. An onsite revisit conducted on February 4, 2025, confirmed that the issue of exceeding the maximum story height allowance had not been resolved. The Administrator acknowledged the deficiency and is in the process of obtaining a Fire Safety Evaluation System (FSES) to address the non-compliance. The deficiency affects the entire component of the building, as the construction type and story height do not meet the required standards.
Plan Of Correction
I am requesting the Department of Health do the FSES in this case. Facility is consulting Lenhardt Rodgers Architecture to assist with this citation. Facility will also be requesting a TLW.
Sanitation and Food Storage Deficiencies in Dietary Department
Penalty
Summary
The facility failed to maintain sanitary conditions and proper food storage in the dietary department. During an environmental tour, a large hole was observed in the paneling on the back wall of the recycling area. The convection ovens were found to be soiled, with the insides of the oven doors coated with grease and the bottom of the top oven covered with burnt debris and food crumbs. A large metal scoop was improperly stored inside a bin containing flour. Debris was present on the floor near the steamer and dry goods bins. Additionally, a brown substance was noted on parts of the lid and the left inside wall of the ice machine. There were also five cracked floor tiles near the entrance of the utility hallway within the dietary department.
Plan Of Correction
1) The hole in the back wall of the recycling area has been repaired. Convection ovens were cleaned & grease to top & bottom ovens removed & area cleaned. Metal scoop was removed from the flour bin. Debris was removed from wall near the steamer. Ice machine was cleaned. Cracked floor tiles near the entrance of the kitchen was repaired. 2) All residents have the potential to be affected by the failure to maintain sanitary conditions & storing food properly in the dietary department. 3) Dietary staff to be educated on importance of maintaining sanitary conditions & proper food storing in the dietary department. 4) Audits will be completed weekly x4 & then monthly x2 or until compliance is met to ensure that sanitary conditions & proper food storing in the dietary department is maintained. Findings will be brought to the QAPI committee.
Fire Door Deficiency Due to Lack of Bottom Latching
Penalty
Summary
The facility failed to maintain the fire resistance rating of fire doors, which is a requirement for ensuring safety in multiple occupancies. During an observation on December 12, 2024, at 10:00 a.m., it was noted that a fire door on the first floor lacked bottom latching. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director at 10:30 a.m. on the same day.
Plan Of Correction
The first-floor fire door bottom latching was repaired. Maintenance staff to be educated on the importance of maintaining fire resistance rating of fire doors. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee.
Failure to Maintain Clear Means of Egress
Penalty
Summary
The facility failed to maintain the means of egress in compliance with NFPA 101 standards, as evidenced by two specific deficiencies. Firstly, during a document review, it was found that the headroom clearance of Exit Stairway Five leading to the attic was approximately 6'3", which is below the required minimum of 6'8". This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director. Secondly, observations revealed obstructions in the exit pathways on two different floors. On the second floor, storage was found on the lower landing of the exit stairwell by the RNAC Office. Additionally, trash was observed on the landing of the exit stairwell next to resident room 216, and storage was found on the lower landing of the exit stairwell near resident room 108 on the first floor. These obstructions were also confirmed during the exit interview with the facility's administration.
Plan Of Correction
I am requesting the Department of Health do the FSES in this case. Facility is consulting Lenhardt Rodgers Architecture to assist with this citation. The second-floor exit stairwell by the RNAC Office was cleaned from storage on the lower landing. Maintenance staff to be educated on the importance of maintaining means of egress. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee. Trash was cleaned from landing on the second-floor exit stairwell next to room 216. Storage was removed from the exit stairwell lower landing near room 108. Maintenance staff to be educated on the importance of maintaining means of egress. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee.
Failure to Inspect Portable Fire Extinguishers
Penalty
Summary
The facility failed to maintain and inspect portable fire extinguishers as required by NFPA 10, affecting one of three levels in the component. During an observation on December 12, 2024, at 9:52 a.m., it was noted that the portable fire extinguisher located on the first floor next to resident room 161 was missing its monthly inspections. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director on the same day at 10:30 a.m.
Plan Of Correction
Facility completed a monthly inspection for portable fire extinguisher next to resident room 161. Maintenance staff to be educated on how to maintain and inspect portable fire extinguishers. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee.
Failure to Ensure Proper Latching of Corridor Doors
Penalty
Summary
The facility failed to ensure that corridor doors were properly latched, which is a requirement for maintaining fire safety and smoke containment. During an observation on December 12, 2024, it was noted that the Housekeeping Closet door on the second floor was binding on the floor and failed to latch. Similarly, the Employee Storage Room door on the first floor also failed to latch. These deficiencies were confirmed during an exit interview with the Administrator and Maintenance Director. Additionally, further observations on the same day revealed that the Nourishment Room door on the second floor and the Storage Room door near resident room 106 on the first floor also failed to latch. These findings indicate a pattern of non-compliance with the requirement for corridor doors to have positive latching hardware, as mandated by the NFPA 101 and CMS regulations. The failure to ensure proper latching of these doors affects the facility's ability to resist the passage of smoke, which is critical for the safety of residents and staff.
Plan Of Correction
The latch & door were repaired for the second floor Housekeeping Closet across from resident room 252. The latch was repaired for the employee storage room door on the first floor. Maintenance staff to be educated on ensuring corridor doors are latched. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee. The second-floor nourishment door latch was repaired. The first-floor storage room door near resident room 106 latch was repaired. Maintenance staff to be educated on ensuring corridor doors are latched. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee.
Smoke Barrier Deficiency Due to Open Penetration
Penalty
Summary
The facility failed to maintain the smoke resistance of smoke barriers, which is a requirement for ensuring safety in the event of a fire. During an observation on December 12, 2024, at 9:08 a.m., it was noted that there was an open penetration by a data wire in the smoke barrier located on the third floor near resident room 304. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director later that morning at 10:30 a.m.
Plan Of Correction
Open penetration by data wire in the smoke barrier by resident room 304 was repaired using an UL approved stop gap penetration system. Maintenance staff to be educated on maintaining the smoke resistance of smoke barriers. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee.
Smoke Barrier Door Deficiency on Third Floor
Penalty
Summary
The facility failed to maintain the smoke resistance of smoke barrier doors on the third floor, as observed during a survey. Specifically, there were holes found in the door frame, which compromised the smoke resistance of the doors. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director.
Plan Of Correction
Holes in the door frame on the third floor were repaired. Maintenance to be educated on maintaining the smoke resistance of smoke barrier doors. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee.
Fire Resistance Deficiency in Linen and Trash Chutes
Penalty
Summary
The facility failed to maintain the fire resistance of soiled linen and trash chutes, affecting two of four levels in the component. During an observation on December 12, 2024, it was noted that the door to the soiled linen chute on the third floor would not close and latch. Additionally, the trash chute door on the second floor also failed to latch. These deficiencies were confirmed during an exit interview with the Administrator and Maintenance Director on the same day.
Plan Of Correction
Latch was repaired for the third-floor door to the Soiled Linen chute. Latch was repaired for the trash chute door. Maintenance to be educated on maintaining the fire resistance of Soiled Linen and trash chutes. Maintenance to monitor monthly or until compliance is met. Findings will be brought to the QAPI committee.
Failure to Implement Physician's Orders for Compression Stockings
Penalty
Summary
The facility failed to implement physician's orders for a resident diagnosed with dementia, hypertension, and chronic obstructive pulmonary disease. The resident, who was dependent on staff for dressing, was ordered by a physician on November 10, 2024, to have compression stockings (Tubigrips) applied to both legs for swelling. However, observations on December 10 and 11, 2024, revealed that the resident was seated in her wheelchair without the Tubigrips in place. A licensed practical nurse confirmed that the Tubigrips were supposed to be applied during morning care. The Director of Nursing also stated that the staff was to apply the Tubigrips daily as per the physician's order.
Plan Of Correction
1. Tubigrips were immediately placed on resident 2. 2. Current residents with Compression stockings were reviewed to assure residents had application per the physician orders. 3. Education will be completed for licensed nursing staff by staff educator/designee on Importance of ensuring residents have physician prescribed measures in place. 4. Audits will be completed by DON/designee to assure residents with Compression stockings have it in place per physician orders. Audits will be done weekly x4 & then monthly x2 or until compliance is met. Findings will be brought to the QAPI committee.
Deficiency in Call Bell System for Two Residents
Penalty
Summary
The facility failed to provide a working call bell system for two residents, leading to a deficiency in resident safety and communication. During a resident group meeting, one resident reported that activating the call bell from her bed did not trigger the light outside her door. Another resident stated that his call bell did not produce any sound or light, forcing him to yell for assistance. Observations confirmed these issues, as the call bell for the first resident did not activate the light, and the second resident's call bell produced neither sound nor light when tested.
Plan Of Correction
1) The call bell system was immediately repaired for residents 4 & 142. 2) Audit was completed to assure residents have a working call bell available. 3) Staff will be educated on the importance of ensuring residents have access to a working call bell. 4) Audits will be completed weekly x4 & then monthly x2 or until compliance is met by randomly auditing 10 resident rooms, to ensure residents have access to working call bells. Findings will be brought to the QAPI committee.
Building Construction Type Exceeds Allowable Height
Penalty
Summary
The facility failed to maintain the building construction requirements as per NFPA 101 standards. During a document review and interview conducted on December 12, 2024, it was found that the building is classified as a three-story, Type V(III), protected wood frame construction, which is fully sprinklered. However, this classification exceeds the maximum allowable story height for this type of construction by one story. This deficiency affects the entire component of the facility, as confirmed during the exit interview with the Administrator and Maintenance Director.
Plan Of Correction
I am requesting the Department of Health do the FSES in this case. Facility is consulting Lenhardt Rodgers Architecture to assist with this citation. Facility will also be requesting a TLW.
Failure to Notify Physician of Resident's Increased Pain Post-Fall
Penalty
Summary
The facility failed to notify a resident's physician of a change in clinical condition, specifically an increase in pain following a fall. The facility's policy, last reviewed on November 1, 2023, requires staff to notify the physician and resident representative of any change in clinical condition. A review of the clinical records for a resident with dementia, difficulty walking, and osteoporosis revealed that the resident experienced a fall on May 13, 2024, and was found on her left side. Initially, the resident's pain was rated as a 3, but by the following morning, it had increased to a 6, with specific pain noted in the left hip. Despite this significant change in the resident's condition, there was no documentation indicating that the resident's physician was notified of the increased pain level.
Failure to Evaluate Pain Medication Effectiveness
Penalty
Summary
The facility failed to evaluate the effectiveness of pain medication for a resident, which is inconsistent with professional standards. The resident, who had diagnoses including dementia, difficulty walking, and osteoporosis, had a physician's order for acetaminophen to be administered as needed for mild pain. After a fall, the resident was given acetaminophen for pain rated at a 3, but there was no documentation of an assessment to determine if the medication was effective. The following morning, the resident's pain worsened to a 6, and the nurse administered the same medication without notifying the physician for additional pain management orders. The Director of Nursing confirmed that the nursing staff should have documented the effectiveness of the pain medication.
Failure to Monitor Resident Weight Changes
Penalty
Summary
The facility failed to accurately monitor weight changes for two residents, CL1 and 3, as per the facility's weight monitoring policy and physician orders. Resident CL1, who was admitted with diagnoses including dementia, diabetes, and adult failure to thrive, had a care plan that required weekly weight monitoring for four weeks. However, there was no documented evidence that weights were obtained on March 19 or 26, 2024, as ordered by the physician. Similarly, Resident 3, admitted with dementia and dysphagia, had a care plan that included monitoring weights per facility policy. A nutrition assessment recommended weekly weights for four weeks, followed by monthly monitoring. Despite this, there was no documented evidence of a weight schedule being developed upon admission or that weekly weights were obtained as recommended. The Director of Nursing confirmed the lack of documentation for weights as per physician orders, dietitian recommendations, or facility policy.
Failure to Provide Palatable and Appetizing Food
Penalty
Summary
The facility failed to provide food that was palatable and at appetizing temperatures on three of five nursing units. A review of the facility policy revealed that food should be palatable, attractive, and served at a safe and appetizing temperature. However, interviews with residents indicated that the food was often cold and not palatable. A test tray audit showed that the temperatures of the chicken, stuffing, and Brussels sprouts were significantly below the required 130 degrees Fahrenheit. Further interviews with residents confirmed that the issue of cold food was consistent, affecting both room service and dining room meals.
What surveyors are citing around you — mapped
All 10 risk areas, ranked with evidence
Repeat citations, what's rising near you, and quality measures — ranked so department heads know exactly where to look first.
Illustrative
What surveyors actually found near you
We read the 1,041 citations issued within 25 miles in the last 12 months — including the 14 immediate-jeopardy cases — and tell you exactly what happened, in plain English, matched to your record.
Resident with a documented fall history left unattended on the patio; found on the ground with a hip fracture.
Walk-in cooler logs missing for 12 days; expired supplements in the medication room fridge.
Illustrative
A prioritized, do-first checklist
Every risk area becomes concrete audit steps drawn from real citations at facilities like yours — run them this week, before your window opens.
Illustrative
Risk indicators are statistical estimates from public CMS data — not predictions, findings, or compliance advice.
Nursing homes near Doylestown
How nearby facilities compare on the same public inspection record.
| Facility | Distance | Overall rating | Citations, 12 mo | Serious (J–L) |
|---|---|---|---|---|
| Harborview Rehabilitation Care Center At Doylestow | 0.2 mi | — | 6 | 0 |
| Wesley Enhanced Living - Doylestown | 0.5 mi | — | 13 | 0 |
| Heritage Pointe Rehabilitation And Healthcare Ctr | 0.9 mi | — | 5 | 0 |
| Pine Run Health Center | 2.5 mi | — | 11 | 0 |
| Neshaminy Manor Home | 3.4 mi | — | 8 | 0 |
Every risk area ranked, a do-first checklist, and your local survey patterns
Built specifically for Liberty Pointe Rehabilitation And Healthcare Ctr.
100% money-back within 48 hours.
Trusted data, never guesswork. Every citation, penalty, rating and Plan of Correction on this page is sourced from public CMS records (latest release August 2026) and official state health department websites.