K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
D

Stairway Exits Blocked by Caution Rope and Signage

Armstrong Rehabilitation And Nursing CenterKittanning, Pennsylvania Survey Completed on 12-19-2025

Summary

During an observation, it was found that stair tower doors on two of five building levels were blocked by a caution retractable rope with signage stating, "STOP!! DO NOT USE STAIRS ONLY FOR EMERGENCY." This setup prevented residents from using the stairways as exits except in emergencies, which could impede their ability to exit promptly. The maintenance director confirmed the presence of the rope and signage at the time of the survey. No additional information about specific residents, their medical history, or their condition at the time of the deficiency was provided in the report.

Plan Of Correction

The systematic change will be to have the retractable rope become a breakaway rope so not to impede progress through the stair tower door. The Director of Maintenance will audit all stairwell doors to assure there a retractable rope in place and report findings to Monthly Quality Assurance meeting.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0225 citations
Improper Storage of Chairs in Exit Stair Towers
E
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

Surveyors observed that stair towers used as exits were not properly maintained, as multiple stair landings were being used for storage. Chairs were found stored on landings in several stairwells on one floor, and the Maintenance Director confirmed that these items were being kept within the stair towers.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Stairtower Door Failed to Latch Due to Improper Hardware
E
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

A stairtower door near the South Nurses' Station was found not to latch properly because of incorrectly mounted magnet hardware. This deficiency was confirmed by the DON and Director of Maintenance during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistive Rating of Exit Stair Enclosures
F
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

Surveyors found that all rated doors inside a stairwell enclosure between Personal Care and Skilled Nursing failed to positively latch, and a hollow wooden door of unknown fire rating was sealed within a fire-rated wall. These issues were confirmed by facility staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Stairtower Door Gap Deficiency
E
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

The facility did not maintain stairtower doors within the allowed gap margins on two floors. Observations revealed that the doors on the 1st and 2nd floors of Stairtower A had gaps exceeding 1/8 inch, confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inoperative Stairway Path Interrupter on 2nd Floor Egress
E
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

An observation revealed that the electronic stairway path interrupter on the 2nd floor egress by the elevators was not functioning, which could cause individuals to miss the correct exit during an emergency. This issue was confirmed with the Maintenance Director and could affect a significant number of residents during a fire.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance of Stairtower Enclosures
E
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

The facility failed to maintain the fire resistance of stairtower enclosures, affecting two smoke compartments. Observations revealed that stairtower doors in specific zones did not positively latch within their frames, as confirmed by the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙