F0695 F695: Provide safe and appropriate respiratory care for a resident when needed.
K

Failure to Verify Oxygen Purity After Medical Gas Line Repair

Providence Holy Cross Med Ctr D/p SnfMission Hills, California Survey Completed on 12-11-2025

Summary

The facility failed to ensure that all 24 residents who were dependent on mechanical ventilators received oxygen that was verified to be free of contaminants after a repair to the medical gas line system. On the date of the incident, an oxygen alarm was triggered in the Subacute Unit, which led to the discovery of a broken oxygen line. The facility's census at the time included 24 residents in the Subacute Unit who were reliant on mechanical ventilation for respiratory support. Following the repair of the oxygen line by a contracted service, the facility returned the oxygen gas line to service without conducting required quality testing or verification by a certified medical gas verifier. Interviews with facility staff, including the Facilities Director and the Regional Compliance Officer, confirmed that no certified medical gas verifier was called to inspect, test, or verify the oxygen gas line after the repair. The Facilities Director, who is not certified as a medical gas verifier, made the decision to return the system to service based on his own judgment and background in electrical and biomedical engineering. The last documented oxygen gas quality testing had been performed over a month prior, and annual testing was the facility's standard practice. No documentation was available to confirm the safety, purity, or integrity of the medical gas system following the repair. The residents affected by this deficiency had significant medical histories, including chronic respiratory failure, traumatic brain injury, stroke, anoxic brain injury, and other conditions requiring continuous mechanical ventilation. Many had tracheostomies and feeding tubes, and were entirely dependent on the facility's oxygen supply for survival. Despite the critical nature of their conditions, the facility did not follow required protocols for post-repair verification of the medical gas system, as outlined in NFPA 99, which mandates thorough leak testing, purging, and functional testing by a certified third-party verifier after any repair or modification to a medical gas piping system.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0695 citations
Unsecured Storage of Full Oxygen Cylinders on Nursing Unit
D
F0695 F695: Provide safe and appropriate respiratory care for a resident when needed.
Short Summary

Surveyors observed four full O2 cylinders on one nursing unit stored unsecured directly on the floor under a sign labeled "FULL CYLINDERS" instead of in a secured storage rack. The ADON confirmed the cylinders were full and should not be on the ground. Reference to NFPA 99 showed that freestanding cylinders must be protected from damage and properly chained or supported in a stand or cart. The DON and Maintenance Director both acknowledged that O2 cylinders are required to be stored in a secure rack, should never be on the floor, and that unsecured cylinders on the floor present a safety risk.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Handling and Storage of Oxygen Nasal Cannula
D
F0695 F695: Provide safe and appropriate respiratory care for a resident when needed.
Short Summary

A resident with severe cognitive impairment and COPD, receiving oxygen therapy via nasal cannula, was observed twice with the cannula lying on the floor beside the bed instead of stored in the bag on the oxygen concentrator as required. A CNA later picked up the cannula from the floor, wiped it with a non-disinfectant incontinent wipe, and reapplied it to the resident, despite having been trained that a cannula found on the floor should be replaced. An LVN, the DON, and the Administrator all confirmed that oxygen cannulas must be stored properly, replaced if found on the floor, and that incontinent wipes are not disinfectants, indicating a failure to follow the facility’s infection prevention and control policy.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage of Nebulizer Mask and Respiratory Supplies
D
F0695 F695: Provide safe and appropriate respiratory care for a resident when needed.
Short Summary

A resident with COPD and dementia, receiving scheduled nebulizer treatments, was found on multiple occasions to have a nebulizer mask stored on top of the machine rather than in a sanitary manner. A CNA and a nurse aide in training confirmed the mask’s placement, and an LPN reported that masks were routinely cleaned, dried, and then stored on top of the machine. The DON later acknowledged that masks should be washed, dried, and placed on a clean surface, and facility policy required oxygen and respiratory supplies to be stored in a plastic bag when not in use.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Oxygen Administered Without Required Physician Order
D
F0695 F695: Provide safe and appropriate respiratory care for a resident when needed.
Short Summary

A resident with acute respiratory failure with hypoxia, pulmonary hypertension, and type 2 diabetes was observed receiving oxygen at 4.5 L/min via nasal cannula without a corresponding physician order in the clinical record. The DON acknowledged that an order should have been in place before oxygen was initiated. Facility policy on supplemental oxygen via nasal cannula requires administration only under a physician or provider order, in alignment with 410 IAC 16.2-3.1-47(a)(6).

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Current Physician Order for Oxygen
D
F0695 F695: Provide safe and appropriate respiratory care for a resident when needed.
Short Summary

A resident was observed receiving O2 via nasal cannula on multiple occasions, but the chart had no current physician order for O2. The resident said she had been told after a recent hospitalization to use O2 for 30 days, but that time had passed and she was still using it because staff told her she needed it. The DON confirmed there was no current O2 order; the last order had already been discontinued.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Provide and Document Respiratory Care
E
F0695 F695: Provide safe and appropriate respiratory care for a resident when needed.
Short Summary

Failure to provide and document respiratory care: A resident with a trach had no documented evidence of respiratory rate, depth, and quality being monitored each shift and as needed, despite oxygen orders and trach care needs. Other residents with CPAP, nebulizer, and oxygen therapy had respiratory equipment left out of required storage, missing CPAP settings and care details in orders and care plans, and MAR entries signed by nursing staff even when respiratory staff reportedly completed the equipment changes.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across California

Get a heads-up on the newest immediate-jeopardy (J–L) citations in California — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.