K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
F

Failure to Maintain Fire/Smoke Barrier Integrity in Electrical Room

Rehabilitation Center Of The Palm Beaches, TheWest Palm Beach, Florida Survey Completed on 05-06-2025

Summary

During an unannounced Fire & Life Safety revisit survey, surveyors observed that the facility failed to maintain proper fire and smoke barrier construction in accordance with NFPA 101 standards. Specifically, in Electrical Room #6, there were five open conduit penetrations through the south side 1-hour fire rated wall and three penetrations through the north side smoke wall. Additionally, thirteen areas on the east and south side 1-hour fire rated walls were found with red fire stopping mixed with a white putty, as well as areas with only white putty surrounding the penetrating conduit. The facility was unable to provide documentation confirming that the white putty used was approved for fire stopping purposes. These deficiencies were identified during a fire safety tour conducted with the Administrator and the Maintenance Director, who acknowledged the findings at the time of observation. The surveyors noted that these examples may not represent all unprotected penetrations in the facility's fire and smoke barriers, emphasizing the need for a thorough inspection of each barrier along its full length and height to ensure all penetrations are properly sealed. The report further states that every breach or penetration of a fire barrier must be appropriately repaired to restore the wall, ceiling, or floor to its original fire or smoke rated integrity. The penetrations in fire rated barriers are required to be sealed with a UL (Underwriters Laboratories) listed approved system. Photographic evidence was obtained to document the observed deficiencies.

Plan Of Correction

6/6/25 Preparation and/or execution of this plan of correction does not constitute admission or agreement of the provider of the truth of the alleged or conclusion set forth in the CMS measured star ratings. The plan of correction is prepared and executed solely because it is required by Federal and State Laws. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: 1. No residents were affected by this alleged deficient practice. How you will identify other residents having potential to be affected by the same deficient practice and what corrective action will be taken: 2. The facility will maintain the fire/smoke barrier construction in Electrical room #5. Penetration holes five (5) through the South side; three through the North side smoke wall; thirteen (13) areas on the East and South side 1-hour fire rated walls were resealed by a 3M trained professional in accordance with NFPA 101. A thorough inspection of each fire/smoke barrier will be conducted to ensure that all penetrations are found and properly sealed in accordance with NFPA 101. What measures will be put into place or what systematic changes you will make to ensure that the deficient practice does not recur: 3. Maintenance staff re-educated on ensuring fire/smoke barrier penetrations are inspected along its full length, height and properly sealed with a UL (Underwriters Laboratories) listed approved system. How the corrective action(s) will be monitored to ensure the deficient practice will not recur, i.e., what quality assurance program will be put in place: 4. Maintenance Director or Designee will report the findings of fire/smoke barrier penetrations audits to the QAA&C monthly times three months or until substantial compliance is met. Preparation and/or execution of this plan of correction does not constitute admission or agreement of the provider of the truth of the alleged or conclusion set forth in the CMS measured star ratings. The plan of correction is prepared and executed solely because it is required by Federal and State Laws. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: 1. No residents were affected by this alleged deficient practice. How you will identify other residents having potential to be affected by the same deficient practice and what corrective action will be taken: 2. The facility will maintain the fire/smoke barrier construction in Electrical room #5. Penetration holes five (5) through the South side; three through the North side smoke wall; thirteen (13) areas on the East and South side 1-hour fire rated walls were resealed by a 3M trained professional in accordance with NFPA 101. A thorough inspection of each fire/smoke barrier will be conducted to ensure that all penetrations are found and properly sealed in accordance with NFPA 101. What measures will be put into place or what systematic changes you will make to ensure that the deficient practice does not recur: 3. Maintenance staff re-educated on ensuring fire/smoke barrier penetrations are inspected along its full length, height and properly sealed with a UL (Underwriters Laboratories) listed approved system. How the corrective action(s) will be monitored to ensure the deficient practice will not recur, i.e., what quality assurance program will be put in place: 4. Maintenance Director or Designee will report the findings of fire/smoke barrier penetrations audits to the QAA&C monthly times three months or until substantial compliance is met.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0372 citations
Improper Repair of Smoke Barrier Penetrations in Multiple Smoke Compartments
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire-rated enclosures were not properly maintained, with penetrations in smoke barriers in several general storage rooms across multiple smoke compartments. The Maintenance Director stated that insulation and fiberglass were used to pack and cover these holes but could not confirm that the materials were approved for fire-rated construction. Inspectors observed penetrations covered with fiberglass and noted a hole in one fiberglass panel in a storage room, resulting in a deficiency under NFPA 101 requirements for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetrations in Smoke/Fire Barriers After Electrical Work
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire barriers in three of fourteen smoke compartments, including the hot water room, the barrier between the kitchen and a smoke compartment, and the smoke wall leading to the Alzheimer’s unit, had penetrations that were not properly fire-stopped. During the on-site interview, the Maintenance Director acknowledged that recent electrical work had been completed and that the contractor failed to seal these penetrations, resulting in noncompliance with NFPA 101 smoke barrier construction requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

A deficiency was identified when an unsealed penetration around data wires was observed in a smoke barrier wall on the second floor near the Rehabilitation Department. This issue was confirmed by the Administrator and Maintenance Director and affected one of two floors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unprotected Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

An unprotected penetration was found in a smoke barrier wall above double doors near the ADON/Medical Records Office, where blue and red wires passed through without proper protection. This issue, confirmed by the Director of Maintenance, affected two of twelve smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Wire Penetrations in Smoke Barrier
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that two wires passed unsealed through a smoke barrier above the ceiling near a resident corridor, with the Maintenance Director confirming unawareness of the sealing requirement. This deficiency had the potential to affect five residents and did not comply with NFPA 101-2012 standards for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Smoke Barrier Integrity per NFPA 101
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found multiple penetrations in smoke barriers sealed with non-fire-rated materials and one unsealed pipe, compromising the required fire and smoke resistance in several corridors and the attic. Maintenance leadership confirmed uncertainty about the materials used, and these deficiencies had the potential to affect all 39 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙