K0919 K919: Meet requirements for the use of electrical equipment.
D

Electrical Panel Circuits Missing Required Identification

California Home For The AgedFresno, California Survey Completed on 03-26-2025

Summary

Surveyors observed that the facility failed to maintain proper identification of electrical circuits in two separate electrical panels located in mechanical rooms. Specifically, Panel A was found to have two out of forty-two circuits (circuits 13 and 27) missing identifiers, and Panel F had three out of forty-two circuits (circuits 26, 28, and 30) without labels. During interviews, staff indicated that the unlabeled circuits in Panel A were considered spares, while for Panel F, staff were unaware of the purpose of the unlabeled circuits. These deficiencies were identified during a facility tour and staff interviews, affecting 23 of 103 residents in one of five smoke compartments. The lack of proper labeling on the electrical panels was found to be non-compliant with NFPA 70 National Electrical Code requirements, which mandate that each circuit be clearly and legibly identified as to its specific purpose or use.

Plan Of Correction

How does the facility plan to monitor its performance to make sure that the corrections are implemented and achieved, that solutions are sustained, and that the corrective actions taken are evaluated for effectiveness through integration into the facility's Quality Assurance system? The Facilities Maintenance Director will review the monthly fire drill reports to ensure compliance with varying times and shift compliance. Any findings will be corrected within the month by way of a separate drill if required. The Facilities Maintenance Director will report compliance and findings of fire drills to the Quality Assurance Committee monthly for 12 months for integration and recommendations if indicated. K 919: How will the corrective action be accomplished for those residents found to have been affected by the deficient practice? No residents were found to be affected by the deficient practice in regard to the unlabeled circuits. The Maintenance Lead inspected and identified that circuits 13 and 27 in Panel A and confirmed them to be "spares". They were correctly labeled as "SPARE" on 03/27/2025. The maintenance lead inspected and identified that circuits 26, 28, and 30 on Panel F and confirmed them to be "spares". They were correctly labeled as "SPARE" on 03/27/2025. How will the facility identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken? No other residents were found to have been affected by the deficient practice and the corrective action taken above ensures that no residents will be affected. What measures will be put into place or what systemic changes will the facility make to ensure that the deficient practice does not recur? The Facilities Maintenance Director in-serviced all Maintenance Personnel in regard to the requirements of K919, specifically ensuring all circuit breakers are labeled. The Facility Maintenance Lead will inspect the electrical panels for proper circuit labeling monthly for three months. After this, the Facilities Maintenance Director added an annual "Inspect and Document the Main and Feeder Circuit Breakers" task to the TELS system to

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0919 citations
Obstructed Electrical Panel in Staff Development Room
E
K0919 K919: Meet requirements for the use of electrical equipment.
Short Summary

Surveyors found that an electrical panel labeled 'Fire Alarm Panel Inside' was obstructed by a desk, boxes, and a backpack in the Director of Staff Development Room, with items placed about one foot from the panel. The Maintenance Director confirmed the desk was recently added for new staff. This obstruction affected 36 residents in one smoke compartment and did not meet NFPA requirements for clear workspace around electrical equipment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Obstructed Electrical Panels in Storage Room
D
K0919 K919: Meet requirements for the use of electrical equipment.
Short Summary

The facility failed to maintain electrical equipment as required by NFPA 70, with two electrical panels obstructed by wheelchairs in a storage room, affecting one smoke compartment. This was confirmed by the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical System Maintenance Deficiency
E
K0919 K919: Meet requirements for the use of electrical equipment.
Short Summary

The facility failed to maintain the electrical system on one floor, as items were stored within 36 inches of electrical components in the 3rd floor storage room near the nurse's station. This was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsecured Junction Box Found in Room 104
E
K0919 K919: Meet requirements for the use of electrical equipment.
Short Summary

The facility failed to maintain its electrical systems, as evidenced by an unsecured junction box located above the suspended ceiling assembly in Room 104. This deficiency was confirmed during an exit interview with the Facility Administrator and the Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exposed Opening in Electrical Panel
D
K0919 K919: Meet requirements for the use of electrical equipment.
Short Summary

An electrical panel in the Biohazard Storage Room was found with an exposed opening due to a missing cover on one of the breaker spaces. Staff confirmed the issue and were previously unaware of the gap, which affected a portion of the facility and did not comply with required electrical safety codes.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Safety Deficiency in Mechanical Room
E
K0919 K919: Meet requirements for the use of electrical equipment.
Short Summary

The facility failed to maintain electrical safety standards as an extension cord was found plugged into a power strip in the 300-wing mechanical room. This was confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙