K0923 K923: Have proper medical gas storage and administration areas.
E

Improper Segregation of Oxygen Cylinders Due to Undefined Signage

Urbana Health & Rehabilitation CenterUrbana, Ohio Survey Completed on 06-05-2025

Summary

During a facility tour, surveyors observed that the oxygen storage area near room A-13 contained two signs labeled "full" and "partial/empty" for cylinder segregation. However, the facility had not defined what constituted a "partial" cylinder, which created the potential for cylinders that were nearly full to be placed in the empty section. This lack of clear definition and segregation did not meet the requirements outlined in NFPA 99-2012 Edition, Section 11.6.5.2, which mandates that empty and full cylinders must be segregated if stored within the same enclosure. An interview with a medical staff member confirmed the finding, as the staff member was unaware of the specific requirements and found the signage confusing. The deficiency was identified as having the potential to affect eight out of 46 residents, but no specific details about the residents' medical history or conditions at the time of the deficiency were provided in the report.

Plan Of Correction

K923 Urbana Health and Rehab wishes to point out to any person who reviews this document that we do not necessarily agree with the citations with which we were cited. However, the law requires us to prepare a plan of correction for the citations regardless of whether we agree with them or not. Thus, we have prepared such a plan as noted below. Please note though, that this plan does not constitute an admission that the citations are either legally or factually correct. This plan of correction is not meant to establish any standard of care, contract, obligation, or position, and Urbana Health and Rehab reserves all rights to raise all possible contentions and defenses in any civil or criminal action or proceeding. Please accept 7/30/25 as the facility's allegation of compliance date. The facility failed to maintain oxygen storage signage near room A 13; empty oxygen bottles were labeled "partial/empty." Step 1: Maintenance Director corrected the signage on 6-6-25 with a sign that reads "Empty." Step 2: All residents that utilize oxygen were assessed for proper storage and placement of oxygen tanks by 7/15/25. Step 3: LNHA educated all clinical staff on appropriate signage for Oxygen room 7/15/25. New hires are educated upon orientation. Step 4: LNHA/designee to monitor for continued compliance will audit oxygen room signage weekly x4 then monthly x2. Results of the audits will be forwarded to the QAPI committee for further review and recommendations.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0923 citations
Failure to Maintain Required Oxygen Cylinder Storage and Secured Storage Room
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen storage requirements were not maintained when a freestanding oxygen cylinder was observed unsecured in a third-floor room and the C-Hall oxygen storage room door failed to close and latch due to a coordinator malfunction. The Maintenance Director confirmed these oxygen storage deficiencies during the survey exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage of Oxygen Cylinders Near Combustibles
F
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors observed that more than 12 "E" oxygen cylinders (18 total) were stored in a sprinkler room within five feet of combustible materials, contrary to NFPA 99 requirements for gas equipment cylinder storage. The Maintenance Director confirmed this storage practice during the survey. This noncompliance with NFPA 99 sections 11.3.1–11.3.3 was cited as a deficiency affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Room Cautionary Signage
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that an oxygen storage room on the second floor lacked the required precautionary signage stating, "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING," as mandated for gas cylinder storage areas. This deficiency was confirmed by facility leadership during the initial survey and again during a subsequent revisit, when the same room was still missing the required sign.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Oxygen Cylinder Storage Near Combustibles and Electrical Receptacles
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders stored within first- and second-floor nurses' stations were placed less than five feet from electrical receptacles and combustible materials, in violation of NFPA 99/101 requirements for separation of oxidizing gases from combustibles and ignition sources. The Administrator and Maintenance Director confirmed during interview that the cylinders were improperly stored in proximity to these combustible and ignition sources.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Post Required Oxygen Storage Signage in Crash Cart Rooms
E
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that oxygen cylinders were stored in crash cart rooms in two separate cores without the required precautionary signage on the doors indicating oxidizing gas storage and no smoking. Observations in two smoke compartments showed oxygen cylinders present in the 3 East and 2 East core crash cart rooms, yet the doors lacked the mandated "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING" signage. The facility administrator and maintenance leadership confirmed that the proper oxygen storage signs were not posted on these doors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage and Security of Gas Cylinders
D
K0923 K923: Have proper medical gas storage and administration areas.
Short Summary

Surveyors found that gas cylinders were improperly stored and unsecured, with 38 cylinders in an outside storage room lacking the required oxidizing gas signage and with full and empty cylinders comingled, and an additional 25 cylinders stored adjacent to this area without any means to prevent unauthorized access. During an interview, the Maintenance Director acknowledged the issues and reported being unaware of the specific NFPA 99 storage requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙