F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
F

Excessive Hot Water Temperatures in Resident Bathroom Sinks

Arbor Grove VillageGreensburg, Indiana Survey Completed on 04-24-2026

Summary

The facility failed to provide a safe, clean, comfortable, and homelike environment related to resident hot water temperatures in resident bathroom sinks, affecting all 75 residents in the building. During multiple observations on the same morning, surveyors found that the hot water at several resident room sinks, including shared bathrooms, was immediately too hot to place hands under without discomfort or redness. Subsequent temperature checks conducted with the Maintenance Director showed hot water temperatures at the point of use as high as 132°F, 127°F, and 123°F when the hot water was first turned on, with later readings at the same sinks dropping into the 110–120°F range after the water had been allowed to run. These findings demonstrated that residents could initially be exposed to excessively hot water at their sinks. In interviews, the Maintenance Director stated he checked water temperatures once a week, allowing the water to run for two to three minutes until it reached a steady temperature, and that he understood the regulatory range to be 100–120°F. He reported that water temperatures fluctuated, that a new mixing valve had recently been installed, and that although the temperature at the mixing valve was appropriate, the water was hotter coming out of the lines and he did not know why. The Administrator reported that no residents had been burned and that she was not aware of residents being instructed to let the water run for a few minutes before placing their hands under it. She also noted that staff assisted residents on the dementia unit with handwashing, but those residents had individual bathrooms accessible to them, and there were no signs in bathrooms advising residents to wait before using the hot water. The facility’s Resident Rights policy stated that residents have the right to a safe, clean, comfortable, and homelike environment, including receiving treatment and supports for daily living safely.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0921 citations
Unsafe and unsanitary resident rooms with clutter, uncovered food, and rodent activity
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe and unsanitary resident rooms were observed with clutter, uncovered food, and rodent activity. A resident with schizophrenia and depression had food crumbs and meat under the bed, while another resident reported mouse droppings and hoarded food in a crowded room. Other rooms had overflowing bins, bags of belongings, and uncovered food, and staff reported that some residents refused housekeeping access and that pest control service in resident rooms was inconsistent.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Strong urine odor in Hallway B
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Strong urine odor in Hallway B. Surveyors repeatedly observed a noticeable urine smell at the beginning of and down Hallway B, including near the entrance where multiple residents were sitting in the hall. CNA 1 and CNA 2 both confirmed the odor, and the DON acknowledged the facility was aware of the strong smell at the entrance of Hallway B and cited the facility policy that residents have the right to a clean and comfortable environment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Homelike and Well-Maintained Resident Rooms
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Multiple rooms on one unit were found with environmental deficiencies, including broken and unsecured electrical outlets, damaged and stained walls and ceilings, improvised extensions on light cords using a plastic bag and a washcloth, dripping and constantly running sink faucets with discolored grout, and a strong urine odor in one room. A review of work orders and an interview with the Facilities Director showed that only two work orders had been submitted for this unit, both generated after surveyor observations, indicating that unit staff had not routinely initiated maintenance requests for these conditions.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Resident Rooms and Hallway Flooring in Safe, Homelike Condition
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

The facility did not maintain a safe, comfortable, and homelike environment, as evidenced by two residents with dementia and other comorbidities living in rooms with multiple wall holes, chipped drywall, missing paint, and water-stained ceilings, and by extensive uneven flooring in two main halls. Observations showed numerous divots, chipped areas around drainage covers, and partially filled floor defects near the nurses' station and along the East and South halls. A resident reported wheelchairs becoming stuck in these floor ruts, and maintenance staff confirmed both the room damage and the lack of flush flooring around drains, as well as the absence of a current repair plan.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Clogged Janitor Room Floor Drain and Black Water Overflow
F
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

A clogged floor drain sink in a janitor room led to black, dirty water accumulating in the drain and overflowing into a hallway. A housekeeper reported that the drain, used for disposing of mop water and cleaning chemicals, had been clogged for some time and that she had informed her supervisor. The housekeeping supervisor stated she had submitted several work orders and that housekeeping staff had been attempting to unclog the drain themselves for months, while the maintenance director reported having no active work orders for the issue and indicated that such black water can carry harmful microorganisms. The administrator stated he expects staff to submit work orders and report issues promptly.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Safe and Well-Repaired Ceilings and Plumbing
F
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

The facility did not maintain ceiling structures and plumbing in a safe and clean condition, resulting in long‑standing stained and bulging ceiling tiles above the nurses’ station and an actively leaking pipe in the ice machine/vending area. Surveyors observed missing ceiling tiles exposing insulation, wiring, and water pipes, standing water collected in a trash can, and soaked blankets and towels on the floor. An RN and an LPN reported that the ceiling tiles above the nurses’ station had been stained for months or longer, and that the ceiling had been leaking in the ice machine area for several days, where the ice machine is used for all residents. The Regional Maintenance Director confirmed the stained tiles and the leaking pipe and acknowledged that the tiles had not yet been replaced.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Indiana

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Indiana — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.