K0352 K352: Properly install and monitor supervisory attachments on automatic sprinkler systems.
F

Deficiency in Sprinkler System Supervisory Signal Monitoring

Eastwood Nursing CenterNegaunee, Michigan Survey Completed on 04-03-2025

Summary

The facility failed to ensure that automatic sprinkler system supervisory attachments were properly installed and monitored for integrity in accordance with NFPA 72 requirements. During a record review, it was found that the annual dry sprinkler inspection indicated the system had been capped and failed the inspection. Additionally, review of the fire alarm control panel (FACP) revealed that supervisory and/or trouble alarms were present, indicating that a portion of the sprinkler system had been shut down. These findings were confirmed by the Maintenance Director at the time of discovery. No information about specific residents or their medical conditions was provided in the report.

Plan Of Correction

1. The facility failed to maintain the automatic sprinkler system's supervisory attachment panel in proper working condition. 2. A malfunctioning supervisory panel compromises the effectiveness of the sprinkler system, potentially placing all residents, staff, and visitors at risk during a fire emergency. 3. Corrective actions are underway as follows: - Superiorland Electronics has been contacted and has ordered a new dry pipe valve and a new control valve equipped with a tamper switch. - Once parts are installed, the system will be tested to ensure full functionality. - The Maintenance Director has been educated on the importance of maintaining a properly functioning automatic sprinkler system supervisory panel. 4. The Maintenance Director is responsible for ensuring the panel remains operational and will report system status and maintenance updates to the Quality Assurance (QA) Committee.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0352 citations
Failure to Maintain Automatic Sprinkler System
F
K0352 K352: Properly install and monitor supervisory attachments on automatic sprinkler systems.
Short Summary

The facility failed to maintain the automatic sprinkler system, as evidenced by a supervisory signal indicating a fire pump loss of power on the fire alarm panel. This affected all three floors, and although a new fire pump was on site, it had not been installed. Previous fire alarm testing found no deficiencies. The issue was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsupervised Sprinkler System Valves
F
K0352 K352: Properly install and monitor supervisory attachments on automatic sprinkler systems.
Short Summary

The facility's sprinkler system was found to have two unsupervised outside screw and yoke (OS&Y) valves, which could prevent staff from knowing if the system was impaired. The domestic and sprinkler riser water line shared the same main water line from the city, and the main water riser room was located in a corporate office storage room. This deficiency had the potential to affect 88 residents.

Fine: $25,635
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙