F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
D

Failure to Maintain Proper Ventilation in Smoke Room

Bernard Care CenterSaint Louis, Missouri Survey Completed on 12-19-2025

Summary

The facility failed to maintain an appropriate exhaust system to remove cigarette smoke from the indoor smoke room, resulting in smoke and odor permeating areas frequented by residents and staff. Multiple observations over several days showed that residents and staff entered and exited the smoke room, with several residents smoking inside. The odor of smoke was detected from the lobby entrance, throughout the hallway, and inside and outside the 300 Hall dining room. On one occasion, a visible haze of smoke was observed outside the smoke room. Two floor fans and two garage fans intended to ventilate the area were not turned on during these observations. Interviews with residents, staff, and facility leadership confirmed the presence of smoke odor and visible smoke in the hallways and dining areas. One resident reported smelling smoke in their room when the door was open, and a housekeeper and CNA both noted strong smoke odors and visible smoke outside the smoke room. The Maintenance Director acknowledged that the fans should have been operating but were either turned off by residents or not functioning due to a power issue. The Administrator confirmed that the exhaust fans were broken and that the smoke odor was more pronounced during colder weather when more residents smoked indoors.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0923 citations
Failure to Maintain Functional Mechanical Ventilation in Soiled Utility Room and Resident Bathrooms
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Surveyors found that mechanical ventilation in a soiled utility room and in resident bathrooms on two halls was not functioning. A strong, pungent odor was present in the soiled utility room, and testing of the ceiling vents with tissue paper showed no suction. The maintenance supervisor confirmed the vents were non-functional and reported that a single unit controlled ventilation for the soiled utility room and both halls’ bathrooms, suggesting a possible belt issue. This failure had the potential to affect all residents on those halls.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Bathroom Ventilation Systems Not Operational
D
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom ventilation systems were not operational in several resident bathrooms, as the fans ran but did not draw a 1-ply square of toilet paper during observations. The Maintenance Director said the fans were only checked monthly by listening for operation, and the Maintenance Man was unaware the systems were not working. The Administrator confirmed the bathroom ventilation was not working and that there was no policy and procedures for the ventilation system.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Bathroom Ventilation Systems Not Functioning and Contaminated
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom vents in rooms 200, 201, 203, 205, 207, 209, 211, and 213 were not functioning and were found with whitish, brown debris. Observations showed the vents did not draw up a 1 ply sheet of toilet paper, and the ADM and Maintenance Director confirmed the vents were not working and had not been checked in a few months.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonfunctioning Bathroom Exhaust Vents in Resident Rooms
D
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Surveyors found that bathroom exhaust vents in two resident rooms were not functioning, as they did not pull air in, despite facility logs indicating that one of these rooms’ vents had previously been checked and recorded as working. Review of the exhaust fan inspection log showed that only a small number of rooms in each hall were checked monthly over several months, and during an on-site observation and interview, the MD confirmed that the vents in the identified rooms were not operating.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Operational Bathroom Ventilation Systems in Multiple Resident Rooms
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Surveyors found that bathroom ventilation systems were not functioning properly in 12 of 27 occupied resident rooms when vents in those bathrooms failed to draw a 1‑ply piece of toilet paper to the vent surface during testing with the MD and Administrator. Facility records showed that monthly exhaust fan checks had been documented as completed, but the log did not identify which rooms were tested or how many rooms were actually checked, and the last recorded check lacked room-specific detail despite multiple rooms having inadequate ventilation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonfunctioning Bathroom Ventilation in Multiple Resident Rooms
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom ventilation was not operational in seven resident bathrooms, including rooms 120, 301, 303, 305, 308, 309, and 313. Surveyors observed the issue during two tours, and WM confirmed the vents should have been working. WM stated the HVAC vendor reported frozen coils due to cold temperatures, and the vents were not checked when temperatures dropped below freezing; the most recent vent log showed the last check was completed in October 2025.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙