K0754 K754: Provide properly sized and located linen or trash receptacles.
E

Non-compliance with NFPA 101 for Trash Container Storage

Transitions Healthcare Shook HomeChambersburg, Pennsylvania Survey Completed on 04-15-2025

Summary

The facility was found to be non-compliant with NFPA 101 standards regarding the storage of soiled linen and trash containers. During an observation on April 15, 2025, at 1:35 PM, it was noted that three 96-gallon shredder containers were stored in the ground floor lobby. This area did not have a 1-hour fire-rated protection, which is required for storing containers exceeding 32 gallons when not attended. The Director of Maintenance confirmed that the containers were not stored in a rated assembly, leading to the deficiency.

Plan Of Correction

The three 96-gallon shredder containers were moved to an area with 1 hour protected rating. Maintenance staff was educated a 1-hour protected rating space is required for storage of soiled-linen and trash containers exceeding 32 gallons. Director of Plant Operations or designee will audit 1 time a week for a month; if compliance is achieved; then random audits monthly of soiled-linen and trash containers exceeding 32 gallons are stored in a 1-hour protected space. Audit results will be reported at QAPI.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0754 citations
Improper Storage of Soiled-Linen and Trash Containers
E
K0754 K754: Provide properly sized and located linen or trash receptacles.
Short Summary

The facility did not adhere to NFPA 101 standards by storing soiled-linen and trash containers exceeding 32 gallons in the 1st floor corridor outside a resident's room, rather than in a 1-hour fire-rated room. This was confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with Soiled Linen and Trash Container Capacity
E
K0754 K754: Provide properly sized and located linen or trash receptacles.
Short Summary

The facility did not adhere to NFPA 101 standards for soiled linen and trash container capacity, as observed on the 3rd floor Central Bath near a resident room. Containers exceeded the 32-gallon limit in a 64-square foot area, confirmed by maintenance staff. A follow-up observation showed the issue remained uncorrected.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage of Soiled Linen in Facility
D
K0754 K754: Provide properly sized and located linen or trash receptacles.
Short Summary

The facility was found to be non-compliant with NFPA 101 standards as soiled linen was improperly stored on the floor under the sink in the 300 Wing Tub Room, outside a rated room or container. This was confirmed by the Director of Plant Operations.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with Soiled Linen and Trash Container Standards
E
K0754 K754: Provide properly sized and located linen or trash receptacles.
Short Summary

The facility failed to comply with NFPA 101 standards by allowing accumulated trash and soiled-linen containers to reach 32 gallons in a 64-square foot area on the 3rd floor Central Bath, near a resident room. This was outside a protected area, violating the requirement for such containers to be within a protected hazardous area if exceeding the specified capacity. The Director of Maintenance confirmed the oversight.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙