K0912 K912: Have power receptacles that are properly grounded.
D

Deficiencies in Electrical Outlet Safety and Maintenance

Coastal Oaks Special Care CenterAtascadero, California Survey Completed on 06-11-2025

Summary

Surveyors identified several deficiencies related to electrical outlets during a facility tour, document review, and staff interviews. In the auxiliary space between two resident rooms, an electrical outlet located beneath a waterline and connected to a refrigerator was found to lack Ground Fault Interrupter (GFI) protection. The Environmental Consultant was unaware of this issue and stated it had not been noted in previous life safety surveys. Additionally, in a resident room, a damaged and bent electrical outlet faceplate was observed, which was not flush with the outlet. The Maintenance Consultant was also unaware of this damage. Further review of documentation revealed that GFI outlets were being tested only annually, despite the manufacturer's instructions on the outlet cover indicating that testing should occur monthly. The Maintenance Consultant confirmed that all outlets were tested annually and was not aware of the monthly testing requirement. These deficiencies affected three of five residents and one of two smoke compartments, as noted in the findings.

Plan Of Correction

The outlet in the Snack Shack was replaced with a GFI receptacle. The wall plate in the resident room was replaced that afternoon. (See attached photos.) The Director of Maintenance will audit the electrical receptacles throughout the building monthly and ongoing, to ensure that each receptacle is in proper working order. The Administrator will review the audits quarterly and bring findings to the Quality Assurance Team as part of the QAPI safety program evaluating the effectiveness. This corrective action was completed June 20th, 2025.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0912 citations
Failure to Maintain GFCI Protection for Electrical Receptacles
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

Surveyors identified that three electrical receptacles in the facility were not GFCI protected as required, including those near a sink in the café, a water fountain near the nurse station, and a juice machine in the kitchen. These deficiencies were confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of GFCI Protection on Kitchen Electrical Receptacle
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

A kitchen electrical receptacle near the hand sink was found without required GFCI protection during an observation, and this deficiency was confirmed by the administrator and maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-Compliance with GFI Protection Near Water Sources
E
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility was found non-compliant with GFI protection requirements for power receptacles within six feet of a water source in three smoke zones. Observations revealed non-GFI protected outlets in the D Hall Nurses' Station Nourishment Area, B Hall Beauty Shop, and Main Kitchen Prep Area. This was confirmed by the Assistant DON and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Receptacle Deficiency in Laundry Room
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility failed to maintain electrical receptacles in compliance with safety standards in one of over thirty rooms. An observation revealed that the A wing resident laundry room had a washing machine without GFCI protection. This deficiency was confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain GFI Protection Near Water Sources
D
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility did not ensure that power receptacles were GFI protected within six feet of a water source in one of the smoke zones. Observations revealed non-GFI protected outlets behind an ice machine near a resident room and in the Boiler/Generator Room. This was confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Electrical Receptacle Maintenance
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility did not maintain electrical receptacles according to NFPA 101 standards, lacking GFCI protection in the employee lounge water cooler and resident laundry washing machine. This was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙