K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
D

Non-Essential Equipment Connected to Life Safety Emergency Outlets

Bel Vista Healthcare CenterLong Beach, California Survey Completed on 05-19-2025

Summary

The facility failed to ensure that only permitted electrical equipment was connected to the Life Safety emergency system, as required by NFPA 99 and related codes. During an observation and interview, it was found that phone charging cords were plugged into the emergency red outlets located behind beds in room 19. The Maintenance Supervisor confirmed that these red outlets are connected to the life safety emergency system, which is intended only for specific, critical functions as outlined in the regulations. The report specifies that, in the event of a prolonged normal electrical failure, unessential equipment such as phone chargers should not be continuously connected to the emergency system. This is to prevent power overload and potential failure of the alternative power source. The deficiency was identified during a concurrent observation and interview, and the findings were acknowledged by the Maintenance Supervisor. A review of the facility's Maintenance Service Policy and Procedure indicated that the Maintenance Department is responsible for maintaining the building and equipment in compliance with all applicable laws and regulations. However, the observed practice of allowing non-essential equipment to be plugged into the life safety emergency outlets was not in compliance with these requirements.

Plan Of Correction

BEL VISTA HEALTHCARE CENTER makes every effort to operate in substantial compliance with Federal and State laws and regulations. Nothing in this Plan of Correction is an admission otherwise. BEL VISTA HEALTHCARE CENTER is submitting this Plan of Correction in compliance with its regulatory obligations and does not waive any objections it may have as to the merit or form of any allegations contained herein. Please note that the facility may contest the merits or form of any of the alleged deficient findings and may take reasonable steps to appeal them. This Plan of Correction constitutes BEL VISTA HEALTHCARE CENTER's written credible allegation of compliance for the deficiencies noted. It is the facility's policy to comply with all applicable federal and state regulations regarding NFPA 99 Health Care Facilities Code 2012 Edition, specifically section 6.4.2.2.3.5 concerning the proper use of Life Safety emergency system electrical outlets. Corrective Action Taken: On 05/20/2025, the Maintenance Director immediately removed all phone charging cords from the emergency red outlets in Room 19. The Maintenance Director conducted a facility-wide inspection of all emergency red outlets to ensure no unauthorized equipment was connected. Identification of Other Areas with Potential to be Affected: The Maintenance Director completed a comprehensive audit of all emergency power outlets throughout the facility on 05/20/2025 to identify any similar instances of improper use. This included inspection of all four smoke compartments and documentation of all emergency power circuits and their current usage. Systemic Changes and Measures Implemented: 1. Installed clear signage at all emergency outlets identifying proper usage restrictions. 2. Conducted in-service training for staff on 05/21/2025 regarding emergency power systems and proper outlet usage. 3. Added emergency outlet inspection to daily maintenance rounds checklist. Monitoring and Quality Assurance: The Maintenance Director will conduct daily rounds to ensure compliance with emergency outlet usage requirements. Results will be documented on a standardized audit tool. The Administrator will review audit results monthly. The Maintenance Director will report monitoring results to the quarterly Quality Assurance and Performance Improvement (QAPI) committee. The QAPI committee will monitor compliance until substantial compliance is achieved and maintained for three consecutive months. Additional education and monitoring will be implemented as needed based on audit findings. Date of Completion: 06/12/2025

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0918 citations
Failure to Perform and Document Annual Main and Feeder Breaker Testing
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to perform and/or document required annual testing and exercising of main and feeder circuit breakers in accordance with NFPA 99 and manufacturer recommendations. During record review, no documentation could be produced to show that the annual breaker exercises had been completed, and the Director of Facilities acknowledged this lack of records. This deficiency relates to the essential electrical system that supports life safety and critical branches during emergencies.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Exercise and Document Main and Feeder Breaker Maintenance per NFPA 99
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility did not have documentation showing that the essential electrical system’s main and feeder circuit breakers were exercised annually in accordance with manufacturer recommendations and NFPA 99 requirements. During record review with the Maintenance Director, no records could be produced to verify that these breakers had been properly exercised, and the Maintenance Director acknowledged this failure. This deficiency was cited as affecting all occupants due to noncompliance with required essential electrical system maintenance and testing standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Required Generator Battery Testing
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to perform and document required testing of backup generator batteries in accordance with NFPA 110. During record review, no documentation of generator battery testing was available, and the Maintenance Director acknowledged both the lack of records and a lack of knowledge of the NFPA 110 battery testing requirements. The report notes that this failure could result in loss of power affecting life support and life safety features for occupants.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Generator Battery Testing Documentation
D
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors identified a deficiency when the facility could not provide documentation that backup generator batteries were being tested in accordance with NFPA 110 and NFPA 99 requirements. During record review, no records of generator battery testing were available, and the Maintenance Director confirmed he was unable to locate the requested documentation. This failure concerns the essential electrical system that supports life safety and critical functions during power loss.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform Required Generator Battery Conductance Testing for Essential Electrical System
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to maintain its Essential Electrical System (EES) in accordance with NFPA 99 and related standards when record review showed that conductance testing was not performed for 2 of 2 sealed generator batteries over a defined period, and only one generator battery was tested during that time. During an interview, the Maintenance Director acknowledged that required testing had not been completed for both batteries. This lapse in required emergency power system maintenance affected the facility’s single EES and all residents and staff relying on it.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Required Generator Testing and Safety Features
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to maintain required documentation showing that its three generators were tested monthly and inspected and tested annually in accordance with NFPA 99 and NFPA 110. Despite multiple requests, no records of these tests or inspections were provided. During the facility tour, surveyors also observed that none of the three generators were equipped with remote manual stop buttons, and this was confirmed by the Maintenance Director. This deficient practice had the potential to affect all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙