F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
F

Failure to Maintain Consistent and Safe Hot Water Temperatures

Armour Oaks Senior Living CommunityKansas City, Missouri Survey Completed on 04-17-2025

Summary

The facility failed to ensure that hot water temperatures from faucets throughout the building were consistently maintained between 105°F and 120°F, as required by both facility policy and state regulations. Observations and measurements revealed that water temperatures in various resident rooms ranged from as low as 76.1°F to as high as 121.4°F. Some rooms on the southeast side had water temperatures between 94°F and 99°F, while rooms on the north side had temperatures exceeding the maximum limit, reaching up to 121.4°F. Other rooms had water temperatures below the minimum requirement, with several readings under 105°F. These inconsistencies were found after allowing the faucets to run for two minutes, as per regulatory guidance. Interviews with facility staff indicated a lack of awareness and understanding regarding the proper procedures for monitoring and measuring water temperatures. The Maintenance Assistant described the water delivery system, which includes a hot water heater, a holding tank, and a mixing valve, but could not explain the cause of the temperature fluctuations. The Maintenance Person admitted to not following the correct method for measuring water temperatures, typically allowing water to flow for only one minute instead of the required two minutes. Additionally, the Administrator was unaware of the extent of the temperature variations until an incident involving a resident in the shower was reported. Review of facility policies confirmed that staff are required to monitor water temperatures, report abnormal findings, and maintain documentation. However, the staff interviews and record reviews demonstrated that these procedures were not consistently followed. The facility had not previously contacted a plumber to address the inconsistent water temperatures, and leadership was only considering this action after the issue was identified. The failure to maintain appropriate water temperatures and to follow established monitoring protocols potentially affected all residents in the facility.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0921 citations
Unsafe and unsanitary resident rooms with clutter, uncovered food, and rodent activity
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe and unsanitary resident rooms were observed with clutter, uncovered food, and rodent activity. A resident with schizophrenia and depression had food crumbs and meat under the bed, while another resident reported mouse droppings and hoarded food in a crowded room. Other rooms had overflowing bins, bags of belongings, and uncovered food, and staff reported that some residents refused housekeeping access and that pest control service in resident rooms was inconsistent.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Strong urine odor in Hallway B
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Strong urine odor in Hallway B. Surveyors repeatedly observed a noticeable urine smell at the beginning of and down Hallway B, including near the entrance where multiple residents were sitting in the hall. CNA 1 and CNA 2 both confirmed the odor, and the DON acknowledged the facility was aware of the strong smell at the entrance of Hallway B and cited the facility policy that residents have the right to a clean and comfortable environment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Homelike and Well-Maintained Resident Rooms
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Multiple rooms on one unit were found with environmental deficiencies, including broken and unsecured electrical outlets, damaged and stained walls and ceilings, improvised extensions on light cords using a plastic bag and a washcloth, dripping and constantly running sink faucets with discolored grout, and a strong urine odor in one room. A review of work orders and an interview with the Facilities Director showed that only two work orders had been submitted for this unit, both generated after surveyor observations, indicating that unit staff had not routinely initiated maintenance requests for these conditions.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Resident Rooms and Hallway Flooring in Safe, Homelike Condition
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

The facility did not maintain a safe, comfortable, and homelike environment, as evidenced by two residents with dementia and other comorbidities living in rooms with multiple wall holes, chipped drywall, missing paint, and water-stained ceilings, and by extensive uneven flooring in two main halls. Observations showed numerous divots, chipped areas around drainage covers, and partially filled floor defects near the nurses' station and along the East and South halls. A resident reported wheelchairs becoming stuck in these floor ruts, and maintenance staff confirmed both the room damage and the lack of flush flooring around drains, as well as the absence of a current repair plan.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Clogged Janitor Room Floor Drain and Black Water Overflow
F
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

A clogged floor drain sink in a janitor room led to black, dirty water accumulating in the drain and overflowing into a hallway. A housekeeper reported that the drain, used for disposing of mop water and cleaning chemicals, had been clogged for some time and that she had informed her supervisor. The housekeeping supervisor stated she had submitted several work orders and that housekeeping staff had been attempting to unclog the drain themselves for months, while the maintenance director reported having no active work orders for the issue and indicated that such black water can carry harmful microorganisms. The administrator stated he expects staff to submit work orders and report issues promptly.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Safe and Well-Repaired Ceilings and Plumbing
F
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

The facility did not maintain ceiling structures and plumbing in a safe and clean condition, resulting in long‑standing stained and bulging ceiling tiles above the nurses’ station and an actively leaking pipe in the ice machine/vending area. Surveyors observed missing ceiling tiles exposing insulation, wiring, and water pipes, standing water collected in a trash can, and soaked blankets and towels on the floor. An RN and an LPN reported that the ceiling tiles above the nurses’ station had been stained for months or longer, and that the ceiling had been leaking in the ice machine area for several days, where the ice machine is used for all residents. The Regional Maintenance Director confirmed the stained tiles and the leaking pipe and acknowledged that the tiles had not yet been replaced.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Missouri

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Missouri — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.