Generator Lacks Required Vehicle Impact Protection
Summary
A deficiency was identified when surveyors observed that the building’s generator, located between the building and the parking lot, lacked any protective barrier from vehicle traffic. During a revisit survey, it was again noted that no guard posts or other approved protective means had been installed around the generator despite its placement in an area subject to vehicular damage. Maintenance personnel acknowledged at the time of observation that the generator remained unprotected. This condition was cited as noncompliant with NFPA 1 (2021) sections 60.5.1.9 and 60.5.1.10, which require guard posts or other approved means to protect equipment such as storage tanks, connected piping, valves, fittings, and use areas where they are subject to vehicular impact. No residents or specific patient conditions were mentioned in the report, and the deficiency focused solely on the physical environment and life safety code requirements related to the generator’s location and lack of required protective barriers.